Pennsylvania Department of Health
PICKERING MANOR HOME
Building Inspection Results

Note: If you need to change the font size, click the "View" menu at the top of the page, place the mouse over the "Text Size" menu item, and select the desired font size.

Severity Designations

Click here for definitions Click here for definitions Click here for definitions Click here for definitions
Minimal Citation - No Harm Minimal Harm Actual Harm Serious Harm
PICKERING MANOR HOME
Inspection Results For:

There are  49 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
PICKERING MANOR HOME - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000
Based on an Emergency Preparedness Survey completed on September 22, 2025, it was determined that Pickering Manor Home was not in compliance with the requirements of 42 CFR 483.73.


 Plan of Correction:


403.748(a), 416.54(a), 418.113(a), 441.184(a), 482.15(a), 483.475(a), 483.73(a), 484.102(a), 485.542(a), 485.625(a), 485.68(a), 485.727(a), 485.920(a), 486.360(a), 491.12(a), 494.62(a) STANDARD Develop EP Plan, Review and Update Annually:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§403.748(a), §416.54(a), §418.113(a), §441.184(a), §460.84(a), §482.15(a), §483.73(a), §483.475(a), §484.102(a), §485.68(a), §485.542(a), §485.625(a), §485.727(a), §485.920(a), §486.360(a), §491.12(a), §494.62(a).

The [facility] must comply with all applicable Federal, State and local emergency preparedness requirements. The [facility] must develop establish and maintain a comprehensive emergency preparedness program that meets the requirements of this section. The emergency preparedness program must include, but not be limited to, the following elements:

(a) Emergency Plan. The [facility] must develop and maintain an emergency preparedness plan that must be [reviewed], and updated at least every 2 years. The plan must do all of the following:

* [For hospitals at §482.15 and CAHs at §485.625(a):] Emergency Plan. The [hospital or CAH] must comply with all applicable Federal, State, and local emergency preparedness requirements. The [hospital or CAH] must develop and maintain a comprehensive emergency preparedness program that meets the requirements of this section, utilizing an all-hazards approach.

* [For LTC Facilities at §483.73(a):] Emergency Plan. The LTC facility must develop and maintain an emergency preparedness plan that must be reviewed, and updated at least annually.

* [For ESRD Facilities at §494.62(a):] Emergency Plan. The ESRD facility must develop and maintain an emergency preparedness plan that must be [evaluated], and updated at least every 2 years.

.
Observations:
Name: - Component: -- - Tag: 0004 Based on documentation review and interview, it was determined the facility failed to ensure Emergency Preparedness Plan policies and procedures were reviewed and updated at least annually, affecting the entire facility. Findings include: 1. Review of documentation on September 22, 2025, between 8:30 a.m. and 10:30 a.m., revealed memorandums, transfer agreements, coalition agreements, and disaster operational procedures were out of date or no longer associated with the facility's Emergency Preparedness Plan. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 p.m., confirmed the documentation within the Emergency Preparedness Plan requires updates, revisions, and agreement removal which was not conducted within the annual review period.
 Plan of Correction - To be completed: 02/01/2026

E-0025
In response to the deficiency to provide arrangements with other facilities. NHA updated our transfer agreement with Pennswood Village's CEO/COF, and a new agreement has been sent to Pennswood to review and sign and return. To be completed and received by February 1, 2025.

403.748(a)(1)-(2), 416.54(a)(1)-(2), 418.113(a)(1)-(2), 441.184(a)(1)-(2), 482.15(a)(1)-(2), 483.475(a)(1)-(2), 483.73(a)(1)-(2), 484.102(a)(1)-(2), 485.542(a)(1)-(2), 485.625(a)(1)-(2), 485.68(a)(1)-(2), 485.727(a)(1)-(2), 485.920(a)(1)-(2), 486.360(a)(1)-(2), 491.12(a)(1)-(2), 494.62(a)(1)-(2) STANDARD Plan Based on All Hazards Risk Assessment:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
§403.748(a)(1)-(2), §416.54(a)(1)-(2), §418.113(a)(1)-(2), §441.184(a)(1)-(2), §460.84(a)(1)-(2), §482.15(a)(1)-(2), §483.73(a)(1)-(2), §483.475(a)(1)-(2), §484.102(a)(1)-(2), §485.68(a)(1)-(2), §485.542(a)(1)-(2), §485.625(a)(1)-(2), §485.727(a)(1)-(2), §485.920(a)(1)-(2), §486.360(a)(1)-(2), §491.12(a)(1)-(2), §494.62(a)(1)-(2)

[(a) Emergency Plan. The [facility] must develop and maintain an emergency preparedness plan that must be reviewed, and updated at least every 2 years. The plan must do the following:]

(1) Be based on and include a documented, facility-based and community-based risk assessment, utilizing an all-hazards approach.*

(2) Include strategies for addressing emergency events identified by the risk assessment.

