Egress Doors Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements: CLINICAL NEEDS OR SECURITY THREAT LOCKING Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times. 18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6 SPECIAL NEEDS LOCKING ARRANGEMENTS Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation. 18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4 DELAYED-EGRESS LOCKING ARRANGEMENTS Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system. 18.2.2.2.4, 19.2.2.2.4 ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted. 18.2.2.2.4, 19.2.2.2.4 ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system. 18.2.2.2.4, 19.2.2.2.4
|
Observations: Name: MAIN BUILDING 01 - Component: 01 - Tag: 0222
Based on observation and interview, the facility failed to maintain egress doors with special locking arrangements, affecting one of at least fifteen egress doors within the component.
Findings include:
1.Observation on April 1, 2026, at 12:05 p.m., revealed, on the fourth floor, the north stair tower door (across from room 427), equipped with special locking arrangement to release within 15 seconds of pressure applied against door, failed to release to provide access.
Exit Interview with the Assistant Administrator and Maintenance Director on April 1, 2026, at 1:00 p.m., confirmed the egress door failed to release.
| | Plan of Correction - To be completed: 05/08/2026
It is the practice of the facility to have delayed egress functionality on exit doors, and all residents had the potential to be affected by this deficiency.
1. Facility has repaired the north stair tower door and delayed egress is now functioning as per the design.
2. All delayed egress doors have been tested on 4/02/2026 and are functioning as per the design. All resident areas are free from hazard, and all systems are operating as designed.
3. The Director of Maintenance has completed education and training with Maintenance staff on testing delayed egress doors for proper function.
4. Every quarter for a year the Maintenance Director or designee will complete testing of delayed egress doors. This information will then be entered on a log and will be presented by the director to the monthly QAPI meeting for one year.
|
|