Pennsylvania Department of Health
AVALON CARE CENTER
Building Inspection Results

Note: If you need to change the font size, click the "View" menu at the top of the page, place the mouse over the "Text Size" menu item, and select the desired font size.

Severity Designations

Click here for definitions Click here for definitions Click here for definitions Click here for definitions
Minimal Citation - No Harm Minimal Harm Actual Harm Serious Harm
AVALON CARE CENTER
Inspection Results For:

There are  51 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
AVALON CARE CENTER - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000


Based on an Emergency Preparedness Survey completed on June 16, 2026, it was determined that Avalon Care Center had deficiencies that have the potential for minimal harm as related to the requirements of 42 CFR 483.73.






 Plan of Correction:


403.748(d), 416.54(d), 418.113(d), 441.184(d), 482.15(d), 483.475(d), 483.73(d), 484.102(d), 485.542(d), 485.625(d), 485.68(d), 485.727(d), 485.920(d), 486.360(d), 491.12(d), 494.62(d) STANDARD EP Training and Testing:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§403.748(d), §416.54(d), §418.113(d), §441.184(d), §460.84(d), §482.15(d), §483.73(d), §483.475(d), §484.102(d), §485.68(d), §485.542(d), §485.625(d), §485.727(d), §485.920(d), §486.360(d), §491.12(d), §494.62(d).

*[For RNCHIs at §403.748, ASCs at §416.54, Hospice at §418.113, PRTFs at §441.184, PACE at §460.84, Hospitals at §482.15, HHAs at §484.102, CORFs at §485.68, REHs at §485.542, CAHs at §486.625, "Organizations" under 485.727, CMHCs at §485.920, OPOs at §486.360, and RHC/FHQs at §491.12:] (d) Training and testing. The [facility] must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least every 2 years.

*[For LTC facilities at §483.73(d):] (d) Training and testing. The LTC facility must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least annually.

*[For ICF/IIDs at §483.475(d):] Training and testing. The ICF/IID must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least every 2 years. The ICF/IID must meet the requirements for evacuation drills and training at §483.470(i).

*[For ESRD Facilities at §494.62(d):] Training, testing, and orientation. The dialysis facility must develop and maintain an emergency preparedness training, testing and patient orientation program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training, testing and orientation program must be evaluated and updated at every 2 years.
Observations:
Name: - Component: -- - Tag: 0036

Based on document review and interview, the facility failed to develop an emergency preparedness plan that included annual staff emergency preparedness training for one of one plan.

Findings include:

Document review on June 16, 2026, at 10:43 a.m., revealed the facility lacked documentation that annual emergency preparedness training was completed by all staff members for each shift within the previous twelve months.

Interview with the maintenance supervisor on June 16, 2026, at 10:43 a.m., confirmed the facility lacked the training documentation at the time of the survey.






 Plan of Correction - To be completed: 07/16/2026

Facility will develop an emergency preparedness plan to include annual staff training. The training and testing program will be reviewed and updated at least annually. The director of maintenance will present to The Quality Assement and Performance Committee to review updates and training/testing of staff.
403.748(d)(2), 416.54(d)(2), 418.113(d)(2), 441.184(d)(2), 482.15(d)(2), 483.475(d)(2), 483.73(d)(2), 484.102(d)(2), 485.542(d)(2), 485.625(d)(2), 485.68(d)(2), 485.727(d)(2), 485.920(d)(2), 486.360(d)(2), 491.12(d)(2), 494.62(d)(2) STANDARD EP Testing Requirements:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§416.54(d)(2), §418.113(d)(2), §441.184(d)(2), §460.84(d)(2), §482.15(d)(2), §483.73(d)(2), §483.475(d)(2), §484.102(d)(2), §485.68(d)(2), §485.542(d)(2), §485.625(d)(2), §485.727(d)(2), §485.920(d)(2), §491.12(d)(2), §494.62(d)(2).

*[For ASCs at §416.54, CORFs at §485.68, REHs at §485.542, OPO, "Organizations" under §485.727, CMHCs at §485.920, RHCs/FQHCs at §491.12, and ESRD Facilities at §494.62]:

(2) Testing. The [facility] must conduct exercises to test the emergency plan annually. The [facility] must do all of the following:

(i) Participate in a full-scale exercise that is community-based every 2 years; or
(A) When a community-based exercise is not accessible, conduct a facility-based functional exercise every 2 years; or
(B) If the [facility] experiences an actual natural or man-made emergency that requires activation of the emergency plan, the [facility] is exempt from engaging in its next required community-based or individual, facility-based functional exercise following the onset of the actual event.
(ii) Conduct an additional exercise at least every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [facility's] response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the [facility's] emergency plan, as needed.

*[For Hospices at 418.113(d):]
(2) Testing for hospices that provide care in the patient's home. The hospice must conduct exercises to test the emergency plan at least annually. The hospice must do the following:
(i) Participate in a full-scale exercise that is community based every 2 years; or
(A) When a community based exercise is not accessible, conduct an individual facility based functional exercise every 2 years; or
(B) If the hospice experiences a natural or man-made emergency that requires activation of the emergency plan, the hospital is exempt from engaging in its next required full scale community-based exercise or individual facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.

(3) Testing for hospices that provide inpatient care directly. The hospice must conduct exercises to test the emergency plan twice per year. The hospice must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual facility-based functional exercise; or
(B) If the hospice experiences a natural or man-made emergency that requires activation of the emergency plan, the hospice is exempt from engaging in its next required full-scale community based or facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop led by a facilitator that includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the hospice's response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the hospice's emergency plan, as needed.


*[For PRFTs at §441.184(d), Hospitals at §482.15(d), CAHs at §485.625(d):]
(2) Testing. The [PRTF, Hospital, CAH] must conduct exercises to test the emergency plan twice per year. The [PRTF, Hospital, CAH] must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or
(B) If the [PRTF, Hospital, CAH] experiences an actual natural or man-made emergency that requires activation of the emergency plan, the [facility] is exempt from engaging in its next required full-scale community based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an [additional] annual exercise or and that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, a facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [facility's] response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the [facility's] emergency plan, as needed.

*[For PACE at §460.84(d):]
(2) Testing. The PACE organization must conduct exercises to test the emergency plan at least annually. The PACE organization must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or
(B) If the PACE experiences an actual natural or man-made emergency that requires activation of the emergency plan, the PACE is exempt from engaging in its next required full-scale community based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the PACE's response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the PACE's emergency plan, as needed.

*[For LTC Facilities at §483.73(d):]
(2) The [LTC facility] must conduct exercises to test the emergency plan at least twice per year, including unannounced staff drills using the emergency procedures. The [LTC facility, ICF/IID] must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise.
(B) If the [LTC facility] facility experiences an actual natural or man-made emergency that requires activation of the emergency plan, the LTC facility is exempt from engaging its next required a full-scale community-based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [LTC facility] facility's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the [LTC facility] facility's emergency plan, as needed.

*[For ICF/IIDs at §483.475(d)]:
(2) Testing. The ICF/IID must conduct exercises to test the emergency plan at least twice per year. The ICF/IID must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or.
(B) If the ICF/IID experiences an actual natural or man-made emergency that requires activation of the emergency plan, the ICF/IID is exempt from engaging in its next required full-scale community-based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the ICF/IID's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the ICF/IID's emergency plan, as needed.

*[For HHAs at §484.102]
(d)(2) Testing. The HHA must conduct exercises to test the emergency plan at
least annually. The HHA must do the following:
(i) Participate in a full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise every 2 years; or.
(B) If the HHA experiences an actual natural or man-made emergency that requires activation of the emergency plan, the HHA is exempt from engaging in its next required full-scale community-based or individual, facility based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the HHA's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the HHA's emergency plan, as needed.

*[For OPOs at §486.360]
(d)(2) Testing. The OPO must conduct exercises to test the emergency plan. The OPO must do the following:
(i) Conduct a paper-based, tabletop exercise or workshop at least annually. A tabletop exercise is led by a facilitator and includes a group discussion, using a narrated, clinically relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan. If the OPO experiences an actual natural or man-made emergency that requires activation of the emergency plan, the OPO is exempt from engaging in its next required testing exercise following the onset of the emergency event.
(ii) Analyze the OPO's response to and maintain documentation of all tabletop exercises, and emergency events, and revise the [RNHCI's and OPO's] emergency plan, as needed.

