Building Construction Type and Height 2012 EXISTING Building construction type and stories meets Table 19.1.6.1, unless otherwise permitted by 19.1.6.2 through 19.1.6.7 19.1.6.4, 19.1.6.5
Construction Type 1 I (442), I (332), II (222) Any number of stories non-sprinklered and sprinklered 2 II (111) One story non-sprinklered Maximum 3 stories sprinklered 3 II (000) Not allowed non-sprinklered 4 III (211) Maximum 2 stories sprinklered 5 IV (2HH) 6 V (111) 7 III (200) Not allowed non-sprinklered 8 V (000) Maximum 1 story sprinklered Sprinklered stories must be sprinklered throughout by an approved, supervised automatic system in accordance with section 9.7. (See 19.3.5) Give a brief description, in REMARKS, of the construction, the number of stories, including basements, floors on which patients are located, location of smoke or fire barriers and dates of approval. Complete sketch or attach small floor plan of the building as appropriate.
|
Observations: Name: MAIN BUILDING - Component: 01 - Tag: 0161
Based on observation, document review and interview, it was determined the facility failed to maintain building construction requirements, such as a minimum two-hour fire resistive rating of structural components throughout the building, affecting the entire component.
Findings include:
1. Interview, observation and document review on March 14, 2018, between 8:00 a.m. and 11:00 a.m., revealed the building is a seven story, Type II (000) unprotected noncombustible structure. This type of construction exceeds the maximum story height allowed.
Exit Interview with the Director, Facilities Services, on March 15, 2018, at 2:30 p.m., confirmed the building construction type and height. **********************************
Based on an Onsite Revisit conducted on November 13, 2023, between 11:00 a.m. and 1:00 p.m., revealed the following:
Item 1 Not Completed. The building is a seven story, Type II (000) unprotected, non-combustible structure. This type of construction exceeds the maximum allowed for this story height.
Exit Interview with the Director of Facilities Management on November 13, 2023, at 1:00 p.m., confirmed the building construction type and height.
| | Plan of Correction - To be completed: 03/04/2024
1)Hire and consult a professional fire protection engineer. Extend time-limited waiver to July 5th, 2028, and complete continuous compliance items in updated FSES. a. Pottstown Hospital has retained Koffel Associates to prepare an updated FSES using the TIA which is anticipated to demonstrate equivalency once completed.
b. Put into place an updated time-limited waiver. Per TIA 13-2 for NFPA 101A (2013 edition), lower mandatory values are permitted to be used in FSES's for existing hospitals where the phase-in period for the requirement for sprinklers in 19.4.2 of NFPA 101 has not yet elapsed. The referenced TIA is provided as an Attachment forwarded in email to the Department of Health. It is requested that Pottstown Hospital be permitted to utilize TIA 13-2 until the plan for improvement is completed, but no later than July 5, 2028. Continuous compliance items currently noted will be remedied within 60 days. Compliance items noted in the FSES analysis conclusion will be maintained at all times.
2) Pottstown Hospital will submit the appropriate documentation for review to PA DOH LSI and all other AHJs regarding any necessary permitted and inspected work. All necessary work will be submitted to PA DOH LSI for compliance inspection/validation.
A full FSES plan detailing the plan of correction and considerations has been emailed to Charlie Schlegel and Gwendolyn Hilliard of PA DOH LSI.
The Chief Executive Officer is ultimately responsible for all corrective actions and ongoing compliance associated with this element of performance.
|
|