Egress Doors Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements: CLINICAL NEEDS OR SECURITY THREAT LOCKING Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times. 18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6 SPECIAL NEEDS LOCKING ARRANGEMENTS Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation. 18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4 DELAYED-EGRESS LOCKING ARRANGEMENTS Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system. 18.2.2.2.4, 19.2.2.2.4 ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted. 18.2.2.2.4, 19.2.2.2.4 ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system. 18.2.2.2.4, 19.2.2.2.4
|
Observations: Name: BUILDING 04 (ARCADIA) - Component: 04 - Tag: 0222
Based on observation and interview, it was determined the facility failed to ensure egress doors with delayed-egress locking systems had required signage displayed on the doors, affecting one of two levels.
Findings include:
1. Observation on April 27, 2026, at 9:25 a.m., revealed a delayed-egress door lacked the required signage that states, "PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 SECONDS", on the first floor, the Service Hall emergency exit that leads to parking lot.
Exit interview with the Assistant Administrator and the Maintenance Director on April 27, 2026, at 11:00 a.m., confirmed the missing signage.
| | Plan of Correction - To be completed: 06/19/2026
Missing delayed-egress signage was immediately installed on the identified exit door.
All delayed-egress doors throughout the facility were checked for proper signage.
Maintenance staff were educated on required egress door signage requirements.
The Maintenance Director/designee will audit egress doors monthly for 3 months and report findings to QAPI.
|
|