Pennsylvania Department of Health
STATESMAN HEALTH & REHABILITATION CENTER
Building Inspection Results

Note: If you need to change the font size, click the "View" menu at the top of the page, place the mouse over the "Text Size" menu item, and select the desired font size.

Severity Designations

Click here for definitions Click here for definitions Click here for definitions Click here for definitions
Minimal Citation - No Harm Minimal Harm Actual Harm Serious Harm
STATESMAN HEALTH & REHABILITATION CENTER
Inspection Results For:

There are  45 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
STATESMAN HEALTH & REHABILITATION CENTER - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000
Based on an Emergency Preparedness Survey completed on August 25, 2026, at Statesman Health &; Rehabilitation Center, it was determined there were no deficiencies identified with the requirements of 42 CFR 483.73.
 Plan of Correction:


Initial comments:Name: MAIN BUILDING 01 (ORIGINAL BUILDING) - Component: 01 - Tag: 0000
Facility ID# 193702Component 01Main BuildingBased on a Medicare/Medicaid Recertification Survey completed on August 25, 2026, it was determined that Statesman Health &; Rehabilitation Center - Main Building, was not in compliance with the following requirements of the Life Safety Code for an existing Nursing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).This is a one-story, Type II (000), unprotected non-combustible building, that is fully sprinklered.
 Plan of Correction:


NFPA 101 STANDARD Egress Doors:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
Observations:
Name: MAIN BUILDING 01 (ORIGINAL BUILDING) - Component: 01 - Tag: 0222 Based on observation and interview, it was determined the facility failed to maintain egress doors with delayed-egress locking systems, affecting one of four smoke compartments. Findings include: 1. Observation on August 25, 2026, at 12:40 p.m., revealed the delayed-egress door inside middle hall, did released after 15 seconds when tested, but did not open easily without the use of excessive force. Interview at the exit conference with the Administrator, Maintenance Director and staff on August 25, 2026, at 1:30 p.m., confirmed the delayed egress door needed excessive force to open.
 Plan of Correction - To be completed: 09/25/2026

0222
Middle Hall door shaved down on its side for easy open/closure.
Five random delayed-egress doors will be randomly audited weekly x90 days for easy opening/closing.
Results of the audits will be submitted to QAPI committee for review and resolution.


NFPA 101 STANDARD Hazardous Areas - Enclosure:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Hazardous Areas - Enclosure
Hazardous areas are protected by a fire barrier having 1-hour fire resistance rating (with 3/4 hour fire rated doors) or an automatic fire extinguishing system in accordance with 8.7.1 or 19.3.5.9. When the approved automatic fire extinguishing system option is used, the areas shall be separated from other spaces by smoke resisting partitions and doors in accordance with 8.4. Doors shall be self-closing or automatic-closing and permitted to have nonrated or field-applied protective plates that do not exceed 48 inches from the bottom of the door.
Describe the floor and zone locations of hazardous areas that are deficient in REMARKS.
19.3.2.1, 19.3.5.9

Area Automatic Sprinkler Separation N/A
a. Boiler and Fuel-Fired Heater Rooms
b. Laundries (larger than 100 square feet)
c. Repair, Maintenance, and Paint Shops
d. Soiled Linen Rooms (exceeding 64 gallons)
e. Trash Collection Rooms
(exceeding 64 gallons)
f. Combustible Storage Rooms/Spaces
(over 50 square feet)
g. Laboratories (if classified as Severe
Hazard - see K322)
Observations:
Name: MAIN BUILDING 01 (ORIGINAL BUILDING) - Component: 01 - Tag: 0321 Based on observation and interview, it was determined the facility failed to maintain the fire resistance rating of hazardous areas, affecting two of four smoke compartments. Findings include: 1. Observation on August 25, 2026, at 12:10 p.m., revealed the D-wing main laundry, double door entrance, both doors did not close and latch unassisted. Doors are equipped with automatic closures. Interview at the exit conference with the Administrator, Maintenance Director and staff on August 25, 2026, at 1:30 p.m., confirmed the doors failed to latch and hold. 2. Observation made on August 25, 2026, at 11:10 a.m., revealed that the back room inside the B-Wing Shower was being used for temporary storage. The temp storage room's door was not equipped with a door closure. Interview at the exit conference with the Administrator, Maintenance Director and staff on August 25, 2026, at 1:30 p.m., confirmed the door was not equipped with a door closure.
 Plan of Correction - To be completed: 09/25/2026

0321
D wing main laundry double doors adjusted to open/close and latch properly.
Door closure was installed on B wing shower door.
Five random facility double doors will be audited for proper opening, closing and latching weekly x90 days. Five random storage room doors will be audited for door closures weekly x90 days.
Results of the audits will be submitted to QAPI committee for review and resolution.


