Pennsylvania Department of Health
YARDLEY REHABILITATION AND HEALTHCARE CENTER
Building Inspection Results

Note: If you need to change the font size, click the "View" menu at the top of the page, place the mouse over the "Text Size" menu item, and select the desired font size.

Severity Designations

Click here for definitions Click here for definitions Click here for definitions Click here for definitions
Minimal Citation - No Harm Minimal Harm Actual Harm Serious Harm
YARDLEY REHABILITATION AND HEALTHCARE CENTER
Inspection Results For:

There are  41 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
YARDLEY REHABILITATION AND HEALTHCARE CENTER - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000


Based on an Emergency Preparedness Survey completed on March 26, 2025, at Yardley Rehabilitation and Healthcare Center, it was determined there were no deficiencies identified with the requirements of 42 CFR 483.73





 Plan of Correction:


Initial comments:Name: MAIN BUILDING 01 - Component: 01 - Tag: 0000


Facility ID #125802
Component 01
Main Building

Based on a Revisit to a Medicare/Medicaid Recertification Survey completed on March 26, 2025, it was determined that Yardley Rehabilitation and Healthcare Center - Main Building was not in substantial compliance with the following requirements of the Life Safety Code for an existing Nursing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a one-story, Type V (111), protected wood frame building, that is fully sprinklered.








 Plan of Correction:


NFPA 101 STANDARD Subdivision of Building Spaces - Smoke Compar:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Subdivision of Building Spaces - Smoke Compartments
2012 EXISTING
Smoke barriers shall be provided to form at least two smoke compartments on every sleeping floor with a 30 or more patient bed capacity. Size of compartments cannot exceed 22,500 square feet or a 200-foot travel distance from any point in the compartment to a door in the smoke barrier.
19.3.7.1, 19.3.7.2
Detail in REMARKS zone dimensions including length of zones and dead-end corridors.
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0371

Based on observation, document review, and interview, it was determined the facility failed to provide smoke compartments not greater than 22,500 square feet, with a travel distance not to exceed 200 feet, affecting one of six smoke compartments within the component.

Findings include:

1.Observation and document review on March 26, 2025, at 10:00 a.m., revealed the total area for Smoke Compartment One was in excess of 22,500 square feet. Smoke Compartment One included the mechanical room, kitchen, main laundry room to the old Heritage dining room, the main entrance and the administration area to the main dining room.

Exit Interview with the Administrator and Maintenance Director on March 26, 2025, at 12:00 p.m., confirmed the smoke compartment exceeded the maximum square footage allowance.

****************************
Observations during an onsite Revisit conducted on May 7, 2025, between 11:00 a.m. and 1:00 p.m., determined the following:

Item 1 - Not Completed. The total area for Smoke Compartment One was in excess of 22,500 square feet. Smoke Compartment One included the mechanical room, kitchen, main laundry room to the old Heritage dining room, the main entrance and the administration area to the main dining room. FSES was not provided at time of Revisit as indicated on Facility Plan of Correction.

Interview at the exit conference with the Administrator and Maintenance Director on January 12, 2023, at 2:30 p.m., confirmed the above item was not completed.









 Plan of Correction - To be completed: 06/10/2025

The facility will perform an FSES inspection and complete the designated worksheets in conjunction with a licensed architect/engineer.
Initial comments:Name: WEST SIDE 24 BED ADDITION - Component: 02 - Tag: 0000


Facility ID# 125802
Component 02
West Side 24-bed Addition

Based on a Revisit to a Medicare/Medicaid Recertification Survey completed on March 26, 2025, it was determined that Yardley Rehabilitation and Healthcare Center was in substantial compliance with the requirements of the Life Safety Code for an existing Nursing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a one-story, Type V (111), protected wood frame building, that is fully sprinklered.







 Plan of Correction:


Initial comments:Name: EAST SIDE 4 BED ADDITION - Component: 03 - Tag: 0000


Facility ID# 125802
Component 03
East Side 4-bed Addition

Based on a Medicare/Medicaid Recertification Survey completed on March 26, 2025, at Yardley Rehabilitation and Healthcare Center, it was determined there were no deficiencies identified under the requirements of the Life Safety Code for an existing Nursing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a one-story, Type V (111), protected wood frame building, that is fully sprinklered.







 Plan of Correction: