Pennsylvania Department of Health
HAVENCREST HEALTHCARE AND REHABILITATION CENTER
Building Inspection Results

Note: If you need to change the font size, click the "View" menu at the top of the page, place the mouse over the "Text Size" menu item, and select the desired font size.

Severity Designations

Click here for definitions Click here for definitions Click here for definitions Click here for definitions
Minimal Citation - No Harm Minimal Harm Actual Harm Serious Harm
HAVENCREST HEALTHCARE AND REHABILITATION CENTER
Inspection Results For:

There are  30 surveys for this facility. Please select a date to view the survey results.

Surveys don't appear on this website until at least 41 days have elapsed since the exit date of the survey.
HAVENCREST HEALTHCARE AND REHABILITATION CENTER - Inspection Results Scope of Citation
Number of Residents Affected
By Deficient Practice
Initial comments:Name: - Component: -- - Tag: 0000


Based on an Emergency Preparedness Survey completed on January 22, 2024, it was determined that Havencrest Nursing Center was not in compliance with the requirements of 42 CFR 483.73.



 Plan of Correction:


403.748(c)(1), 416.54(c)(1), 418.113(c)(1), 441.184(c)(1), 482.15(c)(1), 483.475(c)(1), 483.73(c)(1), 484.102(c)(1), 485.542(c)(1), 485.625(c)(1), 485.68(c)(1), 485.727(c)(1), 485.920(c)(1), 486.360(c)(1), 491.12(c)(1), 494.62(c)(1) STANDARD Names and Contact Information:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§403.748(c)(1), §416.54(c)(1), §418.113(c)(1), §441.184(c)(1), §460.84(c)(1), §482.15(c)(1), §483.73(c)(1), §483.475(c)(1), §484.102(c)(1), §485.68(c)(1), §485.542(c)(1), §485.625(c)(1), §485.727(c)(1), §485.920(c)(1), §486.360(c)(1), §491.12(c)(1), §494.62(c)(1).

[(c) The [facility must develop and maintain an emergency preparedness communication plan that complies with Federal, State and local laws and must be reviewed and updated at least every 2 years [annually for LTC facilities]. The communication plan must include all of the following:]

(1) Names and contact information for the following:
(i) Staff.
(ii) Entities providing services under arrangement.
(iii) Patients' physicians
(iv) Other [facilities].
(v) Volunteers.

*[For Hospitals at §482.15(c) and CAHs at §485.625(c)] The communication plan must include all of the following:
(1) Names and contact information for the following:
(i) Staff.
(ii) Entities providing services under arrangement.
(iii) Patients' physicians
(iv) Other [hospitals and CAHs].
(v) Volunteers.

*[For RNHCIs at §403.748(c):] The communication plan must include all of the following:
(1) Names and contact information for the following:
(i) Staff.
(ii) