RADIANCE - A PRIVATE OUTPATIENT SURGERY CENTER, LLC Building Inspection Results For:
There are 8 surveys for this facility. Please select a date to view the survey results.
Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
|
Initial Comments: Name - MAIN BUILDING Component - 02 Facility ID# 17601501 Component 02 Main Building
Based on a Relicensure Survey completed on September 12, 2023, it was determined that Radiance-A Private Outpatient Surgery Center was not in compliance with the following requirements of the Life Safety Code for an existing Ambulatory health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 28 Pa Code 569.2.
This is a two-story, Type III (200), unprotected ordinary building, without a basement, that is fully sprinklered.
Plan of Correction:
28 Pa. Code § 569.2 STANDARD Hazardous Areas - Enclosure Name - MAIN BUILDING Component - 02 Hazardous Areas - Enclosure Hazardous areas must meet one of the following: *Contain 1 hour rated enclosure when non-sprinklered *Sprinkler protected with smoke resistive separation *Severe Hazard locations contain sprinkler protection and 1 hour separation with 3/4 hour rated self-closing doors 20.3.2, 21.3.2, 38.3.2, 38.3.2.2, 39.3.2.1, 39.3.2.2, 8.7
Observations:
Based on observation and interview, it was determined the facility failed to maintain hazardous area enclosures in one instance, affecting the entire facility.
Findings include:
1. Observation on September 12, 2023, at 10:25 a.m., revealed the door seperating the clean utility to central sterile was not equipped with a self closure.
Interview with the Director of Nursing and the Maintenance Manager on September 12, 2023, at 11:30 a.m., confirmed the hazardous area enclosure deficiency.
Plan of Correction:On 9-16-23 the facility manager installed an automatic self door closure on the door separating the clean utility to central sterile.
| |