Pennsylvania Department of Health
RADIANCE - A PRIVATE OUTPATIENT SURGERY CENTER, LLC
Building Inspection Results

Note: If you need to change the font size, click the "View" menu at the top of the page, place the mouse over the "Text Size" menu item, and select the desired font size.

Severity Designations

Click here for definitions Click here for definitions Click here for definitions Click here for definitions
Minimal Citation - No Harm Minimal Harm Actual Harm Serious Harm
RADIANCE - A PRIVATE OUTPATIENT SURGERY CENTER, LLC
Inspection Results For:

There are  8 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
RADIANCE - A PRIVATE OUTPATIENT SURGERY CENTER, LLC - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: MAIN BUILDING - Component: 02 - Tag: 0000

Facility ID# 17601501
Component 02
Main Building

Based on a Relicensure Survey completed on September 12, 2023, it was determined that Radiance-A Private Outpatient Surgery Center was not in compliance with the following requirements of the Life Safety Code for an existing Ambulatory health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 28 Pa Code 569.2.

This is a two-story, Type III (200), unprotected ordinary building, without a basement, that is fully sprinklered.



 Plan of Correction:


28 Pa. Code § 569.2 STANDARD Hazardous Areas - Enclosure:State only Deficiency.
Hazardous Areas - Enclosure
Hazardous areas must meet one of the following:
*Contain 1 hour rated enclosure when non-sprinklered
*Sprinkler protected with smoke resistive separation
*Severe Hazard locations contain sprinkler protection and 1 hour separation with 3/4 hour rated self-closing doors
20.3.2, 21.3.2, 38.3.2, 38.3.2.2, 39.3.2.1, 39.3.2.2, 8.7
Observations:
Name: MAIN BUILDING - Component: 02 - Tag: 0321


Based on observation and interview, it was determined the facility failed to maintain hazardous area enclosures in one instance, affecting the entire facility.

Findings include:

1. Observation on September 12, 2023, at 10:25 a.m., revealed the door seperating the clean utility to central sterile was not equipped with a self closure.

Interview with the Director of Nursing and the Maintenance Manager on September 12, 2023, at 11:30 a.m., confirmed the hazardous area enclosure deficiency.




 Plan of Correction - To be completed: 09/19/2023

On 9-16-23 the facility manager installed an automatic self door closure on the door separating the clean utility to central sterile.