VALLEY AMBULATORY SURGICAL CENTER, LLC Building Inspection Results For:
There are 17 surveys for this facility. Please select a date to view the survey results.
Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
|
Initial Comments: Name - 02 MAIN BUILDING (FORMER 01 COMPONENT) Component - 02
Facility ID# 21281501 Component 02 Main Building
Based on a Relicensure Survey completed on November 27, 2023, it was determined that Valley Ambulatory Surgical Center, Llc was not in compliance with the following requirements of the Life Safety Code for an existing Ambulatory health care occupancy.
This is a one story, Type II (000), unprotected noncombustible building, that is fully sprinklered.
Plan of Correction:
28 Pa. Code § 569.2 STANDARD Sprinkler System - Maintenance and Testing Name - 02 MAIN BUILDING (FORMER 01 COMPONENT) Component - 02 Sprinkler System - Maintenance and Testing Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available. a) Date sprinkler system last checked _____________________ b) Who provided system test ____________________________ c) Water system supply source __________________________ Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system. 9.7.5, 9.7.7, 9.7.8, and NFPA 25
Observations:
Based on observation and interview, it was determined the facility failed to maintain the sprinkler system that provides sprinkler protection throughout the facility.
Findings include:
1. Document review and observation on Novemeber 27, 2023, between 10:30 am, and 11:30 am, revealed the required five inspections of the sprinkler system were over due, including gauges.
Interview with the facility representative on November 27, 2023, at 11:30 am, confirmed the five year inspections were not completed and were now over due.
Plan of Correction:The assistant administrator of the facility will obtain the required 5 year sprinkler system and gauge inspection. This date will be documented in the governing body quarterly meetings to insure this deficiency does not recur.
| |