*[ RNCHIs at §403.748]:
(d)(2) Testing. The RNHCI must conduct exercises to test the emergency plan. The RNHCI must do the following:
(i) Conduct a paper-based, tabletop exercise at least annually. A tabletop exercise is a group discussion led by a facilitator, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(ii) Analyze the RNHCI's response to and maintain documentation of all tabletop exercises, and emergency events, and revise the RNHCI's emergency plan, as needed.
Observations:
Name: - Component: -- - Tag: 0039

Based on document review and interview, the facility failed to exercise, test, and evaluate an emergency plan on a full-scale basis.

Findings include:

Document review on June 16, 2026, at 10:45 a.m., revealed the facility lacked documentation that the emergency plan was exercised, tested, and evaluated for each shift on a full-scale and that a documented tabletop drill was completed.

Interview with the administrator on June 16, 2026, at 10:45 a.m., confirmed the lack of documentation.






 Plan of Correction - To be completed: 07/16/2026

Facility will ensure that an exercise test and evaluated emergency plan is completed at least twice per year. This will be documented by the Director of Maintenance and reviewed by the Nursing Home Administrator for compliance. Additionally, tabletop drills will be performed on each shift. Director of Maintenance will review outcomes with Quality Assement and Performance Committee.
Initial comments:Name: MAIN BUILDING 01 - Component: 01 - Tag: 0000


Facility ID #194102
Component 01
Main Building

Based on a Medicare/Medicaid Recertification Survey completed on June 16, 2026, it was determined that Avalon Care Center was not in compliance with the following requirements of the Life Safety Code for an existing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a one-story, Type V (000), unprotected, wood frame building, that is fully sprinklered.





 Plan of Correction:


NFPA 101 STANDARD General Requirements - Other:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
General Requirements - Other
List in the REMARKS section any LSC Section 18.1 and 19.1 General Requirements that are not addressed by the provided K-tags, but are deficient. This information, along with the applicable Life Safety Code or NFPA standard citation, should be included on Form CMS-2567.
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0100

Based on document review, observation, and interview, the facility failed to maintain portable floor plans that outlined designated rated partitions, affecting the entire facility.

Findings include:

Document review on June 16, 2026, at 9:05 a.m., revealed the facility failed to provide a set of accurate, portable floor plans. The Division of Safety Inspection is requiring that all facilities under its jurisdiction provide a portable, accurate floor plan on-site, to be used during the Life Safety Code Survey.

The Life Safety Code Floor Plan shall include the following:

a. Smoke barrier walls (outside wall to outside wall);
b. Fire barrier walls (1-2 hour walls);
c. Horizontal exits;
d. Rated rooms (storage rooms, soiled utility rooms, designated medical gas rooms) will be clearly designated. It is the facility's responsibility to have all rated rooms indicated on its Life Safety Code Floor Plan;
e. Required exits should be clearly noted;
f. Shaft walls.

Interview with the maintenance supervisor on June 16, 2026, at 9:05 a.m., confirmed the Life Safety Code Floor Plan provided during the survey failed to accurately contain the listed items.




 Plan of Correction - To be completed: 07/16/2026

Facility will revise all floor plans to include the following smoke barrier walls, fire barrier walls, horizontal exits, rate rooms exit clearly noted, and shaft walls. The Director of Maintenance with the Nursing Home Administrator will review for accuracy. New floor plan will be presented to QAPI for review.
NFPA 101 STANDARD Fire Alarm System - Testing and Maintenance:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0345

Based on observation and interview, the facility failed to meet fire alarm system maintenance and testing requirements for one of one system.

Findings include:

Observation on June 16, 2026, at 11:20 a.m., revealed a trouble signal on the fire alarm panel at the time of the survey.

Interview with the maintenance supervisor on June 16, 2026, at 11:20 a.m., confirmed the deficiency.




