SAFE HAVEN IN YORK PA INC
305 CARLISLE AVENUE
YORK, PA 17404

Inspection Results   Overview    Definitions       Surveys   Additional Services   Search

Survey conducted on 06/11/2026

INITIAL COMMENTS
 
This report is a result of an on-site licensure renewal inspection conducted on June 11, 2026, by staff from the Bureau of Program Licensure. Based on the findings of the on-site inspection 25VZ6701 Safe Haven In York Pa Inc was found not to be in compliance with the applicable chapters of 28 PA Code which pertain to the facility. Therefore, deficiencies were identified during this inspection, and a plan of correction is required.
 
Plan of Correction

§ 717.29(e)(3)  LICENSURE Physical plant standards - Bathrooms

§ 717.29. Physical plant standards. (e) Bathrooms. The licensee shall: (3) Have hot and cold water under pressure. Hot water temperature may not exceed 120°F.
Observations
Based on a physical plant inspection, the facility failed to keep the water temperature from exceeding 120 degrees Fahrenheit. The bathroom had a water temperature of 130 degrees Fahrenheit.



These findings were reviewed with the recovery house staff during the licensing process.
 
Plan of Correction
Plan of Correction:

1. PLAN OF CORRECTION

The facility will correct the cited area of noncompliance regarding water temperature by lowering the hot water



heater thermostat settings to ensure hot water at all resident-accessible fixtures does not exceed 120 degrees



Fahrenheit. Immediately following the inspection, the hot water tank mixing valves were adjusted, and the



bathroom water temperature was successfully re-tested and verified to be within safe regulatory limits.



2. PERSONS RESPONSIBLE



Director of Female Operations and Director of Male Operations



3. PREVENTION PLAN



To prevent this physical plant issue from happening again, the facility has implemented a mandatory Water



Temperature Log. Staff members will conduct weekly testing of water temperatures at various resident



accessible fixtures across the property using a calibrated digital thermometer. The weekly temperature readings



will be documented on a physical tracking sheet. The directors will review these logs on a monthly basis. If any



reading approaches 120 degrees Fahrenheit, immediate maintenance adjustments will be triggered.



4. CORRECTIVE ACTION / COMPLETION DATE



06/16/2026

 