Egress Doors Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements: CLINICAL NEEDS OR SECURITY THREAT LOCKING Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times. 18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6 SPECIAL NEEDS LOCKING ARRANGEMENTS Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation. 18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4 DELAYED-EGRESS LOCKING ARRANGEMENTS Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system. 18.2.2.2.4, 19.2.2.2.4 ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted. 18.2.2.2.4, 19.2.2.2.4 ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system. 18.2.2.2.4, 19.2.2.2.4
|
Observations: Name: MAIN BUILDING 01 - Component: 01 - Tag: 0222
Based on observation and interview, it was determined the facility failed to maintain delayed egress doors, affecting one of three levels in the facility.
Findings include:
Observation on August 13, 2024, at 10:36 a.m., revealed, on the first floor, the delayed egress door from Physical Therapy failed to alarm when pushed.
Exit interview with the Regional Director of Nursing and the Maintenance Director on August 13, 2024, at 11:00 a.m., confirmed the door failed to alarm.
| | Plan of Correction - To be completed: 10/01/2024
1. The delayed egress door from Physical Therapy was immediately repaired. 2. All delayed egress doors will be audited to ensure they properly alarm when pushed. 3. The Nursing Home Administrator (NHA) and maintenance Director was re-educated on the relevant regulations, with an emphasis on ensuring that delayed egress doors alarm appropriately when pushed open. 4. delayed egress doors will be audited once a month for the next three months to ensure that they are in proper working order. The results of these audits will be reported to the Quality Assurance/Performance Improvement (QAPI) Committee on a monthly basis until substantial compliance is achieved. The frequency of these audits will be adjusted based on the findings to ensure ongoing compliance.
|
|