Initial Comments: Name - MAIN BUILDING 01 Component - 01 Facility ID# 50261501 Component 01 Shadyside Place Building
Based on a Relicensure Survey completed on October 19, 2023, it was determined that Leo R. McCafferty, M.D., Plastic Surgery was not in compliance with the following requirements of the Life Safety Code for an existing Ambulatory Health Care Occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 416.44(b).
This is a five-story, Type IV (2HH), heavy timber building, with a basement, that is fully sprinklered.
The ASC is on the fifth floor.
Plan of Correction:
28 Pa. Code § 569.2 STANDARD Emergency Lighting Name - MAIN BUILDING 01 Component - 01 Emergency Lighting Emergency lighting of at least 1-1/2 hour duration is provided automatically in accordance with 7.9. 20.2.9.1, 21.2.9.1, 7.9
Observations:
Based on document review and interview, it was determined the facility failed to maintain emergency lighting in one instance, affecting the entire facility.
Findings include:
1. Documentation review on October 19, 2023, at 8:45 a.m., revealed the facility lacked documentation for an annual 90-minute test for the emergency lights.
Interview with the Facility Administrator and Maintenance Director on October 19, 2023, at 8:45 a.m., confirmed the facility lacked documentation for the annual 90-minute test for the emergency lights.
Plan of Correction:Plan of Correction: A meeting was held 10/19/2023 with the clinical director and the director of engineering and maintenance for UPMC Shadyside to discuss and correct the plan of correction regarding observation #0291. UPMC engineering and maintenance found the date entered in the system was incorrect therefore, it did not generate the work order to complete the 90 minute test on the emergency lights in the operating room.
UPMC engineering and maintenance contacted dispatch on 10/19/2023 and the dates in the system were corrected. The report will print when the testing is due next October of 2024.
The 90 minute test on the operating room Emergency lights was completed 10/20/2023. A copy of the test will be maintained by UPMC engineering and maintenance and be available upon request.
|