SURGERY CENTER AT CRANBERRY, THE - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: MAIN BUILDING 01 - Component: 01 - Tag: 0000


Facility ID #16591501
Component 01
Main Building

Based on a Relicensure Survey completed on August 28, 2024, it was determined that The Surgery Center at Cranberry was not in compliance with the following requirements of the Life Safety Code for an existing ambulatory health care occupancy.

This is a two-story, Type II (000), unprotected, non-combustible building, that is fully sprinklered.




 Plan of Correction:


28 Pa. Code § 569.2 STANDARD Sprinkler System - Maintenance and Testing:State only Deficiency.
Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available.
a) Date sprinkler system last checked _____________________
b) Who provided system test ____________________________
c) Water system supply source __________________________
Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0353
Based on document review and interview, the facility failed to meet sprinkler system requirements for one of two sprinkler systems.

Findings include:

Document review on August 28, 2024, at 10:00 a.m., revealed the facility failed to provide documentation for a recent three-year full flow trip test.

Interview with the administrator on August 28, 2024, at 10:00 a.m., confirmed the sprinkler system deficiency.



 Plan of Correction - To be completed: 09/06/2024

The full flow trip test will be performed every three years. A contractor (S.A. Comunale) has been secured to perform a three-year full flow trip test. This test is scheduled for 9/6/2024.

A maintenance checklist will list "3 year Full Flow Trip Test". This checklist will be reviewed by the Facility Administrator monthly. A report will be addressed with the QA committee at the quarterly QA meeting.