Initial comments:Name: - Component: -- - Tag: 0000


Based on an Emergency Preparedness Survey completed on July 27, 2026, it was determined that Abington Manor was not in compliance with the requirements of 42 CFR 483.73.








 Plan of Correction:


403.748, 416.54, 418.113, 441.184, 482.15, 483.475, 483.73, 484.102, 485.542, 485.625, 485.68, 485.727, 485.920, 486.360, 491.12 CONDITION Establishment of the Emergency Program (EP):This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
§403.748, §416.54, §418.113, §441.184, §460.84, §482.15, §483.73, §483.475, §484.102, §485.68, §485.542, §485.625, §485.727, §485.920, §486.360, §491.12

The [facility, except for Transplant Programs] must comply with all applicable Federal, State and local emergency preparedness requirements. The [facility, except for Transplant Programs] must establish and maintain a [comprehensive] emergency preparedness program that meets the requirements of this section.* The emergency preparedness program must include, but not be limited to, the following elements:

* (Unless otherwise indicated, the general use of the terms "facility" or "facilities" in this Appendix refers to all provider and suppliers addressed in this appendix. This is a generic moniker used in lieu of the specific provider or supplier noted in the regulations. For varying requirements, the specific regulation for that provider/supplier will be noted as well.)

*[For hospitals at §482.15:] The hospital must comply with all applicable Federal, State, and local emergency preparedness requirements. The hospital must develop and maintain a comprehensive emergency preparedness program that meets the requirements of this section, utilizing an all-hazards approach. The emergency preparedness program must include, but not be limited to, the following elements:

*[For CAHs at §485.625:] The CAH must comply with all applicable Federal, State, and local emergency preparedness requirements. The CAH must develop and maintain a comprehensive emergency preparedness program, utilizing an all-hazards approach. The emergency preparedness program must include, but not be limited to, the following elements:
Observations:
Name: - Component: -- - Tag: 0001

Based on documentation review and interview, it was determined the facility failed to provide an all-hazards approach to both Facility Risk Assessment and Emerging Infectious Diseases, affecting three of three floors.

Findings include:

1. Observation on July 27, 2026, at 11:40 a.m., revealed the facility failed to provide an all-hazards approach to facility risk assessment, as well as emerging infectious diseases.

Exit interview on July 27, 2026, between 11:45 a.m., and 12:00 p.m., with the Facilities Manager and the Human Resources Manager, confirmed the above deficiencies.






 Plan of Correction - To be completed: 09/22/2026

1. Facility completed Facility Risk Assessment and included Emerging Infectious Diseases.
2. Facility made master copies of completed ER Preparedness Binder to ensure it is kept in secure locations. NHA educated Maintenance Director on requirements of ER Preparedness Policies and Procedures.
3. ER Preparedness Policies and Procedures will be reviewed at QAPI quarterly to ensure it is accurate to facility needs and regulations.

403.748(b)(8), 416.54(b)(6), 418.113(b)(6)(C)(iv), 441.184(b)(8), 482.15(b)(8), 483.475(b)(8), 483.73(b)(8), 485.542(b)(7), 485.625(b)(8), 485.920(b)(7), 494.62(b)(7) STANDARD Roles Under a Waiver Declared by Secretary:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§403.748(b)(8), §416.54(b)(6), §418.113(b)(6)(C)(iv), §441.184(b)(8), §460.84(b)(9), §482.15(b)(8), §483.73(b)(8), §483.475(b)(8), §485.542(b)(7), §485.625(b)(8), §485.920(b)(7), §494.62(b)(7).

[(b) Policies and procedures. The [facilities] must develop and implement emergency preparedness policies and procedures, based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, and the communication plan at paragraph (c) of this section. The policies and procedures must be reviewed and updated at least every 2 years [annually for LTC facilities]. At a minimum, the policies and procedures must address the following:]

(8) [(6), (6)(C)(iv), (7), or (9)] The role of the [facility] under a waiver declared by the Secretary, in accordance with section 1135 of the Act, in the provision of care and treatment at an alternate care site identified by emergency management officials.

