Hazardous Areas - Enclosure Hazardous areas are protected by a fire barrier having 1-hour fire resistance rating (with 3/4 hour fire rated doors) or an automatic fire extinguishing system in accordance with 8.7.1 or 19.3.5.9. When the approved automatic fire extinguishing system option is used, the areas shall be separated from other spaces by smoke resisting partitions and doors in accordance with 8.4. Doors shall be self-closing or automatic-closing and permitted to have nonrated or field-applied protective plates that do not exceed 48 inches from the bottom of the door. Describe the floor and zone locations of hazardous areas that are deficient in REMARKS. 19.3.2.1, 19.3.5.9
Area Automatic Sprinkler Separation N/A a. Boiler and Fuel-Fired Heater Rooms b. Laundries (larger than 100 square feet) c. Repair, Maintenance, and Paint Shops d. Soiled Linen Rooms (exceeding 64 gallons) e. Trash Collection Rooms (exceeding 64 gallons) f. Combustible Storage Rooms/Spaces (over 50 square feet) g. Laboratories (if classified as Severe Hazard - see K322)
|
Observations: Name: MAIN BUILDING 01 (WOOLMAN & BARCLAY LEVELS) - Component: 01 - Tag: 0321
Based on observation and interview, it was determined the facility failed to maintain a hazardous area enclosure on 1 of 2 levels of the facility.
Findings include:
1. Observation on September 1, 2026, between 10:30 a.m. and 11:45 a.m., revealed:Soiled room door, next to room W27, failed to self-close and latch.
b) Office admin area, that doubles as document storage, had a door equipped with a damaged door closure.
Exit interview with the Administrator and Maintenance Team on September 1, 2026, at 12:00 p.m., confirmed the above deficiencies.\'c2
| | Plan of Correction - To be completed: 09/24/2026
The facility has and shall continue to maintain hazardous area enclosure. A work order has been issued to repair the door to the Soiled Linen door next to W27 on September 16, 2026 and was completed on September 18, 2026. A work order has also been issued to replace the damaged door closer on the entrance to the Office Admin area. A work order has been issued on September 16, 2026 to be completed by September 23, 2026.
The Maintenance Manager/Designee will continue to oversee the inspection and repair of all hazardous area enclosures. Results of ongoing inspections and repairs will be reported to the Quality Assurance and Performance Improvement (QAPI) Team by the Maintenance Manager/Designee.
|
|