Pennsylvania Department of Health
SUBURBAN WOODS HEALTH & REHABILITATION CENTER
Building Inspection Results

Note: If you need to change the font size, click the "View" menu at the top of the page, place the mouse over the "Text Size" menu item, and select the desired font size.

Severity Designations

Click here for definitions Click here for definitions Click here for definitions Click here for definitions
Minimal Citation - No Harm Minimal Harm Actual Harm Serious Harm
SUBURBAN WOODS HEALTH & REHABILITATION CENTER
Inspection Results For:

There are  41 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
SUBURBAN WOODS HEALTH & REHABILITATION CENTER - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000


Based on a Revisit to an Emergency Preparedness Survey completed on June 25, 2024, it was determined that Suburban Woods Health & Rehabilitation Center had deficiencies which have the potential for minimal harm as related to the requirements of 42 CFR 483.73.








 Plan of Correction:


403.748(b)(8), 416.54(b)(6), 418.113(b)(6)(C)(iv), 441.184(b)(8), 482.15(b)(8), 483.475(b)(8), 483.73(b)(8), 485.542(b)(7), 485.625(b)(8), 485.920(b)(7), 494.62(b)(7) STANDARD Roles Under a Waiver Declared by Secretary:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§403.748(b)(8), §416.54(b)(6), §418.113(b)(6)(C)(iv), §441.184(b)(8), §460.84(b)(9), §482.15(b)(8), §483.73(b)(8), §483.475(b)(8), §485.542(b)(7), §485.625(b)(8), §485.920(b)(7), §494.62(b)(7).

[(b) Policies and procedures. The [facilities] must develop and implement emergency preparedness policies and procedures, based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, and the communication plan at paragraph (c) of this section. The policies and procedures must be reviewed and updated at least every 2 years [annually for LTC facilities]. At a minimum, the policies and procedures must address the following:]

(8) [(6), (6)(C)(iv), (7), or (9)] The role of the [facility] under a waiver declared by the Secretary, in accordance with section 1135 of the Act, in the provision of care and treatment at an alternate care site identified by emergency management officials.

*[For RNHCIs at §403.748(b):] Policies and procedures. (8) The role of the RNHCI under a waiver declared by the Secretary, in accordance with section 1135 of Act, in the provision of care at an alternative care site identified by emergency management officials.
Observations:
Name: - Component: -- - Tag: 0026

Based on document review and interview, it was determined the facility failed to provide policy and procedure documentation concerning the role of the LTC facility under a waiver declared by the Secretary, in accordance with section 1135 of the Act, in the provision of care and treatment at an alternate care site identified by emergency management officials, affecting the entire facility.

Findings include:

Document review on June 25, 2024, at 9:15 a.m., revealed the facility could not provide Emergency Preparedness Plan policy and procedure documentation concerning the Roles under a Waiver Declared by Secretary.

Exit interview with the Administrator and the Maintenance Director on June 25, 2024, at 12:45 p.m., confirmed the lack of documentation.


************************

Based on document review and interview during a onsite Revisit conducted on August 12, 2024, the following was determined:

Not Completed. The facility could not provide Emergency Preparedness Plan policy and procedure documentation concerning the Roles under a Waiver Declared by Secretary.

Exit interview with the Administrator and the Maintenance Director on August 12, 2024, at 11:30 a.m., confirmed the lack of documentation.






 Plan of Correction - To be completed: 09/13/2024

1. Emergency Plan policies and procedures updated to include the roles under a waiver declared by Secretary.
2.Maintenance Director educated on requirements of concerning the roles under a waiver declared by Secretary.

3.NHA/designee will be responsible for ensuring the Emergency Plan policies and procedures are updated timely.
403.748(d)(2), 416.54(d)(2), 418.113(d)(2), 441.184(d)(2), 482.15(d)(2), 483.475(d)(2), 483.73(d)(2), 484.102(d)(2), 485.542(d)(2), 485.625(d)(2), 485.68(d)(2), 485.727(d)(2), 485.920(d)(2), 486.360(d)(2), 491.12(d)(2), 494.62(d)(2) STANDARD EP Testing Requirements:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§416.54(d)(2), §418.113(d)(2), §441.184(d)(2), §460.84(d)(2), §482.15(d)(2), §483.73(d)(2), §483.475(d)(2), §484.102(d)(2), §485.68(d)(2), §485.542(d)(2), §485.625(d)(2), §485.727(d)(2), §485.920(d)(2), §491.12(d)(2), §494.62(d)(2).

*[For ASCs at §416.54, CORFs at §485.68, REHs at §485.542, OPO, "Organizations" under §485.727, CMHCs at §485.920, RHCs/FQHCs at §491.12, and ESRD Facilities at §494.62]:

(2) Testing. The [facility] must conduct exercises to test the emergency plan annually. The [facility] must do all of the following:

(i) Participate in a full-scale exercise that is community-based every 2 years; or
(A) When a community-based exercise is not accessible, conduct a facility-based functional exercise every 2 years; or
(B) If the [facility] experiences an actual natural or man-made emergency that requires activation of the emergency plan, the [facility] is exempt from engaging in its next required community-based or individual, facility-based functional exercise following the onset of the actual event.
(ii) Conduct an additional exercise at least every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [facility's] response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the [facility's] emergency plan, as needed.

*[For Hospices at 418.113(d):]
(2) Testing for hospices that provide care in the patient's home. The hospice must conduct exercises to test the emergency plan at least annually. The hospice must do the following:
(i) Participate in a full-scale exercise that is community based every 2 years; or
(A) When a community based exercise is not accessible, conduct an individual facility based functional exercise every 2 years; or
(B) If the hospice experiences a natural or man-made emergency that requires activation of the emergency plan, the hospital is exempt from engaging in its next required full scale community-based exercise or individual facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.

(3) Testing for hospices that provide inpatient care directly. The hospice must conduct exercises to test the emergency plan twice per year. The hospice must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual facility-based functional exercise; or
(B) If the hospice experiences a natural or man-made emergency that requires activation of the emergency plan, the hospice is exempt from engaging in its next required full-scale community based or facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop led by a facilitator that includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the hospice's response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the hospice's emergency plan, as needed.


*[For PRFTs at §441.184(d), Hospitals at §482.15(d), CAHs at §485.625(d):]
(2) Testing. The [PRTF, Hospital, CAH] must conduct exercises to test the emergency plan twice per year. The [PRTF, Hospital, CAH] must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or
(B) If the [PRTF, Hospital, CAH] experiences an actual natural or man-made emergency that requires activation of the emergency plan, the [facility] is exempt from engaging in its next required full-scale community based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an [additional] annual exercise or and that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, a facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [facility's] response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the [facility's] emergency plan, as needed.

*[For PACE at §460.84(d):]
(2) Testing. The PACE organization must conduct exercises to test the emergency plan at least annually. The PACE organization must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or
(B) If the PACE experiences an actual natural or man-made emergency that requires activation of the emergency plan, the PACE is exempt from engaging in its next required full-scale community based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the PACE's response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the PACE's emergency plan, as needed.

*[For LTC Facilities at §483.73(d):]
(2) The [LTC facility] must conduct exercises to test the emergency plan at least twice per year, including unannounced staff drills using the emergency procedures. The [LTC facility, ICF/IID] must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise.
(B) If the [LTC facility] facility experiences an actual natural or man-made emergency that requires activation of the emergency plan, the LTC facility is exempt from engaging its next required a full-scale community-based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [LTC facility] facility's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the [LTC facility] facility's emergency plan, as needed.

*[For ICF/IIDs at §483.475(d)]:
(2) Testing. The ICF/IID must conduct exercises to test the emergency plan at least twice per year. The ICF/IID must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or.
(B) If the ICF/IID experiences an actual natural or man-made emergency that requires activation of the emergency plan, the ICF/IID is exempt from engaging in its next required full-scale community-based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the ICF/IID's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the ICF/IID's emergency plan, as needed.

*[For HHAs at §484.102]
(d)(2) Testing. The HHA must conduct exercises to test the emergency plan at
least annually. The HHA must do the following:
(i) Participate in a full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise every 2 years; or.
(B) If the HHA experiences an actual natural or man-made emergency that requires activation of the emergency plan, the HHA is exempt from engaging in its next required full-scale community-based or individual, facility based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the HHA's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the HHA's emergency plan, as needed.

*[For OPOs at §486.360]
(d)(2) Testing. The OPO must conduct exercises to test the emergency plan. The OPO must do the following:
(i) Conduct a paper-based, tabletop exercise or workshop at least annually. A tabletop exercise is led by a facilitator and includes a group discussion, using a narrated, clinically relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan. If the OPO experiences an actual natural or man-made emergency that requires activation of the emergency plan, the OPO is exempt from engaging in its next required testing exercise following the onset of the emergency event.
(ii) Analyze the OPO's response to and maintain documentation of all tabletop exercises, and emergency events, and revise the [RNHCI's and OPO's] emergency plan, as needed.