 Plan of Correction - To be completed: 07/16/2026

On 06/22/2026 an outside vendor repaired the fire alarm panel showing that had a trouble signal showing. The Maintenance department has supporting documentation of the repair.
NFPA 101 STANDARD Sprinkler System - Maintenance and Testing:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0353

Based on observation and interview, the facility failed to meet sprinkler system maintenance and testing requirements for one of one system.

Findings include:

Observation on June 16, 2026, at 10:55 a.m., revealed the facility's fire department connection failed to have a cap secured to the inlet or signage identifying the location that was unobstructed from the roadway.

Interview with the maintenance supervisor on June 16, 2026, at 10:55 a.m., confirmed the deficiency at the time of the survey.







 Plan of Correction - To be completed: 07/16/2026

The Maintenance Department will ensure all testing and maintenance for the sprinkler system is completed in accordance with NFPA-25 standards. Date of service, provider name, and water supply source will all be documented and kept at the facility. Also, maintenance will install a new cap to the inlet, identifying the location that was unobstructed from the roadway.
NFPA 101 STANDARD Fire Drills:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
19.7.1.4 through 19.7.1.7
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0712

Based on document review and interview, the facility failed to meet fire drill requirements for two of three shifts.

Findings include:

Document review on June 16, 2026, at 8:30 a.m., revealed the following shifts lacked unexpected fire drills that varied in time and condition:

A. (8:30 a.m.) Second shift, first quarter;
B. (8:30 a.m.) Third shift, second quarter.

Interview with the administrator and maintenance technician on June 16, 2026, at 8:30 a.m., confirmed the fire drill deficiencies.









 Plan of Correction - To be completed: 07/16/2026

The Maintenance Department will be reeducated on meeting the required standard for fire drills by the Nursing Home Administrator. Maintenance director will review supporting documentation at least quarterly to QAPI to ensure compliance.
NFPA 101 STANDARD Electrical Systems - Essential Electric Syste:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70)
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0918

Based on document review and interview, the facility failed to maintain essential electric system maintenance and testing for one of one emergency generator.

Findings include:

Document review on June 16, 2026, at 10:26 a.m., revealed the facility lacked the following emergency generator testing documentation for four of twelve months:

A) Monthly thirty-minute load testing;
B) Monthly battery testing, specific gravity or conductance;
C) Weekly battery voltage and visual inspection.

Interview with the maintenance supervisor on June 16, 2026, at 10:26 a.m., confirmed the generator documentation was unavailable at the time of the survey.





 Plan of Correction - To be completed: 07/16/2026

Maintenance Department will be reeducated on essential electric system maintenance and testing for emergency generators by the Nursing Home Administrator. Education will include monthly 30-minute load testing, monthly battery testing, weekly battery voltage and visual inspection. Maintenance department will review all documentation monthly with the Nursing Home Administrator.
Initial comments:Name: BUILDING 02 - Component: 02 - Tag: 0000


Facility ID #194102
Component 02
Constructed 1962

Based on a Medicare/Medicaid Recertification Survey completed on June 16, 2026, it was determined that Avalon Care Center was not in compliance with the following requirements of the Life Safety Code for an existing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a one-story, Type V (000), unprotected, wood frame building, that is fully sprinklered.






 Plan of Correction:


NFPA 101 STANDARD General Requirements - Other:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
General Requirements - Other
List in the REMARKS section any LSC Section 18.1 and 19.1 General Requirements that are not addressed by the provided K-tags, but are deficient. This information, along with the applicable Life Safety Code or NFPA standard citation, should be included on Form CMS-2567.
Observations:
Name: BUILDING 02 - Component: 02 - Tag: 0100

Based on document review, observation, and interview, the facility failed to maintain portable floor plans that outlined designated rated partitions, affecting the entire facility.

Findings include:

Document review on June 16, 2026, at 9:05 a.m., revealed the facility failed to provide a set of accurate, portable floor plans. The Division of Safety Inspection is requiring that all facilities under its jurisdiction provide a portable, accurate floor plan on-site, to be used during the Life Safety Code Survey.