NFPA 101 STANDARD Portable Fire Extinguishers:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Portable Fire Extinguishers
Portable fire extinguishers are selected, installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers.
18.3.5.12, 19.3.5.12, NFPA 10
Observations:
Name: MAIN BUILDING 01 (ORIGINAL BUILDING) - Component: 01 - Tag: 0355 Based on observation and interview, it was determined the facility failed to ensure portable fire extinguishers were accessible and inspected at required intervals, affecting one of four smoke compartments. Findings include: 1. Observation on August 25, 2026, at 8:30 a.m., revealed the wall mounted portable fire extinguisher holder in the exterior patio area, had a missing fire extinguisher. Interview at the exit conference with the Administrator, Maintenance Director and staff on August 25, 2026, at 1:30 p.m., confirmed the missing fire extinguisher in the smoker's area.
 Plan of Correction - To be completed: 09/25/2026

0355
Fire Extinguisher placed in holder of the exterior patio area.
5 random fire extinguisher holders will be audited weekly x90 days for a fire extinguisher.
Results of the audits will be submitted to QAPI committee for review and resolution.


NFPA 101 STANDARD Corridor - Doors:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Corridor - Doors
Doors protecting corridor openings in other than required enclosures of vertical openings, exits, or hazardous areas resist the passage of smoke and are made of 1 3/4 inch solid-bonded core wood or other material capable of resisting fire for at least 20 minutes. Doors in fully sprinklered smoke compartments are only required to resist the passage of smoke. Corridor doors and doors to rooms containing flammable or combustible materials have positive latching hardware. Roller latches are prohibited by CMS regulation. These requirements do not apply to auxiliary spaces that do not contain flammable or combustible material.
Clearance between bottom of door and floor covering is not exceeding 1 inch. Powered doors complying with 7.2.1.9 are permissible if provided with a device capable of keeping the door closed when a force of 5 lbf is applied. There is no impediment to the closing of the doors. Hold open devices that release when the door is pushed or pulled are permitted. Nonrated protective plates of unlimited height are permitted. Dutch doors meeting 19.3.6.3.6 are permitted. Door frames shall be labeled and made of steel or other materials in compliance with 8.3, unless the smoke compartment is sprinklered. Fixed fire window assemblies are allowed per 8.3. In sprinklered compartments there are no restrictions in area or fire resistance of glass or frames in window assemblies.

19.3.6.3, 42 CFR Parts 403, 418, 460, 482, 483, and 485
Show in REMARKS details of doors such as fire protection ratings, automatics closing devices, etc.
Observations:
Name: MAIN BUILDING 01 (ORIGINAL BUILDING) - Component: 01 - Tag: 0363 Based on observation and interview, it was determined the facility failed to maintain corridor doors in one of approximately thirty locations inspected. Findings include: 1. Observation on August 25, 2026, at 1:00 p.m., revealed the double dining rooms doors that were equipped with a newer in-line door coordinator did not positively latch and hold due to lack of an auto activating door flush bolt latch, on the strike panel door. Interview at the exit conference with the Administrator, Maintenance Director and staff on August 25, 2026, at 1:30 p.m., confirmed the doors could be pulled or pushed open after closing.
 Plan of Correction - To be completed: 09/25/2026

0363
Door flush bolt latch installed on the strike of the double dining room doors.
5 random facility doors will be audited that they cannot be pushed or pulled open after closing, weekly x90 days.
Results of the audits will be submitted to QAPI committee for review and resolution.

NFPA 101 STANDARD Subdivision of Building Spaces - Smoke Barrie:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Subdivision of Building Spaces - Smoke Barrier Doors
2012 EXISTING
Doors in smoke barriers are 1-3/4-inch thick solid bonded wood-core doors or of construction that resists fire for 20 minutes. Nonrated protective plates of unlimited height are permitted. Doors are permitted to have fixed fire window assemblies per 8.5. Doors are self-closing or automatic-closing, do not require latching, and are not required to swing in the direction of egress travel. Door opening provides a minimum clear width of 32 inches for swinging or horizontal doors.
19.3.7.6, 19.3.7.8, 19.3.7.9
Observations:
Name: MAIN BUILDING 01 (ORIGINAL BUILDING) - Component: 01 - Tag: 0374 Based on observation and interview, it was determined the facility failed to ensure doors in smoke barrier walls were maintained to resist the passage of smoke, affecting two of four smoke compartments. Findings include: 1. Observation on August 25, 2026, at 10:45 a.m., revealed, the smoke barrier doors (B-Wing) failed to close smoke tight due to a malfunction with the door coordinator. Interview at the exit conference with the Administrator, Maintenance Director and staff on August 25, 2026, at 1:30 p.m., confirmed the door coordinator failed.
 Plan of Correction - To be completed: 09/25/2026

0374
Door coordinator adjusted on B wing smoke barrier doors.
5 random smoke barrier doors will be audited for proper close, weekly x90 days.
Results of the audits will be submitted to QAPI committee for review and resolution.

Initial comments:Name: BUILDING 02 (PHYSICAL THERAPY BUILDING) - Component: 02 - Tag: 0000
Facility ID# 193702Component 02Physical Therapy AdditionBased on a Medicare/Medicaid Recertification Survey completed on August 25, 2026, at Statesman Health and Rehabilitation Center - Physical Therapy Addition, it was determined there were no deficiencies identified under the requirements of the Life Safety Code for an existing Nursing health care occupancy.  Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.70(a).This is a one-story building, Type V (111), protected wood frame building, that is fully sprinklered.
 Plan of Correction: