Inspection Results For:

There are  45 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
JEWEL HEALTHCARE AND REHABILITATION CENTER - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000


Based on an Emergency Preparedness Survey completed on September 21, 2026, at Jewel Healthcare and Rehabilitation Center, it was determined there were no deficiencies identified with the requirements of 42 CFR 483.73.




 Plan of Correction:


Initial comments:Name: MAIN BUILDING 01 - Component: 01 - Tag: 0000


Facility ID# 121802
Component 01
Main Building

Based on a Medicare/Medicaid Recertification Survey completed on September 21, 2026, it was determined that Jewel Healthcare and Rehabilitation Center was not in compliance with the following requirements of the Life Safety Code for an existing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a three story, Type II (222), fire resistive building, with basement, that is fully sprinklered.






 Plan of Correction:


NFPA 101 STANDARD Hazardous Areas - Enclosure:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Hazardous Areas - Enclosure
Hazardous areas are protected by a fire barrier having 1-hour fire resistance rating (with 3/4 hour fire rated doors) or an automatic fire extinguishing system in accordance with 8.7.1 or 19.3.5.9. When the approved automatic fire extinguishing system option is used, the areas shall be separated from other spaces by smoke resisting partitions and doors in accordance with 8.4. Doors shall be self-closing or automatic-closing and permitted to have nonrated or field-applied protective plates that do not exceed 48 inches from the bottom of the door.
Describe the floor and zone locations of hazardous areas that are deficient in REMARKS.
19.3.2.1, 19.3.5.9

Area Automatic Sprinkler Separation N/A
a. Boiler and Fuel-Fired Heater Rooms
b. Laundries (larger than 100 square feet)
c. Repair, Maintenance, and Paint Shops
d. Soiled Linen Rooms (exceeding 64 gallons)
e. Trash Collection Rooms
(exceeding 64 gallons)
f. Combustible Storage Rooms/Spaces
(over 50 square feet)
g. Laboratories (if classified as Severe
Hazard - see K322)
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0321

Based on observation and interview, it was determined the facility failed to maintain hazardous area enclosures, affecting one of four floors.

Findings include:

1. Observation on September 21, 2026, between 9:37 a.m., and 9:42 a.m., revealed the following basement-level hazardous area enclosure doors required adjustment to fully latch:

a. 9:37 a.m., Laundry Personal Clothing Room.
b. 9:42 a.m., Soiled Linen.

Exit interview on September 21, 2026, between 11:00 a.m., and 11:10 a.m., with the Facilities Manager, confirmed the hazardous area enclosure deficiencies.




 Plan of Correction - To be completed: 10/20/2026

1. Laundry clothing room, and soiled linen rooms doors now latch according to code

2. Director of maintenance and or designee will conduct random audits confirming doors latch per code.

3. Director of maintenance and or designee will be educated on ensuring doors latch per code.

4. Director of maintenance and or designee will conduct random weekly audits for one month, then monthly for 3 months confirming doors latch per code, finding to be discussed in qapi.
NFPA 101 STANDARD Sprinkler System - Maintenance and Testing:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0353

Based on observation and interview, it was determined the facility failed to maintain the automatic sprinkler system in multiple locations, affecting one of four floors.

Findings include:

1. Observation on September 21, 2026, between 9:35 a.m., and 10:01 a.m., revealed ceiling tiles lacking in the following basement-level locations:

a. 9:35 a.m., Expansion Tank Room.
b. 9:40 a.m., Soiled Utility Room.
c. 9:44 a.m., DON's Office.
d. 9:48 a.m., Back-up Linen.
e. 9:50 a.m., Delivery entrance.
f. 9:55 a.m., Therapy HVAC Room.
f. 10:01 a.m., Dietary.

Exit interview on September 21, 2026, between 11:00 a.m., and 11:10 a.m., with the Facilities Manager, confirmed the automatic sprinkler system deficiencies.




 Plan of Correction - To be completed: 10/20/2026

1. All identified ceiling tiles are fixed.

2. Director of maintenance and or designee will conduct random audits ensuring ceiling tiles are in their proper place.

3. Director of maintenance and or designee will be educated ensuring ceiling tiles are in their proper place.

4. Director of maintenance and or designee will conduct random weekly audits for one month, then monthly for 3 months ensuring ceiling are in their proper place .findings to be discussed in qapi.
NFPA 101 STANDARD Portable Fire Extinguishers:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Portable Fire Extinguishers
Portable fire extinguishers are selected, installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers.
18.3.5.12, 19.3.5.12, NFPA 10
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0355

Based on observation and interview, it was determined the facility failed to maintain portable fire extinguishers in one location, affecting one of four floors.

Findings include:

1. Observation on September 21, 2026, at 9:55 a.m., revealed the K-Type, portable fire extinguisher, located within Dietary, resided on a shelf, in lieu of the provided mounting bracket.

Exit interview on September 21, 2026, between 11:00 a.m., and 11:10 a.m., with the Facilities Manager, confirmed the portable fire extinguisher deficiency.




 Plan of Correction - To be completed: 10/20/2026

1. Fire extinguisher in dietary was placed in proper place.

2. Director of maintenance and or designee will be educated ensuring fire extinguishers are in their proper place.

3. Director of maintenance and or designee will conduct random weekly audits for one month, then monthly for 3 months ensuring fire extinguishers are mounted in their proper place. Findings to be discussed in qapi.
NFPA 101 STANDARD Corridor - Doors:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Corridor - Doors
Doors protecting corridor openings in other than required enclosures of vertical openings, exits, or hazardous areas resist the passage of smoke and are made of 1 3/4 inch solid-bonded core wood or other material capable of resisting fire for at least 20 minutes. Doors in fully sprinklered smoke compartments are only required to resist the passage of smoke. Corridor doors and doors to rooms containing flammable or combustible materials have positive latching hardware. Roller latches are prohibited by CMS regulation. These requirements do not apply to auxiliary spaces that do not contain flammable or combustible material.
Clearance between bottom of door and floor covering is not exceeding 1 inch. Powered doors complying with 7.2.1.9 are permissible if provided with a device capable of keeping the door closed when a force of 5 lbf is applied. There is no impediment to the closing of the doors. Hold open devices that release when the door is pushed or pulled are permitted. Nonrated protective plates of unlimited height are permitted. Dutch doors meeting 19.3.6.3.6 are permitted. Door frames shall be labeled and made of steel or other materials in compliance with 8.3, unless the smoke compartment is sprinklered. Fixed fire window assemblies are allowed per 8.3. In sprinklered compartments there are no restrictions in area or fire resistance of glass or frames in window assemblies.

19.3.6.3, 42 CFR Parts 403, 418, 460, 482, 483, and 485
Show in REMARKS details of doors such as fire protection ratings, automatics closing devices, etc.
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0363

Based on observation and interview, it was determined the facility failed to maintain corridor openings in ten locations, affecting four of four floors.

Findings include:

1. Observation on September 21, 2026, between 9:41 a.m., and 10:33 a.m., revealed the following:

a. 9:41 a.m., a hole within the Back-Up Linen Room door.
b. 9:48 a.m., Dietary door held open by unapproved means (door chock).
c. 9:59 a.m., first floor, Clean Linen Room door required adjustment to latch.
d. 10:02 a.m., first floor, Employees Only Room door required adjustment to latch.
e. 10:08 a.m., first floor, Clean Utility required adjustment to latch.
f. 10:12 a.m., second floor Resident Room 204 required adjustment to latch.
f. 10:14 a.m., second floor, Resident Room 207 required adjustment to latch.
g. 10:15 a.m., second floor, Resident Room 208 required adjustment to latch.
h. 10:23 a.m., second floor, Clean Linen required adjustment to latch.
i. 10:33 a.m., third floor Resident Room 312 door would not close, nor latch.

Exit interview on September 21, 2026, between 11:00 a.m., and 11:10 a.m., with the Facilities Manager, confirmed the corridor opening deficiencies.





 Plan of Correction - To be completed: 10/20/2026

1. Identified incorrect corridor openings were fixed.

2. Director of maintenance and or designee will be educated ensuring corridor openings are being held per code.

3. Director of maintenance and or designee will conduct random weekly audits for one month, then monthly for 3 ensuring doors are being latched per code.findings to be discussed in qapi
NFPA 101 STANDARD HVAC:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
HVAC
Heating, ventilation, and air conditioning shall comply with 9.2 and shall be installed in accordance with the manufacturer's specifications.
18.5.2.1, 19.5.2.1, 9.2




Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0521

Based on observation and interview, it was determined the facility failed to maintain heating, ventilation, and air conditioning in two instances, affecting one of four floors.

Findings include:

1. Observation on September 21, 2026, between 9:34 a.m., and 9:50 a.m., revealed portable air conditioning unit exhaust vented into the interstitial spaces beyond the suspended ceiling assemblies in the following locations:

a. 9:34 a.m., basement-level, Laundry.
b. 9:50 a.m., basement-level Dietary.

Exit interview on September 21, 2026, between 11:00 a.m., and 11:10 a.m., with the Facilities Manager, confirmed the HVAC deficiencies.




 Plan of Correction - To be completed: 10/20/2026

1. Portable ac units were removed.

2. Director of maintenance and or designee will be educated ensuring all portable hvac units are vented correctly.
NFPA 101 STANDARD Fire Drills:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
19.7.1.4 through 19.7.1.7
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0712

Based on observation and interview, it was determined the facility failed to maintain fire drills in two of twelve instances, affecting four of four floors.

Findings include:

1. Observation on September 21, 2026, between 10:50 a.m., and 10:55 a.m., revealed the facility lacked third quarter fire drill documentation for first and third shifts.

Exit interview on September 21, 2026, between 11:00 a.m., and 11:10 a.m., with the Facilities Manager, confirmed the the fire drill deficiencies.







 Plan of Correction - To be completed: 10/20/2026

1. Facility cant amend identified missing fire drills

2. Director of maintenance and or designee will be educated on completing the necessary fire drills per code.
NFPA 101 STANDARD Electrical Equipment - Power Cords and Extens:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Electrical Equipment - Power Cords and Extension Cords
Power strips in a patient care vicinity are only used for components of movable patient-care-related electrical equipment (PCREE) assembles that have been assembled by qualified personnel and meet the conditions of 10.2.3.6. Power strips in the patient care vicinity may not be used for non-PCREE (e.g., personal electronics), except in long-term care resident rooms that do not use PCREE. Power strips for PCREE meet UL 1363A or UL 60601-1. Power strips for non-PCREE in the patient care rooms (outside of vicinity) meet UL 1363. In non-patient care rooms, power strips meet other UL standards. All power strips are used with general precautions. Extension cords are not used as a substitute for fixed wiring of a structure. Extension cords used temporarily are removed immediately upon completion of the purpose for which it was installed and meets the conditions of 10.2.4.
10.2.3.6 (NFPA 99), 10.2.4 (NFPA 99), 400-8 (NFPA 70), 590.3(D) (NFPA 70), TIA 12-5
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0920

Based on observation and interview, it was determined the facility failed to maintain extension cord usage in one location, affecting one of four floors.

Findings include:

1. Observation on September 21, 2026, at 9:47 a.m., revealed an extension cord in use within the DON's Office.

Exit interview on September 21, 2026, between 11:00 a.m., and 11:10 a.m., with the Facilities Manager, confirmed the extension cord use.




 Plan of Correction - To be completed: 10/20/2026

1. Extension cord was removed from identified office.

2. Director of maintenance and or designee will conduct random audits ensuring extension cords aren't in use .

3. Director of maintenance and or designee will be educated ensuring extension cords aren't in use.

4. Director of maintenance and or designee will conduct random weekly audits for one month, then monthly for 3 ensuring extension cords aren't in use. Findings to be discussed in qapi
Initial comments:Name: LOBBY AND CONFERENCE ROOM - Component: 02 - Tag: 0000


Facility ID# 121802
Component 02
Main Lobby and Conference Room

Based on a Medicare/Medicaid Recertification Survey completed on September 21, 2026, it was determined that Jewel Healthcare and Rehabilitation was in substantial compliance with the requirements of the Life Safety Code for an existing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a one story, Type II (000), unprotected, noncombustible building, that is fully sprinklered.




 Plan of Correction: