Corridor - Doors Doors protecting corridor openings in other than required enclosures of vertical openings, exits, or hazardous areas resist the passage of smoke and are made of 1 3/4 inch solid-bonded core wood or other material capable of resisting fire for at least 20 minutes. Doors in fully sprinklered smoke compartments are only required to resist the passage of smoke. Corridor doors and doors to rooms containing flammable or combustible materials have positive latching hardware. Roller latches are prohibited by CMS regulation. These requirements do not apply to auxiliary spaces that do not contain flammable or combustible material. Clearance between bottom of door and floor covering is not exceeding 1 inch. Powered doors complying with 7.2.1.9 are permissible if provided with a device capable of keeping the door closed when a force of 5 lbf is applied. There is no impediment to the closing of the doors. Hold open devices that release when the door is pushed or pulled are permitted. Nonrated protective plates of unlimited height are permitted. Dutch doors meeting 19.3.6.3.6 are permitted. Door frames shall be labeled and made of steel or other materials in compliance with 8.3, unless the smoke compartment is sprinklered. Fixed fire window assemblies are allowed per 8.3. In sprinklered compartments there are no restrictions in area or fire resistance of glass or frames in window assemblies.
19.3.6.3, 42 CFR Parts 403, 418, 460, 482, 483, and 485 Show in REMARKS details of doors such as fire protection ratings, automatics closing devices, etc.
|
Observations: Name: MAIN BUILDING 01 - Component: 01 - Tag: 0363
Based on observation and interview, it was determined the facility failed to maintain corridor openings in two locations, affecting one of one floor.
Findings include:
1. Observation on Janaury 23, 2024, between 9:45 a.m., and 10:50 a.m., revealed the following doors were not smoke-tight:
a. 9:45 a.m., Resident Room 302. b.10:50 a.m., Nursing Services.
Exit interview with the Facility Administrator and the Facilities Manager, on January 23, 2024, between 11:20 a.m., and 11:30 a.m., confirmed the corridor opening deficiencies.
| | Plan of Correction - To be completed: 02/12/2024
Maintenance added fire and smoke rated brushings 20-minute smoke rating to room 302 and to nursing services door. Maintenance will do spot checks throughout the building on all doors ensuring they are smoke-tight. Maintenance Supervisor/designee will complete weekly audits for one month and then monthly thereafter. Maintenance Director will present audit at QAPI
|
|