*[ RNCHIs at §403.748]:
(d)(2) Testing. The RNHCI must conduct exercises to test the emergency plan. The RNHCI must do the following:
(i) Conduct a paper-based, tabletop exercise at least annually. A tabletop exercise is a group discussion led by a facilitator, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(ii) Analyze the RNHCI's response to and maintain documentation of all tabletop exercises, and emergency events, and revise the RNHCI's emergency plan, as needed.
Observations:
Name: - Component: -- - Tag: 0039

Based on document review and interview, it was determined the facility failed to conduct the required annual-full scale exercise and additional exercise to test the emergency preparedness plan, affecting the entire facility.

Findings include:

Document review on June 25, 2024, at 9:15 a.m., revealed the facility failed to conduct the required annual-full scale exercise and additional exercise to test the emergency preparedness plan within the previous 12 months.

Exit interview with the Administrator and the Maintenance Director on June 25, 2024, at 12:45 p.m., confirmed the lack of documentation.

******************

Based on document review and interview during an onsite Revisit conducted on August 12, 2024, the following was determined:

Not Completed. The facility failed to conduct the required annual-full scale exercise and additional exercise to test the emergency preparedness plan within the previous 12 months.

Exit interview with the Administrator and the Maintenance Director on August 12, 2024, at 11:30 a.m., confirmed the lack of documentation.





 Plan of Correction - To be completed: 09/13/2024

1. Facility completed the required annual-full scale exercise.
2. Maintenance Director educated on the importance of completing annual-full scale exercise.

3. NHA/designee will be responsible for ensuring annual-full scale exercise is completed yearly.
Initial comments:Name: MAIN BUILDING 01 - Component: 01 - Tag: 0000


Facility ID# 044002
Component 01
Main Building

Based on a Revisit to a Medicare/Medicaid Recertification Survey completed on June 25, 2024, it was determined that Suburban Woods Health & Rehabilitation Center was not in compliance with the following requirements of the Life Safety Code for an existing Nursing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a three story, Type II (111), protected non-combustible building, that is fully sprinklered.

Failure to correct the following deficiencies may negate the acceptance of certain earlier deficiencies by the approved FSES.







 Plan of Correction:


NFPA 101 STANDARD Egress Doors:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Egress Doors
Doors in a required means of egress shall not be equipped with a latch or a lock that requires the use of a tool or key from the egress side unless using one of the following special locking arrangements:
CLINICAL NEEDS OR SECURITY THREAT LOCKING
Where special locking arrangements for the clinical security needs of the patient are used, only one locking device shall be permitted on each door and provisions shall be made for the rapid removal of occupants by: remote control of locks; keying of all locks or keys carried by staff at all times; or other such reliable means available to the staff at all times.
18.2.2.2.5.1, 18.2.2.2.6, 19.2.2.2.5.1, 19.2.2.2.6
SPECIAL NEEDS LOCKING ARRANGEMENTS
Where special locking arrangements for the safety needs of the patient are used, all of the Clinical or Security Locking requirements are being met. In addition, the locks must be electrical locks that fail safely so as to release upon loss of power to the device; the building is protected by a supervised automatic sprinkler system and the locked space is protected by a complete smoke detection system (or is constantly monitored at an attended location within the locked space); and both the sprinkler and detection systems are arranged to unlock the doors upon activation.
18.2.2.2.5.2, 19.2.2.2.5.2, TIA 12-4
DELAYED-EGRESS LOCKING ARRANGEMENTS
Approved, listed delayed-egress locking systems installed in accordance with 7.2.1.6.1 shall be permitted on door assemblies serving low and ordinary hazard contents in buildings protected throughout by an approved, supervised automatic fire detection system or an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
ACCESS-CONTROLLED EGRESS LOCKING ARRANGEMENTS
Access-Controlled Egress Door assemblies installed in accordance with 7.2.1.6.2 shall be permitted.
18.2.2.2.4, 19.2.2.2.4
ELEVATOR LOBBY EXIT ACCESS LOCKING ARRANGEMENTS
Elevator lobby exit access door locking in accordance with 7.2.1.6.3 shall be permitted on door assemblies in buildings protected throughout by an approved, supervised automatic fire detection system and an approved, supervised automatic sprinkler system.
18.2.2.2.4, 19.2.2.2.4
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0222

Based on observation and interview, it was determined the facility failed to maintain delayed locking egress doors, affecting two of three levels in the facility.

Findings include:

Observations on June 25, 2024, between 11:44 a.m. and 12:24 a.m., revealed delayed egress locking doors failed to open in the following locations:

a. 11:44 a.m., Basement, exit door by Physical Therapy;
b. 12:24 a.m., on the second floor, exit door by resident room 226.

Exit interview with the Administrator and the Maintenance Director on June 25, 2024, at 12:45 p.m., confirmed the doors failed to open.

