Pennsylvania Department of Health
GREENFIELD HEALTHCARE AND REHABILITATION CENTER
Building Inspection Results

Note: If you need to change the font size, click the "View" menu at the top of the page, place the mouse over the "Text Size" menu item, and select the desired font size.

Severity Designations

Click here for definitions Click here for definitions Click here for definitions Click here for definitions
Minimal Citation - No Harm Minimal Harm Actual Harm Serious Harm
GREENFIELD HEALTHCARE AND REHABILITATION CENTER
Inspection Results For:

There are  47 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
GREENFIELD HEALTHCARE AND REHABILITATION CENTER - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000


Based on an Emergency Preparedness Survey completed on January 28, 2026, it was determined that Greenfield Healthcare and Rehabilitation had deficiencies that have the potential for minimal harm as related to the requirements of 42 CFR 483.73.





 Plan of Correction:


403.748(a), 416.54(a), 418.113(a), 441.184(a), 482.15(a), 483.475(a), 483.73(a), 484.102(a), 485.542(a), 485.625(a), 485.68(a), 485.727(a), 485.920(a), 486.360(a), 491.12(a), 494.62(a) STANDARD Develop EP Plan, Review and Update Annually:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§403.748(a), §416.54(a), §418.113(a), §441.184(a), §460.84(a), §482.15(a), §483.73(a), §483.475(a), §484.102(a), §485.68(a), §485.542(a), §485.625(a), §485.727(a), §485.920(a), §486.360(a), §491.12(a), §494.62(a).

The [facility] must comply with all applicable Federal, State and local emergency preparedness requirements. The [facility] must develop establish and maintain a comprehensive emergency preparedness program that meets the requirements of this section. The emergency preparedness program must include, but not be limited to, the following elements:

(a) Emergency Plan. The [facility] must develop and maintain an emergency preparedness plan that must be [reviewed], and updated at least every 2 years. The plan must do all of the following:

* [For hospitals at §482.15 and CAHs at §485.625(a):] Emergency Plan. The [hospital or CAH] must comply with all applicable Federal, State, and local emergency preparedness requirements. The [hospital or CAH] must develop and maintain a comprehensive emergency preparedness program that meets the requirements of this section, utilizing an all-hazards approach.

* [For LTC Facilities at §483.73(a):] Emergency Plan. The LTC facility must develop and maintain an emergency preparedness plan that must be reviewed, and updated at least annually.

* [For ESRD Facilities at §494.62(a):] Emergency Plan. The ESRD facility must develop and maintain an emergency preparedness plan that must be [evaluated], and updated at least every 2 years.

.
Observations:
Name: - Component: -- - Tag: 0004

Based on document review and interview, the facility failed to develop and maintain an emergency preparedness plan that is reviewed and updated at least annually, for one of one plan.

Findings include:

Document review on January 28, 2026, at 12:33 p.m., revealed the facility failed to update local resources and key personnel on its succession plan as well as annually reviewing the emergency preparedness plan.

Interview with the administrator on January 28, 2026, at 12:33 p.m., confirmed the incomplete annual update.





 Plan of Correction - To be completed: 02/24/2026

1. The Emergency Preparedness Plan has been reviewed and updated by the administrator/designee, including the list of local resources and key personnel.
2. An annual review of the emergency preparedness plan has been scheduled for each January by the Quality Assurance team.
3. Quality Assurance will review the current plan at the February meeting. Administrator to monitor.


403.748(c)(1), 416.54(c)(1), 418.113(c)(1), 441.184(c)(1), 482.15(c)(1), 483.475(c)(1), 483.73(c)(1), 484.102(c)(1), 485.542(c)(1), 485.625(c)(1), 485.68(c)(1), 485.727(c)(1), 485.920(c)(1), 486.360(c)(1), 491.12(c)(1), 494.62(c)(1) STANDARD Names and Contact Information:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§403.748(c)(1), §416.54(c)(1), §418.113(c)(1), §441.184(c)(1), §460.84(c)(1), §482.15(c)(1), §483.73(c)(1), §483.475(c)(1), §484.102(c)(1), §485.68(c)(1), §485.542(c)(1), §485.625(c)(1), §485.727(c)(1), §485.920(c)(1), §486.360(c)(1), §491.12(c)(1), §494.62(c)(1).