*[For RNHCIs at §403.748(b):] Policies and procedures. (8) The role of the RNHCI under a waiver declared by the Secretary, in accordance with section 1135 of Act, in the provision of care at an alternative care site identified by emergency management officials.
Observations:
Name: - Component: -- - Tag: 0026

Based on documentation review and interview, it was determined the facility failed to provide the role of the facility under a waiver declared by the Secretary of the Department of Health, affecting three of three floors.

Findings include:

1. Observation on July 27, 2026, at 11:41 a.m., revealed the facility lacked 1135 waiver documentation.

Exit interview on July 27, 2026, between 11:45 a.m., and 12:00 p.m., with the Facilities Manager and the Human Resources Manager, confirmed the above deficiency.





 Plan of Correction - To be completed: 09/22/2026

1. Facility completed 1135 waiver documentation.
2. Facility made master copies of completed ER Preparedness Binder to ensure it is kept in secure locations. NHA educated Maintenance Director on requirements of ER Preparedness Policies and Procedures.
3. ER Preparedness Policies and Procedures will be reviewed at QAPI quarterly to ensure it is accurate to facility needs and regulations.

403.748(d), 416.54(d), 418.113(d), 441.184(d), 482.15(d), 483.475(d), 483.73(d), 484.102(d), 485.542(d), 485.625(d), 485.68(d), 485.727(d), 485.920(d), 486.360(d), 491.12(d), 494.62(d) STANDARD EP Training and Testing:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
§403.748(d), §416.54(d), §418.113(d), §441.184(d), §460.84(d), §482.15(d), §483.73(d), §483.475(d), §484.102(d), §485.68(d), §485.542(d), §485.625(d), §485.727(d), §485.920(d), §486.360(d), §491.12(d), §494.62(d).

*[For RNCHIs at §403.748, ASCs at §416.54, Hospice at §418.113, PRTFs at §441.184, PACE at §460.84, Hospitals at §482.15, HHAs at §484.102, CORFs at §485.68, REHs at §485.542, CAHs at §486.625, "Organizations" under 485.727, CMHCs at §485.920, OPOs at §486.360, and RHC/FHQs at §491.12:] (d) Training and testing. The [facility] must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least every 2 years.

*[For LTC facilities at §483.73(d):] (d) Training and testing. The LTC facility must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least annually.

*[For ICF/IIDs at §483.475(d):] Training and testing. The ICF/IID must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least every 2 years. The ICF/IID must meet the requirements for evacuation drills and training at §483.470(i).

*[For ESRD Facilities at §494.62(d):] Training, testing, and orientation. The dialysis facility must develop and maintain an emergency preparedness training, testing and patient orientation program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training, testing and orientation program must be evaluated and updated at every 2 years.
Observations:
Name: - Component: -- - Tag: 0036

Based on documentation review and interview, it was determined the facility failed to maintain staff Emergency Management training, affecting three of three floors.

Findings include:

1. Observation on July 27, 2026, at 11:43 a.m., revealed the facility lacked documentation to support required annual emergency management training of all staff members.

Exit interview on July 27, 2026, between 11:45 a.m., and 12:00 p.m., with the Facilities Manager and the Human Resources Manager, confirmed the above deficiency.





 Plan of Correction - To be completed: 09/22/2026

1. Facility educated facility staff on ER Preparedness Policies and Procedures.
2. Facility added ER Preparedness Training to the monthly annual staff training schedule.
3. NHA educated Maintenance Director on completing this training on scheduled month.
4. NHA/designee will audit yearly to ensure this training was completed.
5. Audits will be submitted to QAPI for review.

403.748(d)(2), 416.54(d)(2), 418.113(d)(2), 441.184(d)(2), 482.15(d)(2), 483.475(d)(2), 483.73(d)(2), 484.102(d)(2), 485.542(d)(2), 485.625(d)(2), 485.68(d)(2), 485.727(d)(2), 485.920(d)(2), 486.360(d)(2), 491.12(d)(2), 494.62(d)(2) STANDARD EP Testing Requirements:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
§416.54(d)(2), §418.113(d)(2), §441.184(d)(2), §460.84(d)(2), §482.15(d)(2), §483.73(d)(2), §483.475(d)(2), §484.102(d)(2), §485.68(d)(2), §485.542(d)(2), §485.625(d)(2), §485.727(d)(2), §485.920(d)(2), §491.12(d)(2), §494.62(d)(2).

*[For ASCs at §416.54, CORFs at §485.68, REHs at §485.542, OPO, "Organizations" under §485.727, CMHCs at §485.920, RHCs/FQHCs at §491.12, and ESRD Facilities at §494.62]:

(2) Testing. The [facility] must conduct exercises to test the emergency plan annually. The [facility] must do all of the following:

(i) Participate in a full-scale exercise that is community-based every 2 years; or
(A) When a community-based exercise is not accessible, conduct a facility-based functional exercise every 2 years; or
(B) If the [facility] experiences an actual natural or man-made emergency that requires activation of the emergency plan, the [facility] is exempt from engaging in its next required community-based or individual, facility-based functional exercise following the onset of the actual event.
(ii) Conduct an additional exercise at least every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [facility's] response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the [facility's] emergency plan, as needed.

*[For Hospices at 418.113(d):]
(2) Testing for hospices that provide care in the patient's home. The hospice must conduct exercises to test the emergency plan at least annually. The hospice must do the following:
(i) Participate in a full-scale exercise that is community based every 2 years; or
(A) When a community based exercise is not accessible, conduct an individual facility based functional exercise every 2 years; or
(B) If the hospice experiences a natural or man-made emergency that requires activation of the emergency plan, the hospital is exempt from engaging in its next required full scale community-based exercise or individual facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.

(3) Testing for hospices that provide inpatient care directly. The hospice must conduct exercises to test the emergency plan twice per year. The hospice must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual facility-based functional exercise; or
(B) If the hospice experiences a natural or man-made emergency that requires activation of the emergency plan, the hospice is exempt from engaging in its next required full-scale community based or facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop led by a facilitator that includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the hospice's response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the hospice's emergency plan, as needed.


*[For PRFTs at §441.184(d), Hospitals at §482.15(d), CAHs at §485.625(d):]
(2) Testing. The [PRTF, Hospital, CAH] must conduct exercises to test the emergency plan twice per year. The [PRTF, Hospital, CAH] must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or
(B) If the [PRTF, Hospital, CAH] experiences an actual natural or man-made emergency that requires activation of the emergency plan, the [facility] is exempt from engaging in its next required full-scale community based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an [additional] annual exercise or and that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, a facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [facility's] response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the [facility's] emergency plan, as needed.

*[For PACE at §460.84(d):]
(2) Testing. The PACE organization must conduct exercises to test the emergency plan at least annually. The PACE organization must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or
(B) If the PACE experiences an actual natural or man-made emergency that requires activation of the emergency plan, the PACE is exempt from engaging in its next required full-scale community based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the PACE's response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the PACE's emergency plan, as needed.

*[For LTC Facilities at §483.73(d):]
(2) The [LTC facility] must conduct exercises to test the emergency plan at least twice per year, including unannounced staff drills using the emergency procedures. The [LTC facility, ICF/IID] must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise.
(B) If the [LTC facility] facility experiences an actual natural or man-made emergency that requires activation of the emergency plan, the LTC facility is exempt from engaging its next required a full-scale community-based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [LTC facility] facility's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the [LTC facility] facility's emergency plan, as needed.

*[For ICF/IIDs at §483.475(d)]:
(2) Testing. The ICF/IID must conduct exercises to test the emergency plan at least twice per year. The ICF/IID must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or.
(B) If the ICF/IID experiences an actual natural or man-made emergency that requires activation of the emergency plan, the ICF/IID is exempt from engaging in its next required full-scale community-based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the ICF/IID's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the ICF/IID's emergency plan, as needed.

*[For HHAs at §484.102]
(d)(2) Testing. The HHA must conduct exercises to test the emergency plan at
least annually. The HHA must do the following:
(i) Participate in a full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise every 2 years; or.
(B) If the HHA experiences an actual natural or man-made emergency that requires activation of the emergency plan, the HHA is exempt from engaging in its next required full-scale community-based or individual, facility based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the HHA's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the HHA's emergency plan, as needed.

*[For OPOs at §486.360]
(d)(2) Testing. The OPO must conduct exercises to test the emergency plan. The OPO must do the following:
(i) Conduct a paper-based, tabletop exercise or workshop at least annually. A tabletop exercise is led by a facilitator and includes a group discussion, using a narrated, clinically relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan. If the OPO experiences an actual natural or man-made emergency that requires activation of the emergency plan, the OPO is exempt from engaging in its next required testing exercise following the onset of the emergency event.
(ii) Analyze the OPO's response to and maintain documentation of all tabletop exercises, and emergency events, and revise the [RNHCI's and OPO's] emergency plan, as needed.

*[ RNCHIs at §403.748]:
(d)(2) Testing. The RNHCI must conduct exercises to test the emergency plan. The RNHCI must do the following:
(i) Conduct a paper-based, tabletop exercise at least annually. A tabletop exercise is a group discussion led by a facilitator, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(ii) Analyze the RNHCI's response to and maintain documentation of all tabletop exercises, and emergency events, and revise the RNHCI's emergency plan, as needed.
Observations:
Name: - Component: -- - Tag: 0039

Based on documentation review and interview, it was determined the facility failed to maintain the Emergency Management Plan with respect to full-scale exercise and Tabletop exercise, affecting three of three floors.

Findings include:

1. Observation on July 27, 2026, at 11:44 a.m., revealed the facility lacked data to support both the required, annual "full-scale exercise," and the "tabletop" portion of the Emergency Management Plan.

Exit interview on July 27, 2026, between 11:45 a.m., and 12:00 p.m., with the Facilities Manager and the Human Resources Manager, confirmed the above deficiency.





 Plan of Correction - To be completed: 09/22/2026


1. Facility completed full scale exercise and table top exercise on an event is HVA assessment.
2. Facility added these exercises to current ER drills schedule to ensure these 2 exercises happen annually.
3. NHA educated Maintenance Director on this new schedule and process to complete both.
4. NHA will audit drill schedule semi annually to ensure these exercises occurred.
5. Audits will be submitted QAPI for review.

Initial comments:Name: MAIN BUILDING - Component: 01 - Tag: 0000


Facility ID# 053202
Component 01
Main Building

Based on a Medicare/Medicaid Recertification Survey completed on July 27, 2026, it was determined that Abington Manor was not in compliance with the following requirements of the Life Safety Code for an existing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a three story, Type II (222), fire resistive building, that is fully sprinklered.






 Plan of Correction:


NFPA 101 STANDARD Cooking Facilities:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Cooking Facilities
Cooking equipment is protected in accordance with NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, unless:
* residential cooking equipment (i.e., small appliances such as microwaves, hot plates, toasters) are used for food warming or limited cooking in accordance with 18.3.2.5.2, 19.3.2.5.2
* cooking facilities open to the corridor in smoke compartments with 30 or fewer patients comply with the conditions under 18.3.2.5.3, 19.3.2.5.3, or
* cooking facilities in smoke compartments with 30 or fewer patients comply with conditions under 18.3.2.5.4, 19.3.2.5.4.
Cooking facilities protected according to NFPA 96 per 9.2.3 are not required to be enclosed as hazardous areas, but shall not be open to the corridor.
18.3.2.5.1 through 18.3.2.5.4, 19.3.2.5.1 through 19.3.2.5.5, 9.2.3, TIA 12-2




Observations:
Name: MAIN BUILDING - Component: 01 - Tag: 0324

Based on documentation review and interview, it was determined the facility failed to maintain cooking facilities in one instance, affecting one of three floors.

Findings include:

1. Observation on July 27, 2026, at 11:37 a.m., revealed the facility lacked one of two required kitchen exhaust hood/duct cleaning documents for the previous twelve month period (facility provided documentation dated 4/23/2026).

Exit interview on July 27, 2026, between 11:45 a.m., and 12:00 p.m., with the Facilities Manager and the Human Resources Manager, confirmed the cooking facilities documentation.






 Plan of Correction - To be completed: 09/22/2026

1. Facility cannot retroactively correct missing hood cleaning from 12 month period.
2. Facility contacted hood cleaning vendor to ensure scheduled maintenance in place. Next service is due October 2026.
3. Facility implemented monthly NHA check-in meeting with Maintenance Director to ensure tracking form being utilized and upcoming maintenance service is scheduled. NHA educated Maintenance Director on this new process.
4. Monthly schedule will be kept in binder by NHA.
5. Audits will be submitted to QAPI for review.

NFPA 101 STANDARD Fire Alarm System - Testing and Maintenance:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Fire Alarm System - Testing and Maintenance
A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available.
9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72
Observations:
Name: MAIN BUILDING - Component: 01 - Tag: 0345

Based on documentation review and interview, it was determined the facility failed to maintain the building fire alarm system in one instance, affecting three of three floors.

Findings include:

1. Observation on July 27, 2026, at 11:36 a.m., revealed the facility lacked semi-annual, visual testing data for the building fire alarm system.

Exit interview on July 27, 2026, between 11:45 a.m., and 12:00 p.m., with the Facilities Manager and the Human Resources Manager, confirmed the fire alarm system deficiency.



 Plan of Correction - To be completed: 09/22/2026

1. Facility cannot retroactively correct past semi annual visual testing data.
2. Facility contacted vendor to ensure scheduled routine testing is in place.
3. Facility implemented monthly NHA check-in meeting with Maintenance Director to ensure tracking form being utilized and upcoming maintenance service is scheduled. NHA educated Maintenance Director on this new process.
4. Monthly schedule will be kept in binder by NHA.
5. Audits will be submitted to QAPI for review.

NFPA 101 STANDARD Corridor - Doors:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Corridor - Doors
Doors protecting corridor openings in other than required enclosures of vertical openings, exits, or hazardous areas resist the passage of smoke and are made of 1 3/4 inch solid-bonded core wood or other material capable of resisting fire for at least 20 minutes. Doors in fully sprinklered smoke compartments are only required to resist the passage of smoke. Corridor doors and doors to rooms containing flammable or combustible materials have positive latching hardware. Roller latches are prohibited by CMS regulation. These requirements do not apply to auxiliary spaces that do not contain flammable or combustible material.
Clearance between bottom of door and floor covering is not exceeding 1 inch. Powered doors complying with 7.2.1.9 are permissible if provided with a device capable of keeping the door closed when a force of 5 lbf is applied. There is no impediment to the closing of the doors. Hold open devices that release when the door is pushed or pulled are permitted. Nonrated protective plates of unlimited height are permitted. Dutch doors meeting 19.3.6.3.6 are permitted. Door frames shall be labeled and made of steel or other materials in compliance with 8.3, unless the smoke compartment is sprinklered. Fixed fire window assemblies are allowed per 8.3. In sprinklered compartments there are no restrictions in area or fire resistance of glass or frames in window assemblies.

19.3.6.3, 42 CFR Parts 403, 418, 460, 482, 483, and 485
Show in REMARKS details of doors such as fire protection ratings, automatics closing devices, etc.
Observations:
Name: MAIN BUILDING - Component: 01 - Tag: 0363

Based on observation and interview, it was determined the facility failed to maintain corridor openings in four locations, affecting two of three floors.

Findings include:

1. Observation on July 27, 2026, between 10:40 a.m., and 11:31 a.m., revealed the following:

a. 10:40 a.m., the first floor, Dining Room doors required adjustment to properly coordinate, and fully close.
b. 10:42 a.m., a penetration of the first floor, Director of Laundry, office door.
c. 10:47 a.m., the first floor, Therapy door was held open by unapproved means (door chock).
d. 11:31 a.m., the second floor, Resident Room 2023 door was not smoke-tight.

Exit interview on July 27, 2026, between 11:45 a.m., and 12:00 p.m., with the Facilities Manager and the Human Resources Manager, confirmed the corridor opening deficiencies.





 Plan of Correction - To be completed: 09/22/2026

1. Facility repaired first floor dining room doors on 8/7/26, repaired the penetration on first floor laundry office door, therapy doors and second floor resident room door repaired.
2. Facility completed baseline audit on dining room doors, floors penetrations, non resident room and resident room smoke doors to ensure they are repaired.
3. Facility implemented new system that smoke doors, dining room doors, and penetrations are added to tels by area and monthly checks and repaired as needed. NHA educated Maintenance Director on this new process.
4. NHA will audit TELS monthly to ensure tasks are being completed.
5. Audits will be submitted to QAPI.

NFPA 101 STANDARD Rubbish Chutes, Incinerators, and Laundry Chu:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Rubbish Chutes, Incinerators, and Laundry Chutes
2012 EXISTING
(1) Any existing linen and trash chute, including pneumatic rubbish and linen systems, that opens directly onto any corridor shall be sealed by fire resistive construction to prevent further use or shall be provided with a fire door assembly having a fire protection rating of 1-hour. All new chutes shall comply with 9.5.
(2) Any rubbish chute or linen chute, including pneumatic rubbish and linen systems, shall be provided with automatic extinguishing protection in accordance with 9.7.
(3) Any trash chute shall discharge into a trash collection room used for no other purpose and protected in accordance with 8.4. (Existing laundry chutes permitted to discharge into same room are protected by automatic sprinklers in accordance with 19.3.5.9 or 19.3.5.7.)
(4) Existing fuel-fed incinerators shall be sealed by fire resistive construction to prevent further use.
19.5.4, 9.5, 8.4, NFPA 82
Observations:
Name: MAIN BUILDING - Component: 01 - Tag: 0541

Based on observation and interview, it was determined the facility failed to maintain one soiled linen chute, affecting one of three floors.

Findings include:

1. Observation on July 27, 2026, 10:47 a.m., the first floor, Soiled Linen Chute Termination Room, internal door, was held open by unapproved means (door chock).

Exit interview on July 27, 2026, between 11:45 a.m., and 12:00 p.m., with the Facilities Manager and the Human Resources Manager, confirmed the above deficiency.




 Plan of Correction - To be completed: 09/22/2026

1. The first floor soiled linen chute termination room was immediately closed and unapproved means was disposed of.
2. Facility completed baseline audit of facility doors to ensure none were held open with unapproved means.
3. Facility staff was educated that doors cannot be held open with unapproved means.
4. Maintenance Director/designee will audit random doors in facility weekly for weeks and then monthly for 2 months to ensure they are not held open with unapproved means.
5. Audits will be submitted to QAPI for review.

NFPA 101 STANDARD Fire Drills:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
19.7.1.4 through 19.7.1.7
Observations:
Name: MAIN BUILDING - Component: 01 - Tag: 0712

Based on documentation review and interview, it was determined the facility failed to conduct and maintain fire drills properly in ten of twelve instances.

Findings include:

1. Observation on July 27, 2026, at 11:35 a.m., revealed ten of twelve required fire drills were conducted during the last four days of each of the affected months within the previous twelve month period.

Exit interview on July 27, 2026, between 11:45 a.m., and 12:00 p.m., with the Facilities Manager and the Human Resources Manager, confirmed the fire drill deficiencies.





 Plan of Correction - To be completed: 09/22/2026

1. Facility cannot retroactively correct past fire drill days/times.
2. Facility scheduled next due fire drill this month on different day/time than prior.
3. Facility implemented new schedule that conducts monthly fire drills on different days/times.
4. NHA/designee will audit monthly days/times of fire drills to ensure they happen randomly for the next 3 months.
5. Audits will be submitted to QAPI for review.

NFPA 101 STANDARD Smoking Regulations:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Smoking Regulations
Smoking regulations shall be adopted and shall include not less than the following provisions:
(1) Smoking shall be prohibited in any room, ward, or compartment where flammable liquids, combustible gases, or oxygen is used or stored and in any other hazardous location, and such area shall be posted with signs that read NO SMOKING or shall be posted with the international symbol for no smoking.
(2) In health care occupancies where smoking is prohibited and signs are prominently placed at all major entrances, secondary signs with language that prohibits smoking shall not be required.
(3) Smoking by patients classified as not responsible shall be prohibited.
(4) The requirement of 18.7.4(3) shall not apply where the patient is under direct supervision.
(5) Ashtrays of noncombustible material and safe design shall be provided in all areas where smoking is permitted.
(6) Metal containers with self-closing cover devices into which ashtrays can be emptied shall be readily available to all areas where smoking is permitted.
18.7.4, 19.7.4

Observations:
Name: MAIN BUILDING - Component: 01 - Tag: 0741

Based on observation and interview, it was determined the facility failed to maintain smoking regulations in one location, affecting one of three floors.

Findings include:

1. Observation on July 27, 2026, at 11:07 a.m., revealed unauthorized smoking at the first floor exit discharge location, closest to the Maintenance Shop. In addition, a cinder block was being used as an ashtray in this location.

Exit interview on July 27, 2026, between 11:45 a.m., and 12:00 p.m., with the Facilities Manager and the Human Resources Manager, confirmed the smoking regulations deficiency.






 Plan of Correction - To be completed: 09/22/2026

1. Facility immediately removed unauthorized smoking container from unauthorized area.
2. Facility completed baseline audit to ensure no other unauthorized smoking containers and areas were being utilized.
3. Facility staff was educated on designated staff smoking areas and approved containers for smoking.
4. Maintenance Director/Designee will audit facility ground random locations weekly for 4 weeks and monthly for 2 months to ensure no unauthorized areas and containers are being used for staff smoking.
5. Audits will be submitted to QAPI for review.

NFPA 101 STANDARD Electrical Systems - Essential Electric Syste:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70)
Observations:
Name: MAIN BUILDING - Component: 01 - Tag: 0918

Based on observation and interview, it was determined the facility failed to maintain the alternate power source supplying the emergency electrical power.

Findings include:

1. Observation on July 27, 2026, at 10:35 a.m., revealed the facility utilizing a temporary electrical generator on wheels that is wired into the transfer switch with temporary wiring/cabling. Temporary cables and wiring are located on the floor in the transfer switch room, and the transfer switch cover is open due to the temporary wiring setup. The temporary wiring/cabling is also located in the grass, adjacent to the public sidewalk/parking lot. This temporary generator set up has been temporary since at least 2019.

2. Observation on July 27, 2026, at 10:37 a.m., revealed the facility's emergency generator lacked a remote emergency stop station, located externally from the generator.

3. Observation of the fuel quality sample report, dated September 30, 2025, revealed the fuel sample failed the "particulates" portion of the test.

Exit interview on July 27, 2026, between 11:45 a.m., and 12:00 p.m., with the Facilities Manager and the Human Resources Manager, confirmed the emergency generator is a mobile unit that is temporarily installed and that the facility lacked a remote emergency stop station, and the fuel quality sample failed the particulates portion of the test.






 Plan of Correction - To be completed: 09/22/2026

1.Facility has temporary generator in place to supply emergency electrical power to facility. The temporary wiring and cables will be resolved once permanent generator in place. The emergency stop station location will be resolved once permanent generator in place.
2. Facility generator installation date is tentatively beginning of October and is based on arrival date from company who is building generator. The construction plans are starting Month of August.
3. Facility contacted vendor regarding failed fuel sample to verify re-test completed. Fuel will be re-tested and repairs made if applicable.
4. Facility will ensure preventive maintenance in place regarding fuel until permanent generator in place.