Observations Based on a physical plant inspection on March 6, 2026, the facility failed to ensure that the hot water temperature did not exceed 120 degrees Fahrenheit.
When tested, the hot water in the back client bathroom was 121.6 degrees Fahrenheit.
These findings were reviewed with project staff during the licensing process.
|
Plan of Correction CleanSlate's Center Manager had the building maintenance company adjust the water temperature in all bathrooms to not exceed 120 degrees on 3/9/2026. Water temperature was tested to ensure compliance with this regulation.
Center Manager will be responsible for checking water temperatures in all bathrooms on a quarterly basis. Should the temperature exceed 120 degrees, maintenance will be notified to fix. |