[(c) The [facility must develop and maintain an emergency preparedness communication plan that complies with Federal, State and local laws and must be reviewed and updated at least every 2 years [annually for LTC facilities]. The communication plan must include all of the following:]

(1) Names and contact information for the following:
(i) Staff.
(ii) Entities providing services under arrangement.
(iii) Patients' physicians
(iv) Other [facilities].
(v) Volunteers.

*[For Hospitals at §482.15(c) and CAHs at §485.625(c)] The communication plan must include all of the following:
(1) Names and contact information for the following:
(i) Staff.
(ii) Entities providing services under arrangement.
(iii) Patients' physicians
(iv) Other [hospitals and CAHs].
(v) Volunteers.

*[For RNHCIs at §403.748(c):] The communication plan must include all of the following:
(1) Names and contact information for the following:
(i) Staff.
(ii) Entities providing services under arrangement.
(iii) Next of kin, guardian, or custodian.
(iv) Other RNHCIs.
(v) Volunteers.

*[For ASCs at §416.45(c):] The communication plan must include all of the following:
(1) Names and contact information for the following:
(i) Staff.
(ii) Entities providing services under arrangement.
(iii) Patients' physicians.
(iv) Volunteers.

*[For Hospices at §418.113(c):] The communication plan must include all of the following:
(1) Names and contact information for the following:
(i) Hospice employees.
(ii) Entities providing services under arrangement.
(iii) Patients' physicians.
(iv) Other hospices.

*[For HHAs at §484.102(c):] The communication plan must include all of the following:
(1) Names and contact information for the following:
(i) Staff.
(ii) Entities providing services under arrangement.
(iii) Patients' physicians.
(iv) Volunteers.

*[For OPOs at §486.360(c):] The communication plan must include all of the following:
(2) Names and contact information for the following:
(i) Staff.
(ii) Entities providing services under arrangement.
(iii) Volunteers.
(iv) Other OPOs.
(v) Transplant and donor hospitals in the OPO's Donation Service Area (DSA).
Observations:
Name: - Component: -- - Tag: 0030

Based on document review and interview, the facility failed to ensure the facility's emergency preparedness communication plan included names and contact information for staff, entities providing services under arrangement, patients' physicians, other facilities, and volunteers for one of one plan.

Findings include:

Document review on January 28, 2026, at 12:35 p.m., revealed the facility's emergency preparedness communications plan did not include updated names and contact information for staff, entities providing services under arrangement, patients' physicians, other facilities, and volunteers.

Interview with the administrator on January 28, 2026, at 12:35 p.m., confirmed the emergency preparedness communications plans were unavailable.





 Plan of Correction - To be completed: 02/24/2026

1. The Emergency Preparedness Plan has been reviewed and updated by the administrator/designee, including the list of emergency vendors, staff contact information, physician contact information, transfer agreements, and volunteers.
2. An annual review of the emergency preparedness plan has been scheduled for each January by the Quality Assurance team.
3. Quality Assurance will review the current plan at the February meeting. Administrator to monitor.

403.748(d), 416.54(d), 418.113(d), 441.184(d), 482.15(d), 483.475(d), 483.73(d), 484.102(d), 485.542(d), 485.625(d), 485.68(d), 485.727(d), 485.920(d), 486.360(d), 491.12(d), 494.62(d) STANDARD EP Training and Testing:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§403.748(d), §416.54(d), §418.113(d), §441.184(d), §460.84(d), §482.15(d), §483.73(d), §483.475(d), §484.102(d), §485.68(d), §485.542(d), §485.625(d), §485.727(d), §485.920(d), §486.360(d), §491.12(d), §494.62(d).

*[For RNCHIs at §403.748, ASCs at §416.54, Hospice at §418.113, PRTFs at §441.184, PACE at §460.84, Hospitals at §482.15, HHAs at §484.102, CORFs at §485.68, REHs at §485.542, CAHs at §486.625, "Organizations" under 485.727, CMHCs at §485.920, OPOs at §486.360, and RHC/FHQs at §491.12:] (d) Training and testing. The [facility] must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least every 2 years.

*[For LTC facilities at §483.73(d):] (d) Training and testing. The LTC facility must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least annually.

*[For ICF/IIDs at §483.475(d):] Training and testing. The ICF/IID must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least every 2 years. The ICF/IID must meet the requirements for evacuation drills and training at §483.470(i).

*[For ESRD Facilities at §494.62(d):] Training, testing, and orientation. The dialysis facility must develop and maintain an emergency preparedness training, testing and patient orientation program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training, testing and orientation program must be evaluated and updated at every 2 years.
Observations:
Name: - Component: -- - Tag: 0036

Based on document review and interview, the facility failed to develop an emergency preparedness plan that included annual emergency preparedness plan staff training for one of one plan.

Findings include:

Document review on January 28, 2026, at 12:40 p.m., revealed the facility lacked documentation that all staff had annual emergency preparedness training within the previous twelve months.

Interview with the administrator on January 28, 2026, at 12:40 p.m., confirmed the facility lacked documentation that all staff had annual emergency preparedness training within the previous twelve months.





 Plan of Correction - To be completed: 02/24/2026

1. All staff education on the emergency preparedness plan will be conducted by administrator/designee.
2. An annual in-service plan has been developed by the administrator that includes emergency preparedness training upon hire and annually.
3. A monthly report of completed educations will be submitted to the Quality Assurance team for review by the Human Resources Director. Administrator to monitor.

403.748(d)(2), 416.54(d)(2), 418.113(d)(2), 441.184(d)(2), 482.15(d)(2), 483.475(d)(2), 483.73(d)(2), 484.102(d)(2), 485.542(d)(2), 485.625(d)(2), 485.68(d)(2), 485.727(d)(2), 485.920(d)(2), 486.360(d)(2), 491.12(d)(2), 494.62(d)(2) STANDARD EP Testing Requirements:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§416.54(d)(2), §418.113(d)(2), §441.184(d)(2), §460.84(d)(2), §482.15(d)(2), §483.73(d)(2), §483.475(d)(2), §484.102(d)(2), §485.68(d)(2), §485.542(d)(2), §485.625(d)(2), §485.727(d)(2), §485.920(d)(2), §491.12(d)(2), §494.62(d)(2).

*[For ASCs at §416.54, CORFs at §485.68, REHs at §485.542, OPO, "Organizations" under §485.727, CMHCs at §485.920, RHCs/FQHCs at §491.12, and ESRD Facilities at §494.62]:

(2) Testing. The [facility] must conduct exercises to test the emergency plan annually. The [facility] must do all of the following:

(i) Participate in a full-scale exercise that is community-based every 2 years; or
(A) When a community-based exercise is not accessible, conduct a facility-based functional exercise every 2 years; or
(B) If the [facility] experiences an actual natural or man-made emergency that requires activation of the emergency plan, the [facility] is exempt from engaging in its next required community-based or individual, facility-based functional exercise following the onset of the actual event.
(ii) Conduct an additional exercise at least every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [facility's] response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the [facility's] emergency plan, as needed.

*[For Hospices at 418.113(d):]
(2) Testing for hospices that provide care in the patient's home. The hospice must conduct exercises to test the emergency plan at least annually. The hospice must do the following:
(i) Participate in a full-scale exercise that is community based every 2 years; or
(A) When a community based exercise is not accessible, conduct an individual facility based functional exercise every 2 years; or
(B) If the hospice experiences a natural or man-made emergency that requires activation of the emergency plan, the hospital is exempt from engaging in its next required full scale community-based exercise or individual facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.

(3) Testing for hospices that provide inpatient care directly. The hospice must conduct exercises to test the emergency plan twice per year. The hospice must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual facility-based functional exercise; or
(B) If the hospice experiences a natural or man-made emergency that requires activation of the emergency plan, the hospice is exempt from engaging in its next required full-scale community based or facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop led by a facilitator that includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the hospice's response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the hospice's emergency plan, as needed.


*[For PRFTs at §441.184(d), Hospitals at §482.15(d), CAHs at §485.625(d):]
(2) Testing. The [PRTF, Hospital, CAH] must conduct exercises to test the emergency plan twice per year. The [PRTF, Hospital, CAH] must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or
(B) If the [PRTF, Hospital, CAH] experiences an actual natural or man-made emergency that requires activation of the emergency plan, the [facility] is exempt from engaging in its next required full-scale community based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an [additional] annual exercise or and that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, a facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [facility's] response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the [facility's] emergency plan, as needed.

*[For PACE at §460.84(d):]
(2) Testing. The PACE organization must conduct exercises to test the emergency plan at least annually. The PACE organization must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or
(B) If the PACE experiences an actual natural or man-made emergency that requires activation of the emergency plan, the PACE is exempt from engaging in its next required full-scale community based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the PACE's response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the PACE's emergency plan, as needed.

*[For LTC Facilities at §483.73(d):]
(2) The [LTC facility] must conduct exercises to test the emergency plan at least twice per year, including unannounced staff drills using the emergency procedures. The [LTC facility, ICF/IID] must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise.
(B) If the [LTC facility] facility experiences an actual natural or man-made emergency that requires activation of the emergency plan, the LTC facility is exempt from engaging its next required a full-scale community-based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [LTC facility] facility's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the [LTC facility] facility's emergency plan, as needed.

*[For ICF/IIDs at §483.475(d)]:
(2) Testing. The ICF/IID must conduct exercises to test the emergency plan at least twice per year. The ICF/IID must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or.
(B) If the ICF/IID experiences an actual natural or man-made emergency that requires activation of the emergency plan, the ICF/IID is exempt from engaging in its next required full-scale community-based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the ICF/IID's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the ICF/IID's emergency plan, as needed.

*[For HHAs at §484.102]
(d)(2) Testing. The HHA must conduct exercises to test the emergency plan at
least annually. The HHA must do the following:
(i) Participate in a full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise every 2 years; or.
(B) If the HHA experiences an actual natural or man-made emergency that requires activation of the emergency plan, the HHA is exempt from engaging in its next required full-scale community-based or individual, facility based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the HHA's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the HHA's emergency plan, as needed.

*[For OPOs at §486.360]
(d)(2) Testing. The OPO must conduct exercises to test the emergency plan. The OPO must do the following:
(i) Conduct a paper-based, tabletop exercise or workshop at least annually. A tabletop exercise is led by a facilitator and includes a group discussion, using a narrated, clinically relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan. If the OPO experiences an actual natural or man-made emergency that requires activation of the emergency plan, the OPO is exempt from engaging in its next required testing exercise following the onset of the emergency event.
(ii) Analyze the OPO's response to and maintain documentation of all tabletop exercises, and emergency events, and revise the [RNHCI's and OPO's] emergency plan, as needed.

*[ RNCHIs at §403.748]:
(d)(2) Testing. The RNHCI must conduct exercises to test the emergency plan. The RNHCI must do the following:
(i) Conduct a paper-based, tabletop exercise at least annually. A tabletop exercise is a group discussion led by a facilitator, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(ii) Analyze the RNHCI's response to and maintain documentation of all tabletop exercises, and emergency events, and revise the RNHCI's emergency plan, as needed.
Observations:
Name: - Component: -- - Tag: 0039

Based on document review and interview, the facility failed to maintain emergency preparedness guidelines for one of one emergency preparedness plan.
Findings include:

Document review on January 28, 2026, at 12:43 p.m., revealed the facility failed to conduct a full-scale emergency preparedness exercise and table top exercise within the previous year.

Interview with the administrator on January 28, 2026, at 12:43 p.m., confirmed the facility lacked the required documentation at the time of the survey.





 Plan of Correction - To be completed: 02/24/2026

1. Facility has conducted a full scale emergency preparedness exercise and a table top exercise as required.
2. Required drills have been placed onto the maintenance annual drill schedule.
3. Quality Assurance will receive a monthly reporting from maintenance/designee of the drills that have been performed the previous month. Administrator to monitor.

Initial comments:Name: MAIN BUILDING 01 - Component: 01 - Tag: 0000


Facility ID #490802
Component 01
Main Building

Based on a Medicare/Medicaid Recertification Survey completed on January 28, 2026, it was determined that Greenfield Healthcare and Rehabilitation was not in compliance with the following requirements of the Life Safety Code for an existing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a one-story, Type III (200), unprotected, ordinary building, with a basement, that is fully sprinklered.





