Pennsylvania Department of Health
QUARRYVILLE PRESBYTERIAN RETIREMENT COMMUNITY
Building Inspection Results

Note: If you need to change the font size, click the "View" menu at the top of the page, place the mouse over the "Text Size" menu item, and select the desired font size.

Severity Designations

Click here for definitions Click here for definitions Click here for definitions Click here for definitions
Minimal Citation - No Harm Minimal Harm Actual Harm Serious Harm
QUARRYVILLE PRESBYTERIAN RETIREMENT COMMUNITY
Inspection Results For:

There are  41 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
QUARRYVILLE PRESBYTERIAN RETIREMENT COMMUNITY - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000
Based on an Emergency Preparedness Survey completed on August 24, 2026, at Quarryville Presbyterian Retirement Community, it was determined there were no deficiencies identified with the requirements of 42 CFR 483.73.
 Plan of Correction:


Initial comments:Name: MAIN BUILDING THOMPSON - Component: 01 - Tag: 0000
Facility ID #170102Component 01Building 01Based on a Medicare/Medicaid Recertification Survey completed on August 24, 2026, it was determined that Quarryville Presbyterian Retirement Community was not in compliance with the following requirements of the Life Safety Code for an existing health care occupancy.  Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).This is a three-story, Type II (222), fire resistive structure, with a basement, which is fully sprinklered.
 Plan of Correction:


NFPA 101 STANDARD Exit Signage:This is a less serious (but not lowest level) deficiency and is isolated to the fewest number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Exit Signage
2012 EXISTING
Exit and directional signs are displayed in accordance with 7.10 with continuous illumination also served by the emergency lighting system.
19.2.10.1
(Indicate N/A in one-story existing occupancies with less than 30 occupants where the line of exit travel is obvious.)
Observations:
Name: MAIN BUILDING THOMPSON - Component: 01 - Tag: 0293
Based on observation and interview, it was determined the facility failed to maintain the illumination of exit signage, affecting one of ten smoke compartments within the component.

Findings include:



1. Observation on August 24, 2026, at 12:38 PM, revealed the exit sign, located above the ground floor Laundry exterior exit door, was not illuminated.






Interview with the Vice President of Facility Services on August 24, 2026, at 12:38 PM, confirmed the light bulbs, within the exit sign, were not lit.





 Plan of Correction - To be completed: 09/22/2026

- The exit signage was replaced with a new lighted exit sign.
- The Maintenance team was re-educated by the Vice President of Facility Services on the requirements of this regulation.
- All exit signage will be audited monthly x three months and then monthly thereafter to ensure compliance with this regulation.
- This audit will be reviewed by the Facility Quality Assurance / Process Improvement team for further recommendations.

NFPA 101 STANDARD Rubbish Chutes, Incinerators, and Laundry Chu:This is a less serious (but not lowest level) deficiency and is isolated to the fewest number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Rubbish Chutes, Incinerators, and Laundry Chutes
2012 EXISTING
(1) Any existing linen and trash chute, including pneumatic rubbish and linen systems, that opens directly onto any corridor shall be sealed by fire resistive construction to prevent further use or shall be provided with a fire door assembly having a fire protection rating of 1-hour. All new chutes shall comply with 9.5.
(2) Any rubbish chute or linen chute, including pneumatic rubbish and linen systems, shall be provided with automatic extinguishing protection in accordance with 9.7.
(3) Any trash chute shall discharge into a trash collection room used for no other purpose and protected in accordance with 8.4. (Existing laundry chutes permitted to discharge into same room are protected by automatic sprinklers in accordance with 19.3.5.9 or 19.3.5.7.)
(4) Existing fuel-fed incinerators shall be sealed by fire resistive construction to prevent further use.
19.5.4, 9.5, 8.4, NFPA 82
Observations:
Name: MAIN BUILDING THOMPSON - Component: 01 - Tag: 0541
Based on observation and interview, it was determined the facility failed to maintain the positive latching of access doors to linen chutes, affecting one of ten of smoke compartments within the component.

Findings include:



1. Observation on August 24, 2026, at 12:20 PM, revealed the access door, to the 1st floor linen chute, located within Storage Room T170, failed to automatically close and positively latch within the frame.






Interview with the Vice President of Facility Services on August 24, 2026, at 12:20 PM, confirmed the access door failed to positively latch within the frame.





 Plan of Correction - To be completed: 09/22/2026

- The Storage Room T170 door latching mechanism was repaired to enable the door to properly close.
- All doors with the same time of latching mechanism were reviewed to ensure that they close properly.
- The Maintenance team was re-educated by the Vice President of Facility Services on the requirements of this regulation.
- The Assistant Administrator or Designee will re-educate the floor staff on the requirements of this regulation.
- All doors with this latching mechanism will be audited monthly x three months and then monthly thereafter to ensure compliance with this regulation.
- This audit will be reviewed by the Facility Quality Assurance / Process Improvement team for further recommendations.

NFPA 101 STANDARD Electrical Equipment - Power Cords and Extens:This is a less serious (but not lowest level) deficiency and is isolated to the fewest number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Electrical Equipment - Power Cords and Extension Cords
Power strips in a patient care vicinity are only used for components of movable patient-care-related electrical equipment (PCREE) assembles that have been assembled by qualified personnel and meet the conditions of 10.2.3.6. Power strips in the patient care vicinity may not be used for non-PCREE (e.g., personal electronics), except in long-term care resident rooms that do not use PCREE. Power strips for PCREE meet UL 1363A or UL 60601-1. Power strips for non-PCREE in the patient care rooms (outside of vicinity) meet UL 1363. In non-patient care rooms, power strips meet other UL standards. All power strips are used with general precautions. Extension cords are not used as a substitute for fixed wiring of a structure. Extension cords used temporarily are removed immediately upon completion of the purpose for which it was installed and meets the conditions of 10.2.4.
10.2.3.6 (NFPA 99), 10.2.4 (NFPA 99), 400-8 (NFPA 70), 590.3(D) (NFPA 70), TIA 12-5
Observations:
Name: MAIN BUILDING THOMPSON - Component: 01 - Tag: 0920
Based on observation and interview, it was determined the facility failed to monitor the use of surge suppressors, affecting one of ten smoke compartments within the component.

Findings include:



1. Observation on August 24, 2026, at 11:05 AM, revealed a surge suppressor, suspended from electrical wiring, located within the 2 East Lounge, by the television.






Interview with the Vice President of Facility Services on August 24, 2026, at 11:05 AM, confirmed the surge suppressor was suspended from electrical wiring.





 Plan of Correction - To be completed: 09/22/2026

- The power strip has been fastened to the wall.
- A facility audit was carried out to ensure that we were complying with this regulation.
- The Maintenance team was re-educated by the Vice President of Facility Services on the requirements of this regulation.
- The Assistant Administrator or Designee will re-educate the floor staff on the requirements of this regulation.
- Audits of power strips in the Resident Common Areas will take place monthly x three months and then monthly thereafter to ensure compliance with this regulation.
- This audit will be reviewed by the Facility Quality Assurance / Process Improvement team for further recommendations.