Hazardous Areas - Enclosure Hazardous areas are protected by a fire barrier having 1-hour fire resistance rating (with 3/4 hour fire rated doors) or an automatic fire extinguishing system in accordance with 8.7.1 or 19.3.5.9. When the approved automatic fire extinguishing system option is used, the areas shall be separated from other spaces by smoke resisting partitions and doors in accordance with 8.4. Doors shall be self-closing or automatic-closing and permitted to have nonrated or field-applied protective plates that do not exceed 48 inches from the bottom of the door. Describe the floor and zone locations of hazardous areas that are deficient in REMARKS. 19.3.2.1, 19.3.5.9
Area Automatic Sprinkler Separation N/A a. Boiler and Fuel-Fired Heater Rooms b. Laundries (larger than 100 square feet) c. Repair, Maintenance, and Paint Shops d. Soiled Linen Rooms (exceeding 64 gallons) e. Trash Collection Rooms (exceeding 64 gallons) f. Combustible Storage Rooms/Spaces (over 50 square feet) g. Laboratories (if classified as Severe Hazard - see K322)
|
Observations: Name: NEW BUILDING - Component: 02 - Tag: 0321
Based on observation and interview, the facility failed to maintain hazardous area enclosures in one instance, affecting one of six smoke compartments.
Findings include:
Observation on September 24, 2026, at 10:45 a.m., revealed the door to the linen storage room would not close and latch in the Mother of Perpetual Health Unit service hallway.
Interview with the facility administrator and the director of maintenance on September 24, 2026, at 1:00 p.m., confirmed the hazardous area enclosure deficiency.
| | Plan of Correction - To be completed: 10/13/2026
On the date of discovery (9/24/26), the door was adjusted by Maintenance, and now closes and latches correctly.
This door will be audited weekly x4 to assure continued compliance, and then monthly checks will resume.
Results will be documented and reviewed in the next QAPI meeting.
|
|