 Plan of Correction:


NFPA 101 STANDARD Doors with Self-Closing Devices:This is a less serious (but not lowest level) deficiency and is isolated to the fewest number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Doors with Self-Closing Devices
Doors in an exit passageway, stairway enclosure, or horizontal exit, smoke barrier, or hazardous area enclosure are self-closing and kept in the closed position, unless held open by a release device complying with 7.2.1.8.2 that automatically closes all such doors throughout the smoke compartment or entire facility upon activation of:
* Required manual fire alarm system; and
* Local smoke detectors designed to detect smoke passing through the opening or a required smoke detection system; and
* Automatic sprinkler system, if installed; and
* Loss of power.
18.2.2.2.7, 18.2.2.2.8, 19.2.2.2.7, 19.2.2.2.8
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0223

Based on observation and interview, the facility failed to maintain doors with self-closing devices, affecting one of over five doors.

Findings include:

Observation on January 28, 2026, at 1:03 p.m., revealed the first floor, east wing, soiled utility room door had the self-closing device missing.

Interview with the maintenance supervisor on January 28, 2026, at 1:03 p.m., confirmed the missing closing device.





 Plan of Correction - To be completed: 02/24/2026

1. A self-closing device was added to the East wing, soiled utility room.
2. The other soiled utility doors have been inspected by Maintenance have a self-closing device.
3. Quality Assurance Committee will receive a monthly report from maintenance on status of building inspections. Monitored by the Administrator or designee.


NFPA 101 STANDARD Sprinkler System - Maintenance and Testing:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0353

Based on observation and interview, the facility failed to maintain the sprinkler system for three of eight kitchen sprinkler heads.

Findings include:

Observation on January 28, 2026, at 1:50 p.m., revealed the first floor kitchen had three of eight sprinkler heads covered with debris, potentially causing a delay in sprinkler activation.

Interview with the maintenance supervisor on January 28, 2026, at 1:50 p.m., confirmed the sprinkler heads were dirty.





 Plan of Correction - To be completed: 02/24/2026

1. The 3 sprinkler heads in the kitchen have been cleaned.
2. The other sprinkler heads in the building have been visually inspected by Maintenance and cleaned when necessary. Sprinkler head inspection will be done monthly by Maintenance/designee.
3. Quality Assurance Committee will receive a monthly report from maintenance on status of building inspections. Reviewed by the Administrator.

NFPA 101 STANDARD Subdivision of Building Spaces - Smoke Compar:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Subdivision of Building Spaces - Smoke Compartments
2012 EXISTING
Smoke barriers shall be provided to form at least two smoke compartments on every sleeping floor with a 30 or more patient bed capacity. Size of compartments cannot exceed 22,500 square feet or a 200-foot travel distance from any point in the compartment to a door in the smoke barrier.
19.3.7.1, 19.3.7.2
Detail in REMARKS zone dimensions including length of zones and dead-end corridors.
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0371

Based on observation and interview, the facility failed to install and maintain smoke barriers, per regulations, on two of two building levels.

Findings include:

Observation on January 28, 2026, at 9:00 a.m., revealed the facility had incomplete smoke barriers throughout the building.

Interview with the maintenance supervisor on January 28, 2026, at 9:00 a.m., confirmed the facility had incomplete smoke barriers throughout the building.





 Plan of Correction - To be completed: 02/24/2026

1. Smoke barriers have been repaired throughout the building. Ceiling tiles have been replaced on the first floor.
2. Inspection of ceilings has been placed on a monthly TELS walkthrough by the maintenance department.
3. Quality Assurance Committee will receive a monthly report from maintenance on status of building inspections. Monitored by the Administrator.


NFPA 101 STANDARD Subdivision of Building Spaces - Smoke Barrie:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Subdivision of Building Spaces - Smoke Barrier Construction
2012 EXISTING
Smoke barriers shall be constructed to a 1/2-hour fire resistance rating per 8.5. Smoke barriers shall be permitted to terminate at an atrium wall. Smoke dampers are not required in duct penetrations in fully ducted HVAC systems where an approved sprinkler system is installed for smoke compartments adjacent to the smoke barrier.
19.3.7.3, 8.6.7.1(1)
Describe any mechanical smoke control system in REMARKS.
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0372

Based on observation and interview, the facility failed to maintain the smoke barrier on one of two building levels.

