Multiple Occupancies - Sections of Ambulatory Health Care Facilities Multiple occupancies shall be in accordance with 6.1.14. Sections of ambulatory health care facilities shall be permitted to be classified as other occupancies, provided they meet both of the following: * The occupancy is not intended to serve ambulatory health care occupants for treatment or customary access. * They are separated from the ambulatory health care occupancy by a 1 hour fire resistance rating. Ambulatory health care facilities shall be separated from other tenants and occupancies and shall meet all of the following: * Walls have not less than 1 hour fire resistance rating and extend from floor slab to roof slab. * Doors are constructed of not less than 1-3/4 inches thick, solid-bonded wood core or equivalent and is equipped with positive latches. * Doors are self-closing and are kept in the closed position, except when in use. * Windows in the barriers are of fixed fire window assemblies per 8.3. Per regulation, ASCs are classified as Ambulatory Health Care Occupancies, regardless of the number of patients served. 20.1.3.2, 21.1.3.3, 20.3.7.1, 21.3.7.1,42 CFR 416.44
|
Observations: Name: CLASS C ASF - Component: 01 - Tag: 0131
Based on observation and interview, it was determined the facility failed to maintain tenant separation walls, affecting one tenant separation wall.
Findings include:
1. Observation on September 27, 2023, at 10:00 am, revealed above patient discharge door, unsealed penetrations around MC wire and a drilled hole.
Interview at the exit conference with the Director of Quality and Maintenance Director on September 27, 2023, at 10:30 am, confirmed the penetrations.
| | Plan of Correction - To be completed: 10/13/2023
The noted penetration will be sealed using high-performance intumescent fire stop sealant - Hilti FS-One #2101531. In addition, the following approved through penetration fire stop system will be used in the location and is kept on file by the Director of Facilities: Hilti System No. C-AJ-8044
Completion Date: October 23, 2023
|
|