***********************

Based on observation and interview during an onsite Revisit conducted on August 12, 2024, the following was determined:

Not Completed. Delayed egress locking doors failed to open in the following location:

a. 11:44 a.m., Basement, exit door by Physical Therapy. At the time of the Revisit the doors had damaged and missing hardware.

Exit interview with the Administrator and the Maintenance Director on August 12, 2024, at 11:30 a.m., confirmed the door deficiencies.

All other deficiencies listed under this tag were corrected.






 Plan of Correction - To be completed: 09/13/2024

1.The delayed egress locking doors in the basement were repaired and now opens

2.Maintenance Director was educated on the requirements of ensuring delayed egress locking doors should release after 15 seconds

3.NHA/designee will audit two random delayed egress locking doors weekly x4
NFPA 101 STANDARD Subdivision of Building Spaces - Smoke Compar:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Subdivision of Building Spaces - Smoke Compartments
2012 EXISTING
Smoke barriers shall be provided to form at least two smoke compartments on every sleeping floor with a 30 or more patient bed capacity. Size of compartments cannot exceed 22,500 square feet or a 200-foot travel distance from any point in the compartment to a door in the smoke barrier.
19.3.7.1, 19.3.7.2
Detail in REMARKS zone dimensions including length of zones and dead-end corridors.
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0371

Based on observation and interview, it was determined the facility failed to maintain the fire resistance of smoke barriers, affecting two of three levels in the facility.

Findings include:

Observations on June 25, 2024, between 11:54 a.m. and 12:20 p.m., revealed the following deficiencies:

a. 11:54 a.m., in the Basement, smoke barrier by Kitchen was not constructed to the underside of the deck above;
b. 12:20 p.m., on the second floor, smoke barrier doors by resident room 225 had an excessive gap between the doors.

Exit interview with the Administrator and the Maintenance Director on June 25, 2024, at 12:45 p.m., confirmed the above deficiencies.

**************************

Based on observation and interview during an onsite Revisit conducted on August 12, 2024, the following was determined:

Not Completed. The following deficiencies remained:

a. smoke barrier by the Kitchen was not constructed to the underside of the deck above;

b. smoke barrier doors by resident room 225 had an excessive gap between the doors.

Exit interview with the Administrator and the Maintenance Director on August 12, 2024, at 11:30 a.m., confirmed the above deficiencies.





 Plan of Correction - To be completed: 09/13/2024

1.The basement smoke barrier by kitchen and smoke barrier doors by resident room 225 are corrected.

2.Maintenance Director was educated on the importance of maintain the fire resistance of smoke barriers.

3.NHA/designee will audit smoke barrier doors weekly x4
NFPA 101 STANDARD Electrical Systems - Essential Electric Syste:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70)
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0918

Based on document review and interview, it was determined the facility failed to maintain and inspect the emergency generator, affecting the entire facility.

Findings include:

Document review on June 25, 2024, at 9:15 a.m., revealed the facility could not provide documentation of the following tests and inspections:

a. Weekly inspection of battery voltage;
b. Monthly testing of battery conductance;
c. Preventative Maintenance indicating no evidence of wet stacking;
d. 3 year, 4 hour load test;
e. Annual fuel quality test.

Exit interview with the Administrator and the Maintenance Director on June 25, 2024, at 12:45 p.m., confirmed the lack of documentation.


**************************

Based on document review and interview during an onsite Revisit conducted on August 12, 2024, the following was determined:

Not Completed. The facility could not provide documentation of the following tests and inspections:

c. Preventative Maintenance indicating no evidence of wet stacking;
d.. 3 year, 4 hour load test;
e. Annual fuel quality test.

Exit interview with the Administrator and the Maintenance Director on August 12, 2024, at 11:30 a.m., confirmed the lack of documentation.

All other deficiencies listed under this tag were corrected.





 Plan of Correction - To be completed: 09/13/2024

1.Preventative Maintenance indicating no evidence of wet stacking completed; 3 year, 4 hour load test completed and annual fuel quality test completed
2.Maintenance Director educated on requirements of Preventative Maintenance document indicating no evidence of wet stacking, 3 year, 4 hour load test and annual fuel quality test.

3.NHA/designee will be responsible for ensuring preventative maintenance document indicates no evidence of wet stacking, 3 year, 4 hour load test and annual fuel quality test are completed

Back to County Map


  
Home : Press Releases : Administration
Health Planning and Assessment : Office of the Secretary
Health Promotion and Disease Prevention : Quality Assurance



Copyright © 2001 Commonwealth of Pennsylvania. All Rights Reserved.
Commonwealth of PA Privacy Statement