Findings include:

Observation on January 28, 2026, at 1:15 p.m., revealed the west side of the basement had multiple missing ceiling tiles.

Interview with the maintenance supervisor on January 28, 2026, at 1:15 p.m., confirmed the ceiling tile deficiency.





 Plan of Correction - To be completed: 02/24/2026

1. Smoke barriers have been repaired throughout the building. Ceiling tiles have been replaced on the first floor.
2. Inspection of ceilings has been placed on a monthly TELS walkthrough to be done by maintenance department.
3. Quality Assurance Committee will receive a monthly report from maintenance on status of building inspections. Monitored by the Administrator.

NFPA 101 STANDARD Fire Drills:This is a less serious (but not lowest level) deficiency and is isolated to the fewest number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
19.7.1.4 through 19.7.1.7
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0712

Based on document review and interview, the facility failed to meet fire drill requirements for four of twelve drills.

Findings include:

Document review on January 28, 2026, at 11:00 a.m., revealed fire drills for the third shift were conducted within the same hour slot for all of the last four quarters.

Interview with the maintenance supervisor on January 28, 2026, at 11:00 a.m., confirmed the fire drill deficiency at the time of the survey.





 Plan of Correction - To be completed: 02/24/2026

1. A fire drill has been held on 3rd shift at a random time, not between the hours of 5 and 6am.
2. Future fire drills will be randomized in timing. Maintenance Director will report on timing of drills after the fact to administrator if they are not present during the drill.
3. Quality Assurance Committee will review fire drill timing during monthly meeting. Monitored by Administrator or Designee.

NFPA 101 STANDARD Electrical Systems - Receptacles:Least serious deficiency but affects more than a limited number of residents, staff, or occurrences. This deficiency has the potential for causing no more than a minor negative impact on the resident but is not found to be throughout this facility.
Electrical Systems - Receptacles
Power receptacles have at least one, separate, highly dependable grounding pole capable of maintaining low-contact resistance with its mating plug. In pediatric locations, receptacles in patient rooms, bathrooms, play rooms, and activity rooms, other than nurseries, are listed tamper-resistant or employ a listed cover.
If used in patient care room, ground-fault circuit interrupters (GFCI) are listed.
6.3.2.2.6.2 (F), 6.3.2.2.4.2 (NFPA 99)
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0912

Based on observation and interview, the facility failed to maintain electrical receptacles for two of more than fifty receptacles.

Findings include:

Observation on January 28, 2026, between 1:05 p.m. and 1:45 p.m., revealed the facility failed to ensure ground fault circuit interrupter (GFCI) protection in the following areas:

1. (1:05 p.m.) First floor east wing nurse station watercooler;
2. (1:45 p.m.) First floor west wing nurse station watercooler.

Interview with the maintenance supervisor on January 28, 2026, at 1:45 p.m., confirmed the electrical outlet deficiencies.





 Plan of Correction - To be completed: 02/24/2026

1. Ground Fault circuit interrupter (GFCI) outlets have been installed behind both water coolers. 1 on east wing, 1 on west wing.
2. Other outlets near a water source have been inspected for need of a GFCI. No others were found to be missing.
3. Quality Assurance Committee will receive a report of building inspections from Maintenance during monthly meeting. Monitored by administrator.

NFPA 101 STANDARD Electrical Systems - Essential Electric Syste:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70)
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0918

Based on document review and interview, the facility failed to maintain the emergency generator, affecting the entire facility.

Findings include:

Document review on January 28, 2026, at 11:30 a.m., revealed the facility failed to provide documentation for the following tests:

A. Monthly battery conductance test (sealed battery);
B. Annual 90-minute load bank;
C. Three-year, four-hour load test.

Interview with the maintenance supervisor on January 28, 2026, at 11:30 a.m., confirmed the documentation was unavailable at the time of the survey.





 Plan of Correction - To be completed: 02/24/2026

1. Documentation has been provided for the following tests on the emergency generator:
a. Monthly battery conductance test (sealed battery)
b. Annual 90 minute load bank
c. Three year, 4 hour load test.
2. Documentation will be maintained in a specific order in the documentation book for review of life safety individuals.
3. Quality Assurance will receive a monthly report of outside vendor tests conducted and monitored by the Maintenance Director.