Survey conducted on 03/15/2012

INITIAL COMMENTS
 
This report is a result of an on-site licensure renewal inspection conducted on March 14 - 15, 2012 by staff from the Division of Drug and Alcohol Program Licensure. Based on the findings of the on-site inspection, Salvation Army Harbor Light Center was found not to be in compliance with the applicable chapters of 28 PA Code which pertain to the facility. The following deficiencies were identified during this inspection.
 
Plan of Correction

705.10 (d) (5)  LICENSURE Fire safety.

705.10. Fire safety. (d) Fire drills. The residential facility shall: (5) Conduct a fire drill during sleeping hours at least every 6 months.
Observations
Based on a review of fire drill records, the facility failed to conduct a fire drill during sleeping hours at least every six months.



The findings include:



Fire drill records from March 2011 through February 2012 were reviewed on March 14, 2012. Sleeping hours at the facility are from 11:00 PM until 6:45 AM. The facility conducted fire drills during sleeping hours on the following dates: November 19, 2011 and December 17, 2011. Based on the fire drill records reviewed, the facility was due to complete a fire drill during sleeping hours no later than May 19, 2011. The facility failed to document a fire drill during sleeping hours at least every six months.



The project/facility director was interviewed on March 14, 2012 at approximately 2:30 PM and confirmed the findings.
 
Plan of Correction
This facility shall conduct a fire drill at least once every six months during resident sleeping hours. The Administrative Secretary will maintain written documentation to insure that this non-compliance issue is corrected. The Institutional Services Director shall continue to review and sign-off on all monthly fire drills and track at least one fire drill to be conducted every six months during resident sleeping hours.

 