Survey conducted on 05/03/2023

INITIAL COMMENTS
 
This report is a result of an on-site licensure renewal inspection conducted on May 1-3, 2023 by staff from the Department of Drug and Alcohol Programs, Bureau of Program Licensure. Based on the findings of the on-site inspection, Cen-Clear Child Services, Inc. was found not to be in compliance with the applicable chapters of 28 PA Code which pertain to the facility. The following deficiencies were identified during this inspection:
 
Plan of Correction

705.28 (d) (1)  LICENSURE Fire safety.

705.28. Fire safety. (d) Fire drills. The nonresidential facility shall: (1) Conduct unannounced fire drills at least once a month.
Observations
Based on a review of the fire drill records, the facility failed to conduct fire drills at least once a month.

Fire drill records were reviewed from April 2022 to March 2023. Fire drills were not conducted for June 2022 or August 2022.





These findings were reviewed with facility staff during the licensing process.
 
Plan of Correction
These findings were reviewed with Departmental Assistants, Clinical Supervisors, and Regional Managers during a regional meeting on 5/3/2023. Fire Drills will be monitored by third week of the month by Outpatient Director to ensure that they are completed monthly. If issues are identified, or it is determined that a fire drill has not yet been completed, one will be completed, and the findings audited for compliance with all regulatory aspects.

705.28 (d) (4)  LICENSURE Fire safety.

705.28. Fire safety. (d) Fire drills. The nonresidential facility shall: (4) Maintain a written fire drill record including the date, time, the amount of time it took for evacuation, the exit route used, the number of persons in the facility at the time of the drill, problems encountered and whether the fire alarm or smoke detector was operative.
Observations
Based on a review of the fire drill records, the facility failed to maintain a written fire drill records that includes documentation whether the fire alarm or smoke detector was operative.

Fire drill records were reviewed from April 2022 to March 2023. Fire drills documented from April 2022 through December 2022 did not include whether the fire alarm or smoke detector was operative.

These findings were reviewed with facility staff during the licensing process.
 
Plan of Correction
Administrative form did not contain a section to indicate whether or not the fire alarm and/or smoke detector were operative. Education occurred with Departmental Assistants, Clinical Supervisors, and Regional Managers on 5/3/2023 regarding the need to ensure this is consistently monitored and findings documented. Fire Drills will be audited by the third week of each month by Outpatient Director to ensure compliance with all aspects of regulatory requirements and request that drills be re-performed and appropriately documented by end of the month in instances where continued deficiencies are identified.

705.28 (d) (7)  LICENSURE Fire safety.

705.28. Fire safety. (d) Fire drills. The nonresidential facility shall: (7) Set off a fire alarm or smoke detector during each fire drill.
Observations
Based on a review of the fire drill records, the facility failed to set off a fire alarm or smoke detector during each fire drill.

Fire drill records were reviewed from April 2022 to March 2023. Fire alarms and smoke detectors were not set off for fire drills documented from April 2022 through December 2022.

These findings were reviewed with facility staff during the licensing process.
 
Plan of Correction
Administrative form did not contain a section to indicate whether or not the fire alarm and/or smoke detector were operative. Education occurred with Departmental Assistants, Clinical Supervisors, and Regional Managers on 5/3/2023 regarding the need to ensure that the fire alarm is set off for each Fire Drill conducted. Fire Drills will be audited by the third week of each month by Outpatient Director to ensure compliance with all aspects of regulatory requirements and request that drills be re-performed and appropriately documented by end of the month in instances where continued deficiencies are identified.

709.91(b)(1)  LICENSURE Intake and admission

709.91. Intake and admission. (b) Intake procedures shall include documentation of: (1) Disclosure to the client of criteria for admission, treatment, completion and discharge.
Observations
Based on a review of client records, the facility failed to document the disclosure of the criteria for admission to the client in seven of seven records.

Neither the handbook nor the documentation the clients sign at intake includes the criteria for admission.

These findings were reviewed with facility staff during the licensing process.
 
Plan of Correction
The SUD Welcome packet provided to all consumers at the time of admission has been revised to include criteria for admission, treatment, completion, and discharge. Welcome packets are provided to all consumers as part of their intake, and written attestation to this effect is obtained during the intake appointment in the "Multi-Consent" documentation. This change will take effect on 5/1/23. Facility Directors and Clinical Supervisors have been made aware of this change, and all active consumers will be provided a copy of the revised SUD Welcome Packet which clearly outlines these criterion. Quality Assurance will, as part of their ongoing monthly quality monitoring, ensure that a valid and signed multi-consent is on-file indicating that consumers received a copy of the revised SUD Welcome Packet. These findings will be reviewed with Regional Managers for follow-up when deficiencies are identified.

 