Electrical Systems - Essential Electric System Maintenance and Testing The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110. Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations. 6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70)
|
Observations: Name: BUILDING 01 (MAIN & MEDBRIDGE BLDG) - Component: 01 - Tag: 0918
Based on document review, observation, and interview, it was determined the facility failed to maintain and test the generator, affecting the entire facility.
Findings include:
1. Document review on August 19, 2026, at 9:30 a.m., revealed the facility could not produce documentation of the Annual Fuel Quality Test.
Exit Interview with the Administrator and Regional Maintenance Director on August 19, 2026, at 1:30 p.m., confirmed the above deficiency.
2. Observation on August 19, 2026, at 12:45 p.m., revealed there was no emergency generator remote manual stop station, outside of the generator enclosure.
Exit Interview with the Administrator and Regional Maintenance Director on August 19, 2026, at 1:30 p.m., confirmed the above deficiency.
| | Plan of Correction - To be completed: 10/18/2026
Step 1 The annual fuel test was completed on 3/5/2026. Annual fuel test report has been added to the life safety binder. Emergency Generator Shut off switch has been located in the facility. Proper signage has been added where the switch is located. Step 2 NHA/ designee will educate maintenance personnel to ensure that annual generator fuel tests are completed and documented in accordance with NFPA codes and standards. NHA/designee will educate staff on the location and use of the Emergency stop switch. Step 3 The Maintenance Director/ designee will audit generator records monthly x3 to ensure required documentation, inspections, and tests are completed as required. Audit findings will be reported to the QAPI committee to ensure compliance.
|
|