LITTLE SISTERS OF THE POOR - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000


Based on an Emergency Preparedness Survey completed on September 24, 2026, at Little Sisters of the Poor, it was determined there were no deficiencies identified with the requirements of 42 CFR 483.73.







 Plan of Correction:


Initial comments:Name: NEW BUILDING - Component: 02 - Tag: 0000


Facility ID #340302
Component 02
Main Building

Based on a Medicare/Medicaid Recertification Survey completed on September 24, 2026, it was determined that Little Sisters of the Poor was not in compliance with the following requirements of the Life Safety Code for an existing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a three-story, Type II (111), protected, non-combustible building, without a basement, that is fully sprinklered.











 Plan of Correction:


NFPA 101 STANDARD Hazardous Areas - Enclosure:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Hazardous Areas - Enclosure
Hazardous areas are protected by a fire barrier having 1-hour fire resistance rating (with 3/4 hour fire rated doors) or an automatic fire extinguishing system in accordance with 8.7.1 or 19.3.5.9. When the approved automatic fire extinguishing system option is used, the areas shall be separated from other spaces by smoke resisting partitions and doors in accordance with 8.4. Doors shall be self-closing or automatic-closing and permitted to have nonrated or field-applied protective plates that do not exceed 48 inches from the bottom of the door.
Describe the floor and zone locations of hazardous areas that are deficient in REMARKS.
19.3.2.1, 19.3.5.9

Area Automatic Sprinkler Separation N/A
a. Boiler and Fuel-Fired Heater Rooms
b. Laundries (larger than 100 square feet)
c. Repair, Maintenance, and Paint Shops
d. Soiled Linen Rooms (exceeding 64 gallons)
e. Trash Collection Rooms
(exceeding 64 gallons)
f. Combustible Storage Rooms/Spaces
(over 50 square feet)
g. Laboratories (if classified as Severe
Hazard - see K322)
Observations:
Name: NEW BUILDING - Component: 02 - Tag: 0321

Based on observation and interview, the facility failed to maintain hazardous area enclosures in one instance, affecting one of six smoke compartments.

Findings include:

Observation on September 24, 2026, at 10:45 a.m., revealed the door to the linen storage room would not close and latch in the Mother of Perpetual Health Unit service hallway.

Interview with the facility administrator and the director of maintenance on September 24, 2026, at 1:00 p.m., confirmed the hazardous area enclosure deficiency.










 Plan of Correction - To be completed: 10/13/2026

On the date of discovery (9/24/26), the door was adjusted by Maintenance, and now closes and latches correctly.

This door will be audited weekly x4 to assure continued compliance, and then monthly checks will resume.

Results will be documented and reviewed in the next QAPI meeting.

NFPA 101 STANDARD Subdivision of Building Spaces - Smoke Barrie:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Subdivision of Building Spaces - Smoke Barrier Doors
2012 EXISTING
Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors.
19.3.7.6, 19.3.7.8, 19.3.7.9
Observations:
Name: NEW BUILDING - Component: 02 - Tag: 0374

Based on observation and interview, the facility failed to maintain smoke barrier doors in two instances, affecting two of six smoke compartments.

Findings include:

Observation on September 24, 2026, revealed the following smoke barrier door deficiencies:

a) 9:25 a.m., The smoke doors to St. Michael's North Unit were not smoke-tight when closed. The doors had a gap measuring greater than 3/4 inch at the bottom;
b) 9:35 a.m., the smoke doors to the St. Michael's South Unit were not smoke-tight when closed. The doors had a gap measuring greater than 3/4 inch at the bottom.

Interview with the facility administrator and maintenance director on September 24, 2026, at 1:00 p.m., confirmed the smoke barrier door deficiencies.









 Plan of Correction - To be completed: 10/13/2026

On the date of discovery (9/24/26), door seals were replaced on the bottom of the identified doors by Maintenance.

These door will be audited weekly x4 to assure continued compliance, and then monthly checks will resume.

Results will be documented and reviewed in the next QAPI meeting.

NFPA 101 STANDARD Electrical Systems - Other:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Electrical Systems - Other
List in the REMARKS section any NFPA 99 Chapter 6 Electrical Systems requirements that are not addressed by the provided K-Tags, but are deficient. This information, along with the applicable Life Safety Code or NFPA standard citation, should be included on Form CMS-2567.
Chapter 6 (NFPA 99)
Observations:
Name: NEW BUILDING - Component: 02 - Tag: 0911

Based on observation and interview, the facility failed to maintain electrical systems in one instance, affecting one of six smoke compartments.

Findings include:

Observation on September 24, 2026, at 11:45 a.m., revealed carts were blocking access to the electrical panels in the St. Anne's Unit service hallway, near the kitchen area.

Interview with the facility administrator and maintenance director on September 24, 2026, at 1:00 p.m., confirmed there were items blocking the electrical panels.











 Plan of Correction - To be completed: 10/13/2026

On the date of discovery (9/24/26), the carts were removed from the identified service hallway.

Unit staff will be educated that no carts are to be stored in the identified service hallway.

This hallway will be audited weekly x4, then monthly thereafter, to assure compliance.

Results will be documented and reviewed in the next QAPI meeting.