Survey conducted on 03/25/2024

INITIAL COMMENTS
 
This report is a result of an on-site licensure renewal inspection conducted on March 25, 2024 by staff from the Department of Drug and Alcohol Programs, Bureau of Program Licensure. Based on the findings of the on-site inspection, Center for Families was found not to be in compliance with the applicable chapters of 28 PA Code which pertain to the facility. The following deficiencies were identified during this inspection:
 
Plan of Correction

705.28 (a) (1) (ii)  LICENSURE Fire safety.

705.28. Fire safety. (a) Exits. (1) The nonresidential facility shall: (ii) Maintain a minimum of two exits on every floor, including the basement, that are separated by a minimum distance of 15 feet.
Observations
Based on a physical plant inspection, the facility failed to maintain a minimum of two exits on every floor, including the basement, that are separated by a minimum distance of 15 feet. The third floor has only one exit. This was reviewed with the facility during the licensing inspection process.
 
Plan of Correction
Third Floor door has been padlocked and is currently not accessible to staff or clients. The space will not be used until and unless we are able to install a 2nd exit.

 