Inspection Results For:

There are  52 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
MEADOWS NURSING AND REHABILITATION CENTER - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000
Based on an Emergency Preparedness Survey completed on July 30, 2026, at Meadows Nursing and Rehabilitation Center, it was determined there were no deficiencies identified with the requirements of 42 CFR 483.73.


 Plan of Correction:


Initial comments:Name: MAIN BUILDING 01 - Component: 01 - Tag: 0000
Facility ID# 137302

Component 01

Main Building

 

Based on a Medicare/Medicaid Recertification Survey completed on July 30, 2026, it was determined that Meadows Nursing and Rehabilitation Center was not in compliance with the following requirements of the Life Safety Code for an existing health care occupancy.  Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

 

This is a three story, Type II (222), fire resistive building, that is fully sprinklered.


 Plan of Correction:


NFPA 101 STANDARD Alcohol Based Hand Rub Dispenser (ABHR):This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Alcohol Based Hand Rub Dispenser (ABHR)
ABHRs are protected in accordance with 8.7.3.1, unless all conditions are met:
* Corridor is at least 6 feet wide
* Maximum individual dispenser capacity is 0.32 gallons (0.53 gallons in suites) of fluid and 18 ounces of Level 1 aerosols
* Dispensers shall have a minimum of 4-foot horizontal spacing
* Not more than an aggregate of 10 gallons of fluid or 135 ounces aerosol are used in a single smoke compartment outside a storage cabinet, excluding one individual dispenser per room
* Storage in a single smoke compartment greater than 5 gallons complies with NFPA 30
* Dispensers are not installed within 1 inch of an ignition source
* Dispensers over carpeted floors are in sprinklered smoke compartments
* ABHR does not exceed 95 percent alcohol
* Operation of the dispenser shall comply with Section 18.3.2.6(11) or 19.3.2.6(11)
* ABHR is protected against inappropriate access
18.3.2.6, 19.3.2.6, 42 CFR Parts 403, 418, 460, 482, 483, and 485
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0325 Based on observation and interview it was determined that the facility failed to monitor the installation of alcohol-based hand rub dispensers (ABHR) in one of eight smoke compartments, Findings include: 1. Observation on July 30, 2026, at 11:25 am revealed an alcohol-based hand rub dispenser installed directly over an electrical outlet between rooms 321 and 323 on the third floor. Interview at the time of the exit conference with Facility Maintenance representatives on July 30, 2026, at 1:00 pm confirmed the ABHR was installed directly over an ignition source
 Plan of Correction - To be completed: 09/24/2026

a. ABHR (Alcohol Based Hand Rub) dispenser has been relocated in compliance with NFPA 101, Life/Safety Code.
b. Maintenance will be provided education on proper placement of ABHR dispensers.
c. A facility wide audit of all ABHR has been conducted to ensure that they are placed appropriately throughout the hallways.
d. Results of findings will be brought to Quality Assurance Committee for review and recommendations.
e. Corrective Action Date: September 24, 2026

NFPA 101 STANDARD Subdivision of Building Spaces - Smoke Barrie:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Subdivision of Building Spaces - Smoke Barrier Construction
2012 EXISTING
Smoke barriers shall be constructed to a 1/2-hour fire resistance rating per 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations in fully ducted HVAC systems where an approved sprinkler system is installed for smoke compartments adjacent to the smoke barrier.
19.3.7.3, 8.6.7.1(1)
Describe any mechanical smoke control system in REMARKS.
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0372 Based on observation and interview it was determined the facility failed to maintain the required fire resistance rating of smoke barrier walls in one location affecting two smoke compartments. Findings include: 1. Observation on July 30, 2026, at 11:53 am revealed an open penetration of the smoke barrier wall above the double doors near room 226 on the 2nd floor. Interview at the time of the exit conference with Facility Maintenance representatives on July 30, 2026, at 1:00 pm confirmed there was an open penetration around a group of blue communication wires.
 Plan of Correction - To be completed: 09/24/2026

a. Penetration will be sealed on both sides of smoke barrier wall, using 3M Fire Barrier Sealant (CP 25 WB).
b. Maintenance/Contractors will be educated/instructed on the importance of checking and sealing of all penetrations in fire barrier walls. Penetration inspections are on preventive maintenance logs.
c. Results of findings will be brought to Quality Assurance Committee for review and recommendations.
d. Corrective Action Date: September 24, 2026

NFPA 101 STANDARD Soiled Linen and Trash Containers:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Soiled Linen and Trash Containers
Soiled linen or trash collection receptacles shall not exceed 32 gallons in capacity. The average density of container capacity in a room or space shall not exceed 0.5 gallons/square feet. A total container capacity of 32 gallons shall not be exceeded within any 64 square feet area. Mobile soiled linen or trash collection receptacles with capacities greater than 32 gallons shall be located in a room protected as a hazardous area when not attended.
Containers used solely for recycling are permitted to be excluded from the above requirements where each container is less than or equal to 96 gallons unless attended, and containers for combustibles are labeled and listed as meeting FM Approval Standard 6921 or equivalent.
18.7.5.7, 19.7.5.7
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0754 Based on observation and interview it was determined that the facility failed to monitor for the capacity of trash containers stored outside of a hazardous area in one of eight smoke compartments. Findings include: 1. Observation on July 30, 2026, at 12:16 pm revealed two 32-gallon trash cans being stored together in the beauty shop on the 1st floor. Interview at the time of the exit conference with Facility Maintenance representatives on July 30, 2026, at 1:00 pm confirmed there was more than 32 gallons of trash container capacity being stored in less than 64 square feet within the beauty shop.
 Plan of Correction - To be completed: 09/24/2026

a. Trash/Soiled Linen containers have been moved/placed in accordance to NFPA 101 regulations.
b. Maintenance, Enviromental, Beauty Salon Operator and staff will be educated on proper storage of Trash/Soiled containers.
c. A facility wide audit will be conducted to ensure compliance with NEPA 101 Soiled Linen and Trash Containers regulation.
e. Results of findings will be brought to Quality Assurance Committee for review and recommendations.
f. Corrective Action Date: September 24, 2026

NFPA 101 STANDARD Electrical Equipment - Power Cords and Extens:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Electrical Equipment - Power Cords and Extension Cords
Power strips in a patient care vicinity are only used for components of movable patient-care-related electrical equipment (PCREE) assembles that have been assembled by qualified personnel and meet the conditions of 10.2.3.6. Power strips in the patient care vicinity may not be used for non-PCREE (e.g., personal electronics), except in long-term care resident rooms that do not use PCREE. Power strips for PCREE meet UL 1363A or UL 60601-1. Power strips for non-PCREE in the patient care rooms (outside of vicinity) meet UL 1363. In non-patient care rooms, power strips meet other UL standards. All power strips are used with general precautions. Extension cords are not used as a substitute for fixed wiring of a structure. Extension cords used temporarily are removed immediately upon completion of the purpose for which it was installed and meets the conditions of 10.2.4.
10.2.3.6 (NFPA 99), 10.2.4 (NFPA 99), 400-8 (NFPA 70), 590.3(D) (NFPA 70), TIA 12-5
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0920 Based on observation and interview it was determined that the facility failed to monitor for the unauthorized use of power taps and outlet multipliers in one of eight smoke compartments. Findings include: 1. Observation on July 30, 2026, at 11:49 am revealed an outlet multiplier was in use in room 220, on the 2nd floor. Interview at the time of the exit conference with Facility Maintenance representatives on July 30, 2026, at 1:00 pm confirmed an outlet multiplier was powering charging cords near the resident bed.
 Plan of Correction - To be completed: 09/24/2026

a. Outlet multiplier has been removed from room #220.
b. Maintenance and staff will be re-educated on the proper use of PCREE and the importance of not allowing or use outlet multipliers.
c. A facility wide audit has been completed as part of electrical maintenance inspections to ensure there are no outlet multipliers.
d. Results of findings will be brought to Quality Assurance Committee for review and recommendations.
e. Corrective Action Date: September 24, 2026