The Life Safety Code Floor Plan shall include the following:

a. Smoke barrier walls (outside wall to outside wall);
b. Fire barrier walls (1-2 hour walls);
c. Horizontal exits;
d. Rated rooms (storage rooms, soiled utility rooms, designated medical gas rooms) will be clearly designated. It is the facility's responsibility to have all rated rooms indicated on its Life Safety Code Floor Plan;
e. Required exits should be clearly noted;
f. Shaft walls.

Interview with the maintenance supervisor on June 16, 2026, at 9:05 a.m., confirmed the Life Safety Code Floor Plan provided during the survey failed to accurately contain the listed items.




 Plan of Correction - To be completed: 07/16/2026

Facility will revise all floor plans to include the following smoke barrier walls, fire barrier walls, horizontal exits, rate rooms exit clearly noted, and shaft walls. The Director of Maintenance with the Nursing Home Administrator will review for accuracy. New floor plan will be presented to QAPI for review.
NFPA 101 STANDARD Subdivision of Building Spaces - Smoke Barrie:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Subdivision of Building Spaces - Smoke Barrier Doors
2012 EXISTING
Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors.
19.3.7.6, 19.3.7.8, 19.3.7.9
Observations:
Name: BUILDING 02 - Component: 02 - Tag: 0374

Based on observation and interview, the facility failed to meet smoke barrier door requirements for one of one system.

Findings include:

Observation on June 16, 2026, at 11:11 a.m., revealed the smoke barrier door near room 209 failed to positively latch at the time of the survey.

Interview with the maintenance supervisor on June 16, 2026, at 11:11 a.m., confirmed the deficiency.




 Plan of Correction - To be completed: 07/16/2026

On June 16th, 2026, Maintenance adjusted the barrier doors near room 209 and it is now positively latching. Maintenance will perform an audit of all smoke barrier doors to ensure all doors are positively latching.
NFPA 101 STANDARD Fire Drills:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
19.7.1.4 through 19.7.1.7
Observations:
Name: BUILDING 02 - Component: 02 - Tag: 0712

Based on document review and interview, the facility failed to meet fire drill requirements for two of three shifts.

Findings include:

Document review on June 16, 2026, at 8:30 a.m., revealed the following shifts lacked unexpected fire drills that varied in time and condition:

A. (8:30 a.m.) Second shift, first quarter;
B. (8:30 a.m.) Third shift, second quarter.

Interview with the administrator and maintenance technician on June 16, 2026, at 8:30 a.m., confirmed the fire drill deficiencies.






 Plan of Correction - To be completed: 07/16/2026

The Maintenance Department will be reeducated on meeting the required standard for fire drills by the Nursing Home Administrator. Maintenance director will review supporting documentation at least quarterly to QAPI to ensure compliance.
NFPA 101 STANDARD Electrical Systems - Essential Electric Syste:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70)
Observations:
Name: BUILDING 02 - Component: 02 - Tag: 0918

Based on document review and interview, the facility failed to maintain essential electric system maintenance and testing for one of one emergency generator.

Findings include:

Document review on June 16, 2026, at 10:26 a.m., revealed the facility lacked the following emergency generator testing documentation for four of twelve months:

A) Monthly thirty-minute load testing;
B) Monthly battery testing, specific gravity or conductance;
C) Weekly battery voltage and visual inspection.

Interview with the maintenance supervisor on June 16, 2026, at 10:26 a.m., confirmed the generator documentation was unavailable at the time of the survey.




 Plan of Correction - To be completed: 07/16/2026

Maintenance Department will be reeducated on essential electric system maintenance and testing for emergency generators by the Nursing Home Administrator. Education will include monthly 30-minute load testing, monthly battery testing, weekly battery voltage and visual inspection. Maintenance department will review all documentation monthly with the Nursing Home Administrator.
Initial comments:Name: BUILDING 03 - Component: 03 - Tag: 0000


Facility ID #194102
Component 03
Construction 2002

Based on a Medicare/Medicaid Recertification Survey completed on June 6, 2026, it was determined that Avalon Care Center was not in compliance with the following requirements of the Life Safety Code for an existing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a one-story, Type V (111), protected, wood frame building, that is fully sprinklered.





 Plan of Correction:


NFPA 101 STANDARD General Requirements - Other:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
General Requirements - Other
List in the REMARKS section any LSC Section 18.1 and 19.1 General Requirements that are not addressed by the provided K-tags, but are deficient. This information, along with the applicable Life Safety Code or NFPA standard citation, should be included on Form CMS-2567.
Observations:
Name: BUILDING 03 - Component: 03 - Tag: 0100

Based on document review, observation, and interview, the facility failed to maintain portable floor plans that outlined designated rated partitions, affecting the entire facility.

Findings include:

Document review on June 16, 2026, at 9:05 a.m., revealed the facility failed to provide a set of accurate, portable floor plans. The Division of Safety Inspection is requiring that all facilities under its jurisdiction provide a portable, accurate floor plan on-site, to be used during the Life Safety Code Survey.

The Life Safety Code Floor Plan shall include the following:

a. Smoke barrier walls (outside wall to outside wall);
b. Fire barrier walls (1-2 hour walls);
c. Horizontal exits;
d. Rated rooms (storage rooms, soiled utility rooms, designated medical gas rooms) will be clearly designated. It is the facility's responsibility to have all rated rooms indicated on its Life Safety Code Floor Plan;
e. Required exits should be clearly noted;
f. Shaft walls.

Interview with the maintenance supervisor on June 16, 2026, at 9:05 a.m., confirmed the Life Safety Code Floor Plan provided during the survey failed to accurately contain the listed items.



 Plan of Correction - To be completed: 07/16/2026

Facility will revise all floor plans to include the following smoke barrier walls, fire barrier walls, horizontal exits, rate rooms exit clearly noted, and shaft walls. The Director of Maintenance with the Nursing Home Administrator will review for accuracy. New floor plan will be presented to QAPI for review.
NFPA 101 STANDARD Fire Drills:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
19.7.1.4 through 19.7.1.7
Observations:
Name: BUILDING 03 - Component: 03 - Tag: 0712

Based on document review and interview, the facility failed to meet fire drill requirements for two of three shifts.

Findings include:

Document review on June 16, 2026 at 8:30 a.m., revealed the following shifts lacked unexpected fire drills that varied in time and condition:

A. (8:30 a.m.) Second shift, first quarter;
B. (8:30 a.m.) Third shift, second quarter.

Interview with the administrator and maintenance technician on June 16, 2026, at 8:30 a.m., confirmed the fire drill deficiencies.





 Plan of Correction - To be completed: 07/16/2026

The Maintenance Department will be reeducated on meeting the required standard for fire drills by the Nursing Home Administrator. Maintenance director will review supporting documentation at least quarterly to QAPI to ensure compliance.
NFPA 101 STANDARD Electrical Systems - Essential Electric Syste:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70)
Observations:
Name: BUILDING 03 - Component: 03 - Tag: 0918

Based on document review and interview, the facility failed to maintain essential electric system maintenance and testing for one of one emergency generator.

Findings include:

Document review on June 16, 2026, at 10:26 a.m., revealed the facility lacked the following emergency generator testing documentation for four of twelve months:

A) Monthly thirty-minute load testing;
B) Monthly battery testing, specific gravity or conductance;
C) Weekly battery voltage and visual inspection.

Interview with the maintenance supervisor on June 16, 2026, at 10:26 a.m., confirmed the generator documentation was unavailable at the time of the survey.





 Plan of Correction - To be completed: 07/16/2026

Maintenance Department will be reeducated on essential electric system maintenance and testing for emergency generators by the Nursing Home Administrator. Education will include monthly 30-minute load testing, monthly battery testing, weekly battery voltage and visual inspection. Maintenance department will review all documentation monthly with the Nursing Home Administrator.

Back to County Map


  
Home : Press Releases : Administration
Health Planning and Assessment : Office of the Secretary
Health Promotion and Disease Prevention : Quality Assurance



Copyright © 2001 Commonwealth of Pennsylvania. All Rights Reserved.
Commonwealth of PA Privacy Statement

Visit the PA Power Port