Survey conducted on 05/11/2022

INITIAL COMMENTS
 
This report is a result of an on-site licensure renewal inspection conducted on May 11, 2022 by staff from the Department of Drug and Alcohol Programs, Bureau of Program Licensure. Based on the findings of the on-site inspection, Retreat at Lancaster County PA, LLC was found not to be in compliance with the applicable chapters of 28 PA Code which pertain to the facility. The following deficiencies were identified during this inspection:
 
Plan of Correction

705.28 (d) (7)  LICENSURE Fire safety.

705.28. Fire safety. (d) Fire drills. The nonresidential facility shall: (7) Set off a fire alarm or smoke detector during each fire drill.
Observations
Based on a review of fire drill records from July, 2021 through April 2022, the facility failed to set off a fire alarm or smoke detector during each fire drill. The facility used a verbal staff announcement.This finding was reviewed with facility staff during the licensing process.This is a repeat citation from the July 1, 2021 licensing inspection.
 
Plan of Correction
Due to the fire alarm system setting off the alarms for all surrounding businesses, a request for a waiver has been submitted to allow for the use of an alternate way of notifying staff and patients of fire drill. Moving forward, facility director, or assigned designee, that is completing the fire drill will utilize a portable fire alarm to notify all staff and patients of a fire drill taking place.



Facility director and all designees responsible for conducting fire drills have been retrained to ensure they know that the portable fire alarm must be used for each fire drill. Facility director will be checking monthly to ensure that each fire drill is completed correctly.

 