* [For Hospices at §418.113(a):] Emergency Plan. The Hospice must develop and maintain an emergency preparedness plan that must be reviewed, and updated at least every 2 years. The plan must do the following:
(1) Be based on and include a documented, facility-based and community-based risk assessment, utilizing an all-hazards approach.
(2) Include strategies for addressing emergency events identified by the risk assessment, including the management of the consequences of power failures, natural disasters, and other emergencies that would affect the hospice's ability to provide care.

*[For LTC facilities at §483.73(a):] Emergency Plan. The LTC facility must develop and maintain an emergency preparedness plan that must be reviewed, and updated at least annually. The plan must do the following:
(1) Be based on and include a documented, facility-based and community-based risk assessment, utilizing an all-hazards approach, including missing residents.
(2) Include strategies for addressing emergency events identified by the risk assessment.

*[For ICF/IIDs at §483.475(a):] Emergency Plan. The ICF/IID must develop and maintain an emergency preparedness plan that must be reviewed, and updated at least every 2 years. The plan must do the following:

(1) Be based on and include a documented, facility-based and community-based risk assessment, utilizing an all-hazards approach, including missing clients.
(2) Include strategies for addressing emergency events identified by the risk assessment.
Observations:
Name: - Component: -- - Tag: 0006 Based on documentation review and interview, it was determined the facility failed to ensure the Emergency Preparedness Plan was based on and included a documented, facility-based, and community-based risk assessment, utilizing an all-hazards approach and include strategies for addressing emergency events identified by the risk assessment. Findings include: 1. Review of documentation on September 22, 2025, between 8:30 a.m. and 10:30 a.m., revealed the facility failed to provide the following emergency preparedness documentation: a. Facility's Emergency Preparedness Plan did not include a documented, facility-based and community-based risk assessment, utilizing an all-hazards approach and include strategies for addressing emergency events identified by the risk assessment. b. for example, the failed to establish and maintain a detailed and specific facility-based Carbon Monoxide emergency procedure. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 p.m., confirmed the missing documentation from the Emergency Preparedness Plan.
 Plan of Correction - To be completed: 01/06/2026

E-0006
In response to the deficiency regarding failing to establish a carbon monoxide plan The Director of Maintenance will establish and maintain a carbon monoxide procedure by 1-6-26 the Director of Maintenance will update the policy annually for compliance.

403.748(a)(4), 416.54(a)(4), 418.113(a)(4), 441.184(a)(4), 482.15(a)(4), 483.475(a)(4), 483.73(a)(4), 484.102(a)(4), 485.542(a)(4), 485.625(a)(4), 485.68(a)(4), 485.727(a)(5), 485.920(a)(4), 486.360(a)(4), 491.12(a)(4), 494.62(a)(4) STANDARD Local, State, Tribal Collaboration Process:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§403.748(a)(4), §416.54(a)(4), §418.113(a)(4), §441.184(a)(4), §460.84(a)(4), §482.15(a)(4), §483.73(a)(4), §483.475(a)(4), §484.102(a)(4), §485.68(a)(4), §485.542(a)(4), §485.625(a)(4), §485.727(a)(5), §485.920(a)(4), §486.360(a)(4), §491.12(a)(4), §494.62(a)(4)

[(a) Emergency Plan. The [facility] must develop and maintain an emergency preparedness plan that must be reviewed, and updated at least every 2 years [annually for LTC facilities]. The plan must do the following:]

(4) Include a process for cooperation and collaboration with local, tribal, regional, State, and Federal emergency preparedness officials' efforts to maintain an integrated response during a disaster or emergency situation. *

* [For ESRD facilities only at §494.62(a)(4)]: (4) Include a process for cooperation and collaboration with local, tribal, regional, State, and Federal emergency preparedness officials' efforts to maintain an integrated response during a disaster or emergency situation. The dialysis facility must contact the local emergency preparedness agency at least annually to confirm that the agency is aware of the dialysis facility's needs in the event of an emergency.
Observations:
Name: - Component: -- - Tag: 0009 Based on document review and interview, it was determined the facility failed to develop an Emergency Preparedness program, which includes a process for cooperation and collaboration with local, tribal, regional, State and Federal EP officials, affecting the entire facility. Findings include: 1. Review of documentation on September 22, 2025, between 8:30 a.m. and 10:30 a.m., revealed the facility failed to develop and maintain an emergency preparedness communication plan that included a process for cooperation and collaboration with local, tribal, regional, State, and Federal emergency preparedness officials' efforts to maintain an integrated response during a disaster or emergency situation, including documentation of the facility's efforts to contact such officials and, when applicable, of its participation in collaborative and cooperative planning efforts. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 pm, confirmed the missing documentation confirming external agency collaboration and planning efforts within the Emergency Preparedness Plan.
 Plan of Correction - To be completed: 02/01/2026

E-0009
In response to the deficiency regarding failing to develop a communication plan with local and state officials, the Director of Maintenance will send copies of the emergency preparedness plan to the local emergency services and the buck county office for approval of our emergency preparedness plan by 2-1-26. The Director of Maintenance will send copies of the emergency preparedness plan annually to local and state officials for compliance.

403.748(b), 416.54(b), 418.113(b), 441.184(b), 482.15(b), 483.475(b), 483.73(b), 484.102(b), 485.542(b), 485.625(b), 485.68(b), 485.727(b), 485.920(b), 486.360(b), 491.12(b), 494.62(b) STANDARD Development of EP Policies and Procedures:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
§403.748(b), §416.54(b), §418.113(b), §441.184(b), §460.84(b), §482.15(b), §483.73(b), §483.475(b), §484.102(b), §485.68(b), §485.542(b), §485.625(b), §485.727(b), §485.920(b), §486.360(b), §491.12(b), §494.62(b).

(b) Policies and procedures. [Facilities] must develop and implement emergency preparedness policies and procedures, based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, and the communication plan at paragraph (c) of this section. The policies and procedures must be reviewed and updated at least every 2 years.

*[For LTC facilities at §483.73(b):] Policies and procedures. The LTC facility must develop and implement emergency preparedness policies and procedures, based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, and the communication plan at paragraph (c) of this section. The policies and procedures must be reviewed and updated at least annually.

*Additional Requirements for PACE and ESRD Facilities:

*[For PACE at §460.84(b):] Policies and procedures. The PACE organization must develop and implement emergency preparedness policies and procedures, based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, and the communication plan at paragraph (c) of this section. The policies and procedures must address management of medical and nonmedical emergencies, including, but not limited to: Fire; equipment, power, or water failure; care-related emergencies; and natural disasters likely to threaten the health or safety of the participants, staff, or the public. The policies and procedures must be reviewed and updated at least every 2 years.

*[For ESRD Facilities at §494.62(b):] Policies and procedures. The dialysis facility must develop and implement emergency preparedness policies and procedures, based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, and the communication plan at paragraph (c) of this section. The policies and procedures must be reviewed and updated at least every 2 years. These emergencies include, but are not limited to, fire, equipment or power failures, care-related emergencies, water supply interruption, and natural disasters likely to occur in the facility's geographic area.
Observations:
Name: - Component: -- - Tag: 0013 Based on documentation review and interview, it was determined the facility failed to ensure emergency preparedness policies and procedures, based on the emergency plan, risk assessment and communication plan, were updated at least annually, affecting the entire facility. Findings include: 1. Review of documentation on September 22, 2025, between 8:30 a.m. and 10:30 a.m., revealed the facility's emergency preparedness policies and procedures including the emergency plan, risk assessment and communication plan had not been updated at least annually. a. for example, the facility failed to provide an earthquake response procedure based on an actual natural event occurring in 2024 and probability factor defined within the annual risk assessment. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 p.m., confirmed that Emergency procedures had not been reviewed based on risk assessment revisions, and that natural based events response procedures were not available.
 Plan of Correction - To be completed: 12/15/2025

E-0013
In response to the deficiency regarding providing procedures for earthquake response procedures, the Director of Maintenance will establish and maintain procedures for an earthquake response by 12-15-25 the Maintenance Director will update the policy annually for compliance.

403.748(b)(6), 416.54(b)(5), 418.113(b)(4), 441.184(b)(6), 482.15(b)(6), 483.475(b)(6), 483.73(b)(6), 484.102(b)(5), 485.542(b)(6), 485.625(b)(6), 485.68(b)(4), 485.727(b)(4), 485.920(b)(5), 491.12(b)(4), 494.62(b)(5) STANDARD Policies/Procedures-Volunteers and Staffing:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§403.748(b)(6), §416.54(b)(5), §418.113(b)(4), §441.184(b)(6), §460.84(b)(7), §482.15(b)(6), §483.73(b)(6), §483.475(b)(6), §484.102(b)(5), §485.68(b)(4), §485.542(b)(6), §485.625(b)(6), §485.727(b)(4), §485.920(b)(5), §491.12(b)(4), §494.62(b)(5).

[(b) Policies and procedures. The [facilities] must develop and implement emergency preparedness policies and procedures, based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, and the communication plan at paragraph (c) of this section. The policies and procedures must be reviewed and updated at least every 2 years [annually for LTC facilities]. At a minimum, the policies and procedures must address the following:]

(6) [or (4), (5), or (7) as noted above] The use of volunteers in an emergency or other emergency staffing strategies, including the process and role for integration of State and Federally designated health care professionals to address surge needs during an emergency.

*[For RNHCIs at §403.748(b):] Policies and procedures. (6) The use of volunteers in an emergency and other emergency staffing strategies to address surge needs during an emergency.

*[For Hospice at §418.113(b):] Policies and procedures. (4) The use of hospice employees in an emergency and other emergency staffing strategies, including the process and role for integration of State and Federally designated health care professionals to address surge needs during an emergency.
Observations:
Name: - Component: -- - Tag: 0024 Based on document review and interview, it was determined the facility failed to develop policies and procedures for the use of volunteers in an emergency, as part of the Emergency Preparedness plan, affecting the entire facility. Findings include: 1. Review of documentation on September 22, 2025, between 8:30 a.m. and 10:30 a.m., revealed the Facilities Emergency Preparedness Plan did not have policy and procedures addressing the use of volunteers in an emergency or other emergency staffing strategies, including the process and role for integration of State and Federally designated health care professionals to address surge needs during an emergency. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 p.m., confirmed the use of volunteer's policies during an emergency could not be defined with supporting documentation.
 Plan of Correction - To be completed: 12/05/2025

E-0024
In response to the deficiency that the emergency preparedness plan did not have a policy and procedures for the use of volunteers. Director of Maintenance and NHA reviewed current regulation and have developed policy and procedures for use of volunteers during an unplanned emergency event. Policy has been adopted in our Emergency Preparedness Manual as 12/05/2025

403.748(b)(7), 418.113(b)(5), 441.184(b)(7), 482.15(b)(7), 483.475(b)(7), 483.73(b)(7), 485.625(b)(7), 485.920(b)(6), 494.62(b)(6) STANDARD Arrangement with Other Facilities:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§403.748(b)(7), §418.113(b)(5), §441.184(b)(7), §460.84(b)(8), §482.15(b)(7), §483.73(b)(7), §483.475(b)(7), §485.625(b)(7), §485.920(b)(6), §494.62(b)(6).

[(b) Policies and procedures. The [facilities] must develop and implement emergency preparedness policies and procedures, based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, and the communication plan at paragraph (c) of this section. The policies and procedures must be reviewed and updated at least every 2 years [annually for LTC facilities]. At a minimum, the policies and procedures must address the following:]

*[For Hospices at §418.113(b), PRFTs at §441.184,(b) Hospitals at §482.15(b), and LTC Facilities at §483.73(b):] Policies and procedures. (7) [or (5)] The development of arrangements with other [facilities] [and] other providers to receive patients in the event of limitations or cessation of operations to maintain the continuity of services to facility patients.

*[For PACE at §460.84(b), ICF/IIDs at §483.475(b), CAHs at §486.625(b), CMHCs at §485.920(b) and ESRD Facilities at §494.62(b):] Policies and procedures. (7) [or (6), (8)] The development of arrangements with other [facilities] [or] other providers to receive patients in the event of limitations or cessation of operations to maintain the continuity of services to facility patients.

*[For RNHCIs at §403.748(b):] Policies and procedures. (7) The development of arrangements with other RNHCIs and other providers to receive patients in the event of limitations or cessation of operations to maintain the continuity of non-medical services to RNHCI patients.
Observations:
Name: - Component: -- - Tag: 0025 Based on documentation review and interview, it was determined the facility failed to provide arrangements with other facilities, affecting the entire component. Findings include: 1. Review of documentation on September 22, 2025, between 8:30 a.m. and 10:30 a.m., revealed the facility failed to provide arrangements with other facilities and other providers to receive patients in the event of limitations or cessation of operations to maintain the continuity of services to facility patients. a. Existing agreements could not define contractual timeline, transfer conditions, surge capacity policies, or contingency of operations for displacement. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 p.m., confirmed the transfer agreement deficiencies and missing supporting documentation within the Emergency Preparedness Plan.
 Plan of Correction - To be completed: 02/01/2026

E-0025
In response to the deficiency to provide arrangements with other facilities. NHA updated our transfer agreement with Pennswood Village's CEO/COF, and a new agreement has been sent to Pennswood to review and sign and return. To be completed and received by February 1, 2025.

403.748(d), 416.54(d), 418.113(d), 441.184(d), 482.15(d), 483.475(d), 483.73(d), 484.102(d), 485.542(d), 485.625(d), 485.68(d), 485.727(d), 485.920(d), 486.360(d), 491.12(d), 494.62(d) STANDARD EP Training and Testing:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
§403.748(d), §416.54(d), §418.113(d), §441.184(d), §460.84(d), §482.15(d), §483.73(d), §483.475(d), §484.102(d), §485.68(d), §485.542(d), §485.625(d), §485.727(d), §485.920(d), §486.360(d), §491.12(d), §494.62(d).

*[For RNCHIs at §403.748, ASCs at §416.54, Hospice at §418.113, PRTFs at §441.184, PACE at §460.84, Hospitals at §482.15, HHAs at §484.102, CORFs at §485.68, REHs at §485.542, CAHs at §486.625, "Organizations" under 485.727, CMHCs at §485.920, OPOs at §486.360, and RHC/FHQs at §491.12:] (d) Training and testing. The [facility] must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least every 2 years.

*[For LTC facilities at §483.73(d):] (d) Training and testing. The LTC facility must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least annually.

*[For ICF/IIDs at §483.475(d):] Training and testing. The ICF/IID must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least every 2 years. The ICF/IID must meet the requirements for evacuation drills and training at §483.470(i).

*[For ESRD Facilities at §494.62(d):] Training, testing, and orientation. The dialysis facility must develop and maintain an emergency preparedness training, testing and patient orientation program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training, testing and orientation program must be evaluated and updated at every 2 years.
Observations:
Name: - Component: -- - Tag: 0036 Based on documentation review and interview, it was determined the facility failed to develop an emergency preparedness training program that is based on the facility's emergency preparedness plan. The training and testing program must be reviewed and updated at least annually, affecting the entire facility. Findings include: 1. Review of documentation on September 22, 2025, between 8:30 a.m. and 10:30 a.m., revealed the facility failed to develop and maintain an emergency preparedness training and testing program that is based on the emergency plan. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 p.m., confirmed the facility failed to develop an emergency preparedness training program.
 Plan of Correction - To be completed: 12/12/2025

E-0036

In response to the deficiency to develop and maintain an emergency preparedness training and testing program based on the emergency plan. Director of Maintenance in-services all employees upon hire and annually on Pickering Manor's fire safety and Emergency preparedness policy and procedures, and all employees are given a post test. Effective December 12, 2025

403.748(d)(1), 416.54(d)(1), 418.113(d)(1), 441.184(d)(1), 482.15(d)(1), 483.475(d)(1), 483.73(d)(1), 484.102(d)(1), 485.542(d)(1), 485.625(d)(1), 485.68(d)(1), 485.727(d)(1), 485.920(d)(1), 486.360(d)(1), 491.12(d)(1) STANDARD EP Training Program:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§403.748(d)(1), §416.54(d)(1), §418.113(d)(1), §441.184(d)(1), §460.84(d)(1), §482.15(d)(1), §483.73(d)(1), §483.475(d)(1), §484.102(d)(1), §485.68(d)(1), §485.542(d)(1), §485.625(d)(1), §485.727(d)(1), §485.920(d)(1), §486.360(d)(1), §491.12(d)(1).

*[For RNCHIs at §403.748, ASCs at §416.54, Hospitals at §482.15, ICF/IIDs at §483.475, HHAs at §484.102, REHs at §485.542, "Organizations" under §485.727, OPOs at §486.360, RHC/FQHCs at §491.12:]
(1) Training program. The [facility] must do all of the following:
(i) Initial training in emergency preparedness policies and procedures to all new and existing staff, individuals providing services under arrangement, and volunteers, consistent with their expected roles.
(ii) Provide emergency preparedness training at least every 2 years.
(iii) Maintain documentation of all emergency preparedness training.
(iv) Demonstrate staff knowledge of emergency procedures.
(v) If the emergency preparedness policies and procedures are significantly updated, the [facility] must conduct training on the updated policies and procedures.

*[For Hospices at §418.113(d):] (1) Training. The hospice must do all of the following:
(i) Initial training in emergency preparedness policies and procedures to all new and existing hospice employees, and individuals providing services under arrangement, consistent with their expected roles.
(ii) Demonstrate staff knowledge of emergency procedures.
(iii) Provide emergency preparedness training at least every 2 years.
(iv) Periodically review and rehearse its emergency preparedness plan with hospice employees (including nonemployee staff), with special emphasis placed on carrying out the procedures necessary to protect patients and others.
(v) Maintain documentation of all emergency preparedness training.
(vi) If the emergency preparedness policies and procedures are significantly updated, the hospice must conduct training on the updated policies and
procedures.

*[For PRTFs at §441.184(d):] (1) Training program. The PRTF must do all of the following:
(i) Initial training in emergency preparedness policies and procedures to all new and existing staff, individuals providing services under arrangement, and volunteers, consistent with their expected roles.
(ii) After initial training, provide emergency preparedness training every 2 years.
(iii) Demonstrate staff knowledge of emergency procedures.
(iv) Maintain documentation of all emergency preparedness training.
(v) If the emergency preparedness policies and procedures are significantly updated, the PRTF must conduct training on the updated policies and procedures.

*[For PACE at §460.84(d):] (1) The PACE organization must do all of the following:
(i) Initial training in emergency preparedness policies and procedures to all new and existing staff, individuals providing on-site services under arrangement, contractors, participants, and volunteers, consistent with their expected roles.
(ii) Provide emergency preparedness training at least every 2 years.
(iii) Demonstrate staff knowledge of emergency procedures, including informing participants of what to do, where to go, and whom to contact in case of an emergency.
(iv) Maintain documentation of all training.
(v) If the emergency preparedness policies and procedures are significantly updated, the PACE must conduct training on the updated policies and procedures.

*[For LTC Facilities at §483.73(d):] (1) Training Program. The LTC facility must do all of the following:
(i) Initial training in emergency preparedness policies and procedures to all new and existing staff, individuals providing services under arrangement, and volunteers, consistent with their expected role.
(ii) Provide emergency preparedness training at least annually.
(iii) Maintain documentation of all emergency preparedness training.
(iv) Demonstrate staff knowledge of emergency procedures.

*[For CORFs at §485.68(d):](1) Training. The CORF must do all of the following:
(i) Provide initial training in emergency preparedness policies and procedures to all new and existing staff, individuals providing services under arrangement, and volunteers, consistent with their expected roles.
(ii) Provide emergency preparedness training at least every 2 years.
(iii) Maintain documentation of the training.
(iv) Demonstrate staff knowledge of emergency procedures. All new personnel must be oriented and assigned specific responsibilities regarding the CORF's emergency plan within 2 weeks of their first workday. The training program must include instruction in the location and use of alarm systems and signals and firefighting equipment.
(v) If the emergency preparedness policies and procedures are significantly updated, the CORF must conduct training on the updated policies and procedures.

*[For CAHs at §485.625(d):] (1) Training program. The CAH must do all of the following:
(i) Initial training in emergency preparedness policies and procedures, including prompt reporting and extinguishing of fires, protection, and where necessary, evacuation of patients, personnel, and guests, fire prevention, and cooperation with firefighting and disaster authorities, to all new and existing staff, individuals providing services under arrangement, and volunteers, consistent with their expected roles.
(ii) Provide emergency preparedness training at least every 2 years.
(iii) Maintain documentation of the training.
(iv) Demonstrate staff knowledge of emergency procedures.
(v) If the emergency preparedness policies and procedures are significantly updated, the CAH must conduct training on the updated policies and procedures.

*[For CMHCs at §485.920(d):] (1) Training. The CMHC must provide initial training in emergency preparedness policies and procedures to all new and existing staff, individuals providing services under arrangement, and volunteers, consistent with their expected roles, and maintain documentation of the training. The CMHC must demonstrate staff knowledge of emergency procedures. Thereafter, the CMHC must provide emergency preparedness training at least every 2 years.
Observations:
Name: - Component: -- - Tag: 0037 Based on documentation review and interview, it was determined the facility failed to maintain a training program that is based on the facility's emergency preparedness plan, affecting the entire facility. Findings include: 1. Review of documentation on September 22, 2025, between 8:30 a.m. and 10:30 a.m., revealed the facility failed to perform training to the emergency preparedness plan that included the following: a. Initial training in emergency preparedness policies and procedures to all new and existing staff, individuals providing services under arrangement, and volunteers, consistent with their expected role. b. Provide emergency preparedness training at least annually. c. Maintain documentation of the training. d. Demonstrate staff knowledge of emergency procedures. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 p.m., confirmed the missing training records supporting the Emergency Preparedness Plan.
 Plan of Correction - To be completed: 12/12/2025

E-0037 In response to the deficiency in performing training. The Director of Maintenance will provide copies of employees' in-service training records with updated Emergency Preparedness policies and procedures. Effective December 12, 2025.
403.748(d)(2), 416.54(d)(2), 418.113(d)(2), 441.184(d)(2), 482.15(d)(2), 483.475(d)(2), 483.73(d)(2), 484.102(d)(2), 485.542(d)(2), 485.625(d)(2), 485.68(d)(2), 485.727(d)(2), 485.920(d)(2), 486.360(d)(2), 491.12(d)(2), 494.62(d)(2) STANDARD EP Testing Requirements:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§416.54(d)(2), §418.113(d)(2), §441.184(d)(2), §460.84(d)(2), §482.15(d)(2), §483.73(d)(2), §483.475(d)(2), §484.102(d)(2), §485.68(d)(2), §485.542(d)(2), §485.625(d)(2), §485.727(d)(2), §485.920(d)(2), §491.12(d)(2), §494.62(d)(2).

*[For ASCs at §416.54, CORFs at §485.68, REHs at §485.542, OPO, "Organizations" under §485.727, CMHCs at §485.920, RHCs/FQHCs at §491.12, and ESRD Facilities at §494.62]:

(2) Testing. The [facility] must conduct exercises to test the emergency plan annually. The [facility] must do all of the following:

(i) Participate in a full-scale exercise that is community-based every 2 years; or
(A) When a community-based exercise is not accessible, conduct a facility-based functional exercise every 2 years; or
(B) If the [facility] experiences an actual natural or man-made emergency that requires activation of the emergency plan, the [facility] is exempt from engaging in its next required community-based or individual, facility-based functional exercise following the onset of the actual event.
(ii) Conduct an additional exercise at least every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [facility's] response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the [facility's] emergency plan, as needed.

*[For Hospices at 418.113(d):]
(2) Testing for hospices that provide care in the patient's home. The hospice must conduct exercises to test the emergency plan at least annually. The hospice must do the following:
(i) Participate in a full-scale exercise that is community based every 2 years; or
(A) When a community based exercise is not accessible, conduct an individual facility based functional exercise every 2 years; or
(B) If the hospice experiences a natural or man-made emergency that requires activation of the emergency plan, the hospital is exempt from engaging in its next required full scale community-based exercise or individual facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.

(3) Testing for hospices that provide inpatient care directly. The hospice must conduct exercises to test the emergency plan twice per year. The hospice must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual facility-based functional exercise; or
(B) If the hospice experiences a natural or man-made emergency that requires activation of the emergency plan, the hospice is exempt from engaging in its next required full-scale community based or facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop led by a facilitator that includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the hospice's response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the hospice's emergency plan, as needed.


*[For PRFTs at §441.184(d), Hospitals at §482.15(d), CAHs at §485.625(d):]
(2) Testing. The [PRTF, Hospital, CAH] must conduct exercises to test the emergency plan twice per year. The [PRTF, Hospital, CAH] must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or
(B) If the [PRTF, Hospital, CAH] experiences an actual natural or man-made emergency that requires activation of the emergency plan, the [facility] is exempt from engaging in its next required full-scale community based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an [additional] annual exercise or and that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, a facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [facility's] response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the [facility's] emergency plan, as needed.

*[For PACE at §460.84(d):]
(2) Testing. The PACE organization must conduct exercises to test the emergency plan at least annually. The PACE organization must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or
(B) If the PACE experiences an actual natural or man-made emergency that requires activation of the emergency plan, the PACE is exempt from engaging in its next required full-scale community based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the PACE's response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the PACE's emergency plan, as needed.

*[For LTC Facilities at §483.73(d):]
(2) The [LTC facility] must conduct exercises to test the emergency plan at least twice per year, including unannounced staff drills using the emergency procedures. The [LTC facility, ICF/IID] must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise.
(B) If the [LTC facility] facility experiences an actual natural or man-made emergency that requires activation of the emergency plan, the LTC facility is exempt from engaging its next required a full-scale community-based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [LTC facility] facility's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the [LTC facility] facility's emergency plan, as needed.

*[For ICF/IIDs at §483.475(d)]:
(2) Testing. The ICF/IID must conduct exercises to test the emergency plan at least twice per year. The ICF/IID must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or.
(B) If the ICF/IID experiences an actual natural or man-made emergency that requires activation of the emergency plan, the ICF/IID is exempt from engaging in its next required full-scale community-based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the ICF/IID's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the ICF/IID's emergency plan, as needed.

*[For HHAs at §484.102]
(d)(2) Testing. The HHA must conduct exercises to test the emergency plan at
least annually. The HHA must do the following:
(i) Participate in a full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise every 2 years; or.
(B) If the HHA experiences an actual natural or man-made emergency that requires activation of the emergency plan, the HHA is exempt from engaging in its next required full-scale community-based or individual, facility based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the HHA's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the HHA's emergency plan, as needed.

*[For OPOs at §486.360]
(d)(2) Testing. The OPO must conduct exercises to test the emergency plan. The OPO must do the following:
(i) Conduct a paper-based, tabletop exercise or workshop at least annually. A tabletop exercise is led by a facilitator and includes a group discussion, using a narrated, clinically relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan. If the OPO experiences an actual natural or man-made emergency that requires activation of the emergency plan, the OPO is exempt from engaging in its next required testing exercise following the onset of the emergency event.
(ii) Analyze the OPO's response to and maintain documentation of all tabletop exercises, and emergency events, and revise the [RNHCI's and OPO's] emergency plan, as needed.

*[ RNCHIs at §403.748]:
(d)(2) Testing. The RNHCI must conduct exercises to test the emergency plan. The RNHCI must do the following:
(i) Conduct a paper-based, tabletop exercise at least annually. A tabletop exercise is a group discussion led by a facilitator, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(ii) Analyze the RNHCI's response to and maintain documentation of all tabletop exercises, and emergency events, and revise the RNHCI's emergency plan, as needed.
Observations:
Name: - Component: -- - Tag: 0039 Based on document review and interview, it was determined the facility failed to test the Emergency Plan twice per year, affecting the entire facility. Findings include: 1. Review of documentation on September 22, 2025, between 8:30 a.m. and 10:30 a.m., revealed the facility failed to conduct an annual full-scale community-based exercise or when not accessible, a facility-based exercise, in addition to a second full-scale community-based or facility-based exercise or acceptable substitution, which includes documented analyzation of the drills and exercises, and revisions to the emergency plan when necessary. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 p.m., confirmed the external involvement exercise had not been performed.
 Plan of Correction - To be completed: 09/30/2025

E-0039
In response to the deficiency in conducting a full-scale community-based exercise the Director of Maintenance held a full-scale community-based exercise on 9-30-25. Director of Maintenance will monitor and ensure that Pickering Manor remains in compliance with the two required disaster drills yearly.

Initial comments:Name: EAST, WEST, NEW ADDITION COMBINED - Component: 01 - Tag: 0000
Facility ID# 160802

Component 01

East &; West Wings

 

Based on a Medicare/Medicaid Recertification Survey completed on September 22, 2025, it was determined that Pickering Manor Home - East &; West Wings was not in compliance with the following requirements of the Life Safety Code for an existing Nursing health care occupancy.  Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

 

This is a one-story, Type II (000), unprotected non-combustible building, with a basement, that is fully sprinklered.


 Plan of Correction:


NFPA 101 STANDARD Fire Alarm System - Testing and Maintenance:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72
Observations:
Name: EAST, WEST, NEW ADDITION COMBINED - Component: 01 - Tag: 0345 Based on observation and interview, it was determined the facility failed to maintain fire alarm system components, affecting one of three levels. Findings include: 1. Observation on September 22, 2025, at 10:00 am, revealed, in Skilled emergency exit stairs by room 218, an inactive fire alarm pull was present in addition to the active pull station. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 pm, confirmed the additional fire alarm pull station.
 Plan of Correction - To be completed: 12/05/2025

K-0345
In response to the deficiency that revealed, in Skilled emergency exit stairs by room 218, an inactive fire alarm pull was present in addition to the active pull station. Director of Maintenance had fire protection service come out and test both pull station and determined which pull station functioning. The non-functioning pull station has been removed by the Fire protection service. Completion date 12/05/2025.

NFPA 101 STANDARD Sprinkler System - Maintenance and Testing:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25
Observations:
Name: EAST, WEST, NEW ADDITION COMBINED - Component: 01 - Tag: 0353 Based on observation and interview it was determined the facility failed to ensure the automatic sprinkler system and its components were maintained, affecting the entire facility. Findings include: 1. Observation made on September 22, 2025, at 11:06 a.m., revealed lower-level sprinkler riser room labeled LL003, sprinkler riser gauges indicated inspection dates for 2019 and the facility documentation from the sprinkler company confirmed valve inspections conducted in 2024. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 p.m., confirmed the mislabeled gauges.
 Plan of Correction - To be completed: 12/05/2025

K-0353
In response to the deficiency that revealed that a lower-level sprinkler riser room labeled LL003, sprinkler riser gauges indicated inspection dates for 2019 and the facility documentation from the sprinkler company confirmed valve inspections conducted in 2024. The Director of Maintenance had the fire Protection service came out and replaced the expired sprinkler riser gauges. Completion date 12/05/2025.

NFPA 101 STANDARD Electrical Systems - Essential Electric Syste:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70)
Observations:
Name: EAST, WEST, NEW ADDITION COMBINED - Component: 01 - Tag: 0918 Based on document review and interview, it was determined the facility failed to maintain and inspect the emergency generator, affecting the entire facility. Findings include: 1. Review of documentation on September 22, 2025, between 8:30 a.m. and 10:30 a.m., revealed the annual fuel quality report had not been conducted, affecting the entire facility. a. Facility generator report states that third party contractor does not perform lab-based fuel quality testing, only field testing. This service needs to be requested by the facility. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 p.m., confirmed the annual fuel quality test had not been performed.
 Plan of Correction - To be completed: 01/15/2026

K-0918
In response to the deficiency regarding field diesel testing on the generator the Director of maintenance will have the generator service company complete a fuel sample tested by a lab by 1-15-26 the Director of Maintenance will monitor for future fuel samples to be lab tested on future annual fuel tests.

Initial comments:Name: NEW REHAB ADDITION - Component: 04 - Tag: 0000
Facility ID# 160802

Component 04

New Rehab Addition

 

Based on a Medicare/Medicaid Recertification Survey completed on September 22, 2025, it was determined that Pickering Manor Home - New Rehab Addition was not in compliance with the following requirements of the Life Safety Code for a new Nursing health care occupancy.  Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

 

This is a two-story, Type II (111), protected, non-combustible building, with a basement, that is fully sprinklered.


 Plan of Correction:


NFPA 101 STANDARD Electrical Systems - Essential Electric Syste:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70)
Observations:
Name: NEW REHAB ADDITION - Component: 04 - Tag: 0918 Based on document review and interview, it was determined the facility failed to maintain and inspect the emergency generator, affecting the entire facility. Findings include: 1. Review of documentation on September 22, 2025, between 8:30 a.m. and 10:30 a.m., revealed the annual fuel quality report had not been conducted, affecting the entire facility. a. Facility generator report states that third party contractor does not perform lab-based fuel quality testing, only field testing. This service needs to be requested by the facility. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 p.m., confirmed the annual fuel quality test had not been performed.
 Plan of Correction - To be completed: 01/15/2026

K-0918

In response to the deficiency regarding field diesel testing on the generator the Director of maintenance will have the generator service company complete a fuel sample tested by a lab by 1-15-26 the Director of Maintenance will monitor for future fuel samples to be lab tested on future annual fuel tests.
NFPA 101 STANDARD Gas Equipment - Cylinder and Container Storag:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99)
Observations:
Name: NEW REHAB ADDITION - Component: 04 - Tag: 0923 Based on observation and interview, it was determined that the facility failed to maintain oxygen storage requirements, affecting one of three levels. Findings Include: 1. Observation on September 22, 2025, at 9:45 am, revealed upper-level skilled oxygen storage room had multiple 2- unsealed penetrations, right side wall. Exit Interview with the Administrator and Maintenance Director on September 22, 2025, at 1:15 pm, confirmed the unsealed penetrations.
 Plan of Correction - To be completed: 12/15/2025

K-0923
In response to the deficiency regarding unsealed penetrations in the skilled oxygen room the Director of Maintenance will have the unsealed penetrations sealed by 12-15-25 using ul W-L-1001 The Director of Maintenance will in-service Maintenance staff to be observant for penetrations during their rounds.