Pennsylvania Department of Health
MON VALLEY CARE CENTER
Building Inspection Results

Note: If you need to change the font size, click the "View" menu at the top of the page, place the mouse over the "Text Size" menu item, and select the desired font size.

Severity Designations

Click here for definitions Click here for definitions Click here for definitions Click here for definitions
Minimal Citation - No Harm Minimal Harm Actual Harm Serious Harm
MON VALLEY CARE CENTER
Inspection Results For:

There are  38 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
MON VALLEY CARE CENTER - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000


Based on an Emergency Preparedness Survey completed on August 3, 2026, at Mon Valley Care Center, it was determined there were no deficiencies identified with the requirements of 42 CFR 483.73.





 Plan of Correction:


Initial comments:Name: MAIN BUILDING - Component: 01 - Tag: 0000


Facility ID #11790201
Component 01
Main Building

Based on a Medicare/Medicaid Recertification Survey completed on August 3, 2026, it was determined that Mon Valley Care Center was not in compliance with the following requirements of the Life Safety Code for an existing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a three-story, Type II (111), protected, non-combustible building, without a basement, that is fully sprinklered.





 Plan of Correction:


NFPA 101 STANDARD Fire Drills:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
19.7.1.4 through 19.7.1.7
Observations:
Name: MAIN BUILDING - Component: 01 - Tag: 0712

Based on document review and interview, the facility failed to perform two of 12 required fire drills, affecting the entire facility.

Findings include:

Document review on August 3, 2026, at 9:00 a.m., revealed the facility lacked documentation for two of twelve required fire drills. The second shift, first and fourth quarter fire drills were missing.

Interview with the facility administrator and maintenance director on August 3, 2026, at 1:30 p.m., confirmed the facility lacked documentation for the two fire drills.






 Plan of Correction - To be completed: 08/12/2026


The facility submits this Plan of Correction as its allegation of compliance.


1.The Administrator and Maintenance Director reviewed the facility's fire drill records and fire drill schedule following the survey finding. The facility identified that documentation was unavailable for two of the twelve required fire drills, specifically the second-shift fire drills for the first and fourth quarters. The facility reviewed its available fire drill documentation to verify completion and documentation of required fire drills.
2. Identification of Others Potentially Affected:
The deficient practice had the potential to affect all residents, staff, and areas of the facility. The Administrator and Maintenance Director reviewed the facility's available fire drill records to identify any additional missing or incomplete fire drill documentation.

3. Systemic Changes:
The Maintenance Director was re-educated by the Administrator regarding the requirement to conduct and document fire drills at least quarterly on each shift, at varying times and under varying conditions, in accordance with applicable Life Safety Code requirements.

A fire drill tracking system will be maintained identifying each quarter, shift, date, time, and completion status. Following each required fire drill, the Maintenance Director or designee will ensure that the fire drill documentation is completed and maintained in the facility's Life Safety records. The Administrator or designee will review the tracking system to verify that all required drills are completed and appropriately documented.

4. Monitoring / Quality Assurance:
The Administrator or designee will audit the fire drill tracking system and supporting documentation monthly for three months and quarterly for three additional quarters to verify that required fire drills are being completed and appropriately documented on each shift. Any identified concerns will be addressed promptly. Results of the audits will be presented to the facility's QAPI Committee for review and recommendations as indicated.

5. Completion Date:
8/12/26