Pennsylvania Department of Health
ASBURY HEALTH CENTER
Building Inspection Results

Note: If you need to change the font size, click the "View" menu at the top of the page, place the mouse over the "Text Size" menu item, and select the desired font size.

Severity Designations

Click here for definitions Click here for definitions Click here for definitions Click here for definitions
Minimal Citation - No Harm Minimal Harm Actual Harm Serious Harm
ASBURY HEALTH CENTER
Inspection Results For:

There are  49 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
ASBURY HEALTH CENTER - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000


Based on an Emergency Preparedness Survey completed on August 10, 2026, at Asbury Health Center, it was determined there were no deficiencies identified with the requirements of 42 CFR 483.73.







 Plan of Correction:


Initial comments:Name: MAIN BUILDING 01 - Component: 01 - Tag: 0000


Facility ID #132602
Component 01
Skilled Nursing Buildings 6 and 7

Based on a Medicare/Medicaid Recertification Survey completed on August 10, 2026, it was determined that Asbury Health Center was not in compliance with the following requirements of the Life Safety Code for an existing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a three-story, Type II (222), fire resistive building, with a penthouse, that is fully sprinklered.




 Plan of Correction:


NFPA 101 STANDARD Doors with Self-Closing Devices:This is a less serious (but not lowest level) deficiency and is isolated to the fewest number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Doors with Self-Closing Devices
Doors in an exit passageway, stairway enclosure, or horizontal exit, smoke barrier, or hazardous area enclosure are self-closing and kept in the closed position, unless held open by a release device complying with 7.2.1.8.2 that automatically closes all such doors throughout the smoke compartment or entire facility upon activation of:
* Required manual fire alarm system; and
* Local smoke detectors designed to detect smoke passing through the opening or a required smoke detection system; and
* Automatic sprinkler system, if installed; and
* Loss of power.
18.2.2.2.7, 18.2.2.2.8, 19.2.2.2.7, 19.2.2.2.8
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0223

Based on observation and interview, the facility failed to maintain self-closing doors in two instances, affecting one of 19 smoke compartments.

Findings include:

Observation on August 10, 2026, revealed the following self-closing door deficiencies:

a) 10:00 a.m., The door to housekeeping closet #7329 failed to fully close and latch when tested;
b) 11:02 a.m., The door to a closet in the physical therapy room had the self-closure device removed.

Interview with the facility administrator and the maintenance director on August 10, 2026, at 2:30 p.m., confirmed the self-closing door deficiencies.






 Plan of Correction - To be completed: 09/16/2026

The two doors identified will be fixed before POC completion date. All other self-closing doors were inspected and confirmed to be functioning. NHA or designee will educate maintenance director on door requirements and routine inspections. Maintenance director or designee will audit self-closing doors and submit repair orders as needed weekly x 4 weeks, then monthly x 2 months. Results will be reviewed and adjusted at QAPI as needed.
NFPA 101 STANDARD Hazardous Areas - Enclosure:This is a less serious (but not lowest level) deficiency and is isolated to the fewest number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Hazardous Areas - Enclosure
Hazardous areas are protected by a fire barrier having 1-hour fire resistance rating (with 3/4 hour fire rated doors) or an automatic fire extinguishing system in accordance with 8.7.1 or 19.3.5.9. When the approved automatic fire extinguishing system option is used, the areas shall be separated from other spaces by smoke resisting partitions and doors in accordance with 8.4. Doors shall be self-closing or automatic-closing and permitted to have nonrated or field-applied protective plates that do not exceed 48 inches from the bottom of the door.
Describe the floor and zone locations of hazardous areas that are deficient in REMARKS.
19.3.2.1, 19.3.5.9

Area Automatic Sprinkler Separation N/A
a. Boiler and Fuel-Fired Heater Rooms
b. Laundries (larger than 100 square feet)
c. Repair, Maintenance, and Paint Shops
d. Soiled Linen Rooms (exceeding 64 gallons)
e. Trash Collection Rooms
(exceeding 64 gallons)
f. Combustible Storage Rooms/Spaces
(over 50 square feet)
g. Laboratories (if classified as Severe
Hazard - see K322)
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0321

Based on observation and interview, the facility failed to maintain hazardous area enclosures in one instance, affecting one of 19 smoke compartments.

Findings include:

Observation on August 10, 2026, at 10:10 a.m., revealed the door to the boiler room was missing the self-closing device.

Interview with the facility administrator and maintenance director on August 10, 2026, at 2:30 p.m., confirmed the hazardous area enclosure deficiency.






 Plan of Correction - To be completed: 09/16/2026

The boiler room self-closing device will be repaired by POC completion date.
All other self-closing doors boiler room doors were inspected and confirmed to be functioning. NHA or designee will educate maintenance director on boiler door requirements and routine inspections. Maintenance director or designee will audit self-closing boiler doors and submit repair orders as needed weekly x 4 weeks, then monthly x 2 months. Results will be reviewed and adjusted at QAPI as needed.
NFPA 101 STANDARD Fire Alarm System - Testing and Maintenance:This is a less serious (but not lowest level) deficiency and is isolated to the fewest number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0345

Based on observation and interview, the facility failed to maintain the fire alarm system in one instance, affecting one of 19 smoke compartments.

Findings Include:

Observation on August 10, 2026, at 11:15 a.m., revealed the fire alarm panel indicated there was a missing photoelectric smoke detector.

Interview with the facility administrator and maintenance director on August 10, 2026, at 2:30 p.m., confirmed the fire alarm system deficiency.






 Plan of Correction - To be completed: 09/16/2026

Fire alarm system will be repaired before POC completion date. NHA or designee will educate maintenance director on fire system requirements and routine inspections. Maintenance director or designee will audit the fire alarm system and submit repair orders as needed weekly x 4 weeks, then monthly x 2 months. Results will be reviewed and adjusted at QAPI as needed.
NFPA 101 STANDARD Sprinkler System - Maintenance and Testing:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0353

Based on document review, observation, and interview, the facility failed to maintain the automatic sprinkler system in three instances, affecting Buildings 6 and 7.

Findings include:

Observation on August 10, 2026, revealed the following automatic sprinkler deficiencies:

a) 9:55 a.m., The facility could not provide documentation for an annual and semi-annual wet sprinkler system test for Building 6;
b) 10:05 a.m., The facility could not provide documentation for an annual and semi-annual wet sprinkler system test for Building 7;
c) 11:55 a.m., There was a penetration surrounding pipes in the ceiling of the 6-2 boiler room, which would allow the passage of heat and smoke, affecting operation of the fire sprinkler system.

Interview with the facility administrator and maintenance director on August 10, 2026, at
2:30 p.m., confirmed the automatic sprinkler system deficiencies.












 Plan of Correction - To be completed: 09/16/2026

The automatic sprinkler system will be fixed before POC completion date. NHA or designee will educate maintenance director on sprinkler system requirements and routine inspections. Maintenance director or designee will audit the sprinkler system and submit repair orders as needed weekly x 4 weeks, then monthly x 2 months. Results will be reviewed and adjusted at QAPI as needed.
NFPA 101 STANDARD Subdivision of Building Spaces - Smoke Barrie:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Subdivision of Building Spaces - Smoke Barrier Doors
2012 EXISTING
Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors.
19.3.7.6, 19.3.7.8, 19.3.7.9
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0374

Based on observation and interview, the facility failed to maintain smoke barrier doors in one instance, affecting two of 19 smoke compartments.

Findings include:

Observation on August 10, 2026, at 10:35 a.m., revealed the smoke barrier doors next to room 7334 in Building 6 were equipped with a self-latching device and failed to self-close and latch when tested.

Interview with the facility administrator and maintenance director on August 10, 2026, at 2:30 p.m., confirmed the smoke barrier door deficiency.








 Plan of Correction - To be completed: 09/16/2026

The two barrier doors identified will be fixed before POC completion date. All other barrier doors were inspected and confirmed to be functioning. NHA or designee will educate maintenance director on barrier requirements and routine inspections. Maintenance director or designee will audit barrier doors and submit repair orders as needed weekly x 4 weeks, then monthly x 2 months. Results will be reviewed and adjusted at QAPI as needed.
NFPA 101 STANDARD Electrical Systems - Other:This is a less serious (but not lowest level) deficiency and is isolated to the fewest number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Electrical Systems - Other
List in the REMARKS section any NFPA 99 Chapter 6 Electrical Systems requirements that are not addressed by the provided K-Tags, but are deficient. This information, along with the applicable Life Safety Code or NFPA standard citation, should be included on Form CMS-2567.
Chapter 6 (NFPA 99)
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0911

Based on observation and interview, the facility failed to maintain protection of electrical wiring in one instance, affecting one of 19 smoke compartments.

Findings include:

Observation on August 10, 2026, at 12:45 p.m., revealed an electrical panel in boiler room 6-2 was missing a circuit breaker or filler plate.

Interview with the facility administrator and maintenance director on August 10, 2026, at 2:30 p.m., confirmed a circuit breaker or filler plate was missing from the electrical panel.











 Plan of Correction - To be completed: 09/16/2026

The electrical wiring identified will be fixed before POC completion date. All other electrical wiring in boiler room were inspected and confirmed to be functioning. NHA or designee will educate maintenance director on electrical wiring requirements and routine inspections. Maintenance director or designee will boiler room electrical panel and submit repair orders as needed weekly x 4 weeks, then monthly x 2 months. Results will be reviewed and adjusted at QAPI as needed.
NFPA 101 STANDARD Gas Equipment - Cylinder and Container Storag:This is a less serious (but not lowest level) deficiency and is isolated to the fewest number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Gas Equipment - Cylinder and Container Storage
Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed, and ventilated in accordance with 5.1.3.3.2 and 5.1.3.3.3.
>300 but <3,000 cubic feet
Storage locations are outdoors in an enclosure or within an enclosed interior space of non- or limited- combustible construction, with door (or gates outdoors) that can be secured. Oxidizing gases are not stored with flammables, and are separated from combustibles by 20 feet (5 feet if sprinklered) or enclosed in a cabinet of noncombustible construction having a minimum 1/2 hr. fire protection rating.
Less than or equal to 300 cubic feet
In a single smoke compartment, individual cylinders available for immediate use in patient care areas with an aggregate volume of less than or equal to 300 cubic feet are not required to be stored in an enclosure. Cylinders must be handled with precautions as specified in 11.6.2.
A precautionary sign readable from 5 feet is on each door or gate of a cylinder storage room, where the sign includes the wording as a minimum "CAUTION: OXIDIZING GAS(ES) STORED WITHIN NO SMOKING."
Storage is planned so cylinders are used in order of which they are received from the supplier. Empty cylinders are segregated from full cylinders. When facility employs cylinders with integral pressure gauge, a threshold pressure considered empty is established. Empty cylinders are marked to avoid confusion. Cylinders stored in the open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA 99)
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0923

Based on observation and interview, the facility failed to properly store oxygen cylinders in one instance, affecting one of 19 smoke compartments.

Findings include:

Observation on August 10, 2026, at 1:35 p.m., revealed an unsecured "D" oxygen cylinder stored in the hallway outside of room 6420 in Building 6.

Interview with the facility administrator and maintenance director on August 10, 2026, at 2:30 p.m., confirmed the cylinder storage deficiency.









 Plan of Correction - To be completed: 09/16/2026

The oxygen tanks identified were returned to proper storage. The other areas of facility were audited for improperly stored oxygen tanks and none identified. NHA or designee will educate maintenance director on oxygen storage and routine inspections. Maintenance director or designee will audit oxygen storage for compliance weekly x 4 weeks, then monthly x 2 months. Results will be reviewed and adjusted at QAPI as needed.