Egress Doors Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements: CLINICAL NEEDS OR SECURITY THREAT LOCKING Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times. 18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6 SPECIAL NEEDS LOCKING ARRANGEMENTS Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation. 18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4 DELAYED-EGRESS LOCKING ARRANGEMENTS Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system. 18.2.2.2.4, 19.2.2.2.4 ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted. 18.2.2.2.4, 19.2.2.2.4 ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system. 18.2.2.2.4, 19.2.2.2.4
|
Observations: Name: MAIN BUILDING - Component: 01 - Tag: 0222
Based on observation and interview, it was determined the facility failed to maintain doors in the means of egress to be free from locking arrangements requiring a tool or key to operate from the egress side and to maintain special locking arrangement signage, affecting two of four smoke compartments within the component.
Findings include:
1. Observation on November 25, 2024, at 11:27 AM, revealed the emergency release knob of the door to the Main Walk-In Cooler, within the Kitchen, was missing, rendering the door able to be locked without a means of egress from within.
Interview with the Maintenance Director on November 25, 2024, at 11:27 AM, confirmed the Cooler could be locked against egress.
2. Observation on November 25, 2024, at 11:31 AM, revealed the exterior exit door, from the Activities Room, was equipped with a special locking arrangement, but lacked signage reading, "Push until alarm sounds. Door can be opened in 15 seconds."
Interview with the Maintenance Director on November 25, 2024, at 11:31 AM, confirmed the lack of special locking arrangement signage.
3. Observation on November 25, 2024, at 12:01 PM, revealed the Zone 3 double exterior exit doors were equipped with a special locking arrangement, but lacked signage reading, "Push until alarm sounds. Door can be opened in 15 seconds."
Interview with the Maintenance Director on November 25, 2024, at 12:01 PM, confirmed the lack of special locking arrangement signage.
| | Plan of Correction - To be completed: 01/07/2025
1) The emergency release knob of the door to the Main Walk-In cooler, within the kitchen, was replaced now allowing the door to be unlocked having a means of egress from within. New signage with the correct wording "push until alarm sounds" "door can be opened in 15 seconds". 2.3) The exterior exit door, from the Activities Room and the Zone 3 double exterior doors has the correct special locking arrangement signage posted. Egress doors in four smoke compartments were checked and have the correct special locking arrangement signage in place. Maintenance Director or designee will complete quarterly audits for correct egress door signage in place and report findings at quarterly QAPI meetings.
|
|