Pennsylvania Department of Health
CONCORDIA AT RP HOME
Building Inspection Results

Note: If you need to change the font size, click the "View" menu at the top of the page, place the mouse over the "Text Size" menu item, and select the desired font size.

Severity Designations

Click here for definitions Click here for definitions Click here for definitions Click here for definitions
Minimal Citation - No Harm Minimal Harm Actual Harm Serious Harm
CONCORDIA AT RP HOME
Inspection Results For:

There are  43 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
CONCORDIA AT RP HOME - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000


Based on an Emergency Preparedness Survey completed on August 17, 2026, it was determined that Concordia at RP Home had deficiencies that have the potential for minimal harm as related to the requirements of 42 CFR 483.73.







 Plan of Correction:


403.748(a)(1)-(2), 416.54(a)(1)-(2), 418.113(a)(1)-(2), 441.184(a)(1)-(2), 482.15(a)(1)-(2), 483.475(a)(1)-(2), 483.73(a)(1)-(2), 484.102(a)(1)-(2), 485.542(a)(1)-(2), 485.625(a)(1)-(2), 485.68(a)(1)-(2), 485.727(a)(1)-(2), 485.920(a)(1)-(2), 486.360(a)(1)-(2), 491.12(a)(1)-(2), 494.62(a)(1)-(2) STANDARD Plan Based on All Hazards Risk Assessment:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§403.748(a)(1)-(2), §416.54(a)(1)-(2), §418.113(a)(1)-(2), §441.184(a)(1)-(2), §460.84(a)(1)-(2), §482.15(a)(1)-(2), §483.73(a)(1)-(2), §483.475(a)(1)-(2), §484.102(a)(1)-(2), §485.68(a)(1)-(2), §485.542(a)(1)-(2), §485.625(a)(1)-(2), §485.727(a)(1)-(2), §485.920(a)(1)-(2), §486.360(a)(1)-(2), §491.12(a)(1)-(2), §494.62(a)(1)-(2)

[(a) Emergency Plan. The [facility] must develop and maintain an emergency preparedness plan that must be reviewed, and updated at least every 2 years. The plan must do the following:]

(1) Be based on and include a documented, facility-based and community-based risk assessment, utilizing an all-hazards approach.*

(2) Include strategies for addressing emergency events identified by the risk assessment.

* [For Hospices at §418.113(a):] Emergency Plan. The Hospice must develop and maintain an emergency preparedness plan that must be reviewed, and updated at least every 2 years. The plan must do the following:
(1) Be based on and include a documented, facility-based and community-based risk assessment, utilizing an all-hazards approach.
(2) Include strategies for addressing emergency events identified by the risk assessment, including the management of the consequences of power failures, natural disasters, and other emergencies that would affect the hospice's ability to provide care.

*[For LTC facilities at §483.73(a):] Emergency Plan. The LTC facility must develop and maintain an emergency preparedness plan that must be reviewed, and updated at least annually. The plan must do the following:
(1) Be based on and include a documented, facility-based and community-based risk assessment, utilizing an all-hazards approach, including missing residents.
(2) Include strategies for addressing emergency events identified by the risk assessment.

*[For ICF/IIDs at §483.475(a):] Emergency Plan. The ICF/IID must develop and maintain an emergency preparedness plan that must be reviewed, and updated at least every 2 years. The plan must do the following:

(1) Be based on and include a documented, facility-based and community-based risk assessment, utilizing an all-hazards approach, including missing clients.
(2) Include strategies for addressing emergency events identified by the risk assessment.
Observations:
Name: - Component: -- - Tag: 0006

Based on document review and interview, the facility failed to maintain an emergency preparedness plan that included a facility-based and a community-based risk assessment for one of one plan.

Findings include:

Document review on August 17, 2026, at 8:25 a.m., revealed the facility-based and community-based risk assessments, that use an all-hazards approach, were not updated in the emergency preparedness plan within the last twelve months.

Interview with the facility administrator and maintenance director on August 17, 2026, at 12:30 p.m., confirmed the risk assessments were not updated for the emergency preparedness plan within the last twelve months.








 Plan of Correction - To be completed: 10/01/2026

1) Facility will update the Facility Hazard Risk assessment and will be on file with NHA.

2) QAPI Committee will receive the Facility Hazard Risk Assessment
Initial comments:Name: MAIN BUILDING 01 - Component: 01 - Tag: 0000


Facility ID #183002
Component 01
Main Building

Based on a Medicare/Medicaid Recertification Survey completed on August 17, 2026, it was determined that Concordia at RP Home was not in compliance with the following requirements of the Life Safety Code for an existing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a five-story, Type III (211), protected, ordinary building, without a basement, that is fully sprinklered.






 Plan of Correction:


NFPA 101 STANDARD Building Construction Type and Height:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Building Construction Type and Height
2012 EXISTING
Building construction type and stories meets Table 19.1.6.1, unless otherwise permitted by 19.1.6.2 through 19.1.6.7
19.1.6.4, 19.1.6.5

Construction Type
1 I (442), I (332), II (222) Any number of stories
non-sprinklered and sprinklered

2 II (111) One story non-sprinklered
Maximum 3 stories sprinklered

3 II (000) Not allowed non-sprinklered
4 III (211) Maximum 2 stories sprinklered
5 IV (2HH)
6 V (111)

7 III (200) Not allowed non-sprinklered
8 V (000) Maximum 1 story sprinklered
Sprinklered stories must be sprinklered throughout by an approved, supervised automatic system in accordance with section 9.7. (See 19.3.5)
Give a brief description, in REMARKS, of the construction, the number of stories, including basements, floors on which patients are located, location of smoke or fire barriers and dates of approval. Complete sketch or attach small floor plan of the building as appropriate.
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0161

Based on observation and interview, the facility failed to maintain the building construction type throughout the facility.

Findings include:

Observation on August 17, 2026, at 9:00 a.m., revealed the building to be a five-story, Type III (211), protected, ordinary building, that is fully sprinklered. This construction type is not permitted to be greater than two stories in height.

Interview with the facility administrator and director of facilities on August 17, 2026, at 12:30 p.m., confirmed the building construction type deficiency.






 Plan of Correction - To be completed: 10/01/2026

1) Waiver request will be re-submitted to the Department of Health for approval related to Building Type III.

2) Waiver request on file with NHA.
NFPA 101 STANDARD Doors with Self-Closing Devices:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Doors with Self-Closing Devices
Doors in an exit passageway, stairway enclosure, or horizontal exit, smoke barrier, or hazardous area enclosure are self-closing and kept in the closed position, unless held open by a release device complying with 7.2.1.8.2 that automatically closes all such doors throughout the smoke compartment or entire facility upon activation of:
* Required manual fire alarm system; and
* Local smoke detectors designed to detect smoke passing through the opening or a required smoke detection system; and
* Automatic sprinkler system, if installed; and
* Loss of power.
18.2.2.2.7, 18.2.2.2.8, 19.2.2.2.7, 19.2.2.2.8
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0223

Based on observation and interview, the facility failed to maintain self-closing doors in two instances, affecting two of twelve smoke compartments.

Findings include:

Observation on August 17, 2026, revealed the following self-closing door deficiencies:

a) 9:45 a.m., The linen supply closet door on the third floor failed to latch when tested;
b) 10:15 a.m., The door to the nutrition room on the third floor failed to latch when tested.

Interview with the facility administrator and maintenance director on August 17, 2026, at 12:30 p.m., confirmed the self-closing door deficiencies.







 Plan of Correction - To be completed: 10/01/2026

1) New Door and/or latch will be replaced at the linen supply closet to ensure self-closing.

2)New Door and/or latch will be replaced at the third floor nutrition room to ensure self-closing.


3) Maintenance will audit all doors and then audit quarterly to ensure all doors are self-closing as required by regulation.

NFPA 101 STANDARD Emergency Lighting:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Emergency Lighting
Emergency lighting of at least 1-1/2-hour duration is provided automatically in accordance with 7.9.
18.2.9.1, 19.2.9.1
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0291

Based on document review and interview, the facility failed to maintain emergency lighting in one instance, affecting the entire facility.

Findings include:

Document review on August 17, 2026, at 8:20 a.m., revealed the facility lacked documentation for the annual 90-minute test for the battery back-up emergency lighting.

Interview with the facility administrator and maintenance director on August 17, 2026, at 12:30 p.m. confirmed the facility lacked the testing documentation.








 Plan of Correction - To be completed: 10/01/2026

1) 90-Minute emergency test will be completed in September 2026 and then scheduled annually thereafter. Workorder on file with NHA

2) Maintenance Director re-educated to requirement for 90-Minute emergency test for battery back-up.

3) Reported to QAPI Committee
NFPA 101 STANDARD Hazardous Areas - Enclosure:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Hazardous Areas - Enclosure
Hazardous areas are protected by a fire barrier having 1-hour fire resistance rating (with 3/4 hour fire rated doors) or an automatic fire extinguishing system in accordance with 8.7.1 or 19.3.5.9. When the approved automatic fire extinguishing system option is used, the areas shall be separated from other spaces by smoke resisting partitions and doors in accordance with 8.4. Doors shall be self-closing or automatic-closing and permitted to have nonrated or field-applied protective plates that do not exceed 48 inches from the bottom of the door.
Describe the floor and zone locations of hazardous areas that are deficient in REMARKS.
19.3.2.1, 19.3.5.9

Area Automatic Sprinkler Separation N/A
a. Boiler and Fuel-Fired Heater Rooms
b. Laundries (larger than 100 square feet)
c. Repair, Maintenance, and Paint Shops
d. Soiled Linen Rooms (exceeding 64 gallons)
e. Trash Collection Rooms
(exceeding 64 gallons)
f. Combustible Storage Rooms/Spaces
(over 50 square feet)
g. Laboratories (if classified as Severe
Hazard - see K322)
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0321

Based on observation and interview, the facility failed to maintain hazardous area enclosures in four instances, affecting four of twelve smoke compartments.

Findings include:

Observation on August 17, 2026, revealed the following hazardous area enclosure deficiencies:

a) 10:35 a.m., The door to clean linen, by the laundry room, would not close and latch;
b) 10:50 a.m., The entrance door to the storage room in the kitchen was missing a door knob and was unable to close and latch;
c) 11:15 a.m., The door to a second storage room in the kitchen was blocked by five-gallon buckets of dish washer chemicals and a chair;
d) 11:35 a.m., The door to the electrical equipment and main fire panel room was propped open with a wooden shim.

Interview with the facility administrator and maintenance director on August 17, 2026, at 12:30 p.m., confirmed the hazardous area enclosure deficiencies.


















 Plan of Correction - To be completed: 10/01/2026

1) Clean Linen Door in Laundry room was repaired by maintenance on day of discovery. Workorder on file with NHA.

2) Doorknob replaced to kitchen storage room on day of discovery. Workorder on file with NHA.

3) Items removed upon discovery. Dining Service Staff re-educated to requirement. Proof of education on file with NHA.

4) Prop removed from door at mechanical room. Staff re-educated to not prop doors open. Signature sheets on file with NHA of proof of education.

5) QAPI notified of citation and repairs.
NFPA 101 STANDARD Fire Alarm System - Testing and Maintenance:This is a less serious (but not lowest level) deficiency and is isolated to the fewest number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0345

Based on observation and interview, the facility failed to maintain the fire alarm system in one instance, affecting one of twelve smoke compartments.

Findings include:

Observation on August 17, 2026, at 11:30 a.m., revealed the facility failed to reinstall a smoke detector after it was removed from its base (right side wall, if facing the dryers) in the laundry room.

Interview with the facility administrator and maintenance director on August 17, 2026, at 12:30 p.m., confirmed the fire alarm system deficiency.







 Plan of Correction - To be completed: 10/01/2026

1) New Smoke detector installed at location in the laundry room (facing dryer). Work order on file to demonstrates completion.

2) QAPI Committee aware of citation and repair.
NFPA 101 STANDARD Sprinkler System - Maintenance and Testing:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0353

Based on document review, observation, and interview, the facility failed to maintain the automatic sprinkler system in eight instances, affecting eight of twelve smoke compartments.

Findings include:

Observation on August 17, 2026, revealed the following automatic sprinkler deficiencies:

a) 8:55 a.m., The last sprinkler inspection revealed a faulty control valve and two sprinkler supervisory switches that need repaired/replaced in the main floor linen closet;
b) 10:15 a.m., There were six sprinkler heads missing escutcheon plates in the office area on the first floor;
c) 10:40 a.m., A sprinkler head was missing an escutcheon plate on the third floor, near the front stairwell;
d) 10:45 a.m., A sprinkler head was missing an escutcheon plate in the foyer;
e) 10:50 a.m., There was a missing ceiling tile in the foyer storage closet;
f) 11:00 a.m., There were some wires attached to a sprinkler line above the smoke doors near room 320;
g) 11:10 a.m., A ceiling tile was missing a corner piece and wire conduit was extending down through the broken corner piece of ceiling tile in the supply room on the third floor;
h) 11:20 a.m., There was a six-inch by six-inch penetration in the ceiling of the electrical equipment and fire panel room.

Interview with the facility administrator and maintenance director on August 17, 2026, at
12:30 p.m., confirmed the automatic sprinkler system deficiencies.











 Plan of Correction - To be completed: 10/01/2026

1) Mongovi Fire Service to repair faulty control valve and 2 sprinklery switches on 8/28/26. Workorder on file with NHA.

2) Escutcheon Plates replaced on office area to reported locations. Workers completing ceiling tile work re-educated to requirement of sprinkler heads.

3) Escutcheon Plates replaced on 3rd Floor nears front stairwell area to reported locations. Workers completing ceiling tile work re-educated to requirement of sprinkler heads.

4) Escutcheon Plates replaced on foyer to reported locations. Workers completing ceiling tile work re-educated to requirement of sprinkler heads.

5) All sprinkler head audited to ensure escutcheon places to ensure located in place.

6) Wires removed from the sprinkler line near room 320 upon discovery.

7) Supply room on the third floor ceiling tile will be replaced to cover conduit. work order available.

8. Penetration in the electoral equipment room applied to meet requirement. Work order on file with NHA.

9_ QAPI Committee aware of citations and updates


NFPA 101 STANDARD Corridor - Doors:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Corridor - Doors
Doors protecting corridor openings in other than required enclosures of vertical openings, exits, or hazardous areas resist the passage of smoke and are made of 1 3/4 inch solid-bonded core wood or other material capable of resisting fire for at least 20 minutes. Doors in fully sprinklered smoke compartments are only required to resist the passage of smoke. Corridor doors and doors to rooms containing flammable or combustible materials have positive latching hardware. Roller latches are prohibited by CMS regulation. These requirements do not apply to auxiliary spaces that do not contain flammable or combustible material.
Clearance between bottom of door and floor covering is not exceeding 1 inch. Powered doors complying with 7.2.1.9 are permissible if provided with a device capable of keeping the door closed when a force of 5 lbf is applied. There is no impediment to the closing of the doors. Hold open devices that release when the door is pushed or pulled are permitted. Nonrated protective plates of unlimited height are permitted. Dutch doors meeting 19.3.6.3.6 are permitted. Door frames shall be labeled and made of steel or other materials in compliance with 8.3, unless the smoke compartment is sprinklered. Fixed fire window assemblies are allowed per 8.3. In sprinklered compartments there are no restrictions in area or fire resistance of glass or frames in window assemblies.

19.3.6.3, 42 CFR Parts 403, 418, 460, 482, 483, and 485
Show in REMARKS details of doors such as fire protection ratings, automatics closing devices, etc.
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0363

Based on observation and interview, the facility failed to maintain doors protecting corridor openings in three instances, affecting two of twelve smoke compartments.

Findings include:

Observation on August 17, 2026, revealed the following corridor door deficiencies:

a) 9:25 a.m., The corridor door to resident room 304 failed to close and latch when tested;
b) 10:03 a.m., The corridor door to resident room 309 failed to close and latch when tested;
c) 10:55 a.m., The corridor door to resident room 320 was missing the door knob and failed to close and latch when tested.

Interview with the facility administrator and director of facilities on August 17, 2026, at 12:30 p.m., confirmed the corridor door deficiencies.








 Plan of Correction - To be completed: 10/01/2026

1) Corridor door to room 304 latches and closes upon discovery (removed enhanced barrier precaution supplies)

2) Corridor door to 309 latches and closes upon discovery (removed enhanced barrier precaution supplies)

3) Room 320 door was repaired with working doorknob 8/17/26. Work order on file with NHA.

4) Monitor resident doors monthly to ensure they latch and secure and with working doorknobs.

5) Staff re-educated to not store enhanced barrier precaution supplies on resident hallway door and to report when door is not in working condition. Education on file with NHA.

6) QAPI committee provided monitor and tracking
NFPA 101 STANDARD Subdivision of Building Spaces - Smoke Barrie:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Subdivision of Building Spaces - Smoke Barrier Doors
2012 EXISTING
Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors.
19.3.7.6, 19.3.7.8, 19.3.7.9
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0374

Based on observation and interview, the facility failed to maintain smoke barrier doors in one instance, affecting two of 12 smoke compartments.

Findings include:

Observation on August 17, 2026, at 11:25 a.m., revealed the smoke doors separating the foyer and therapy on the third floor failed to fully close and latch when tested.

Interview with the facility administrator and maintenance director on August 17, 2026, at 12:30 p.m., confirmed the smoke barrier doors failed to close and latch.






 Plan of Correction - To be completed: 10/01/2026

1) Door closuring has been ordered (8/14/26) ) and is scheduled to be installed on 10/20/2026.

2) Maintenance will audit all doors to ensure working properly and then will audit quarterly thereafter to ensure working condition.

NFPA 101 STANDARD Gas Equipment - Cylinder and Container Storag:This is a less serious (but not lowest level) deficiency and is isolated to the fewest number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99)
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0923

Based on observation and interview, the facility failed to properly store oxygen cylinders in one instance, affecting one of 12 smoke compartments.

Findings include:

Observation on August 17, 2026, at 11:02 a.m., revealed an unsecured "D" oxygen cylinder stored in the hallway outside of the O2 storage closet on the third floor.

Interview with the facility administrator and maintenance director on August 17, 2026, at 12:30 p.m., confirmed the cylinder storage deficiency.







 Plan of Correction - To be completed: 10/01/2026

1) Removed oxygen cylinder from hallway and stored in appropriate location upon discovery.

2) Staff training regarding oxygen storage and handling. Signature sheets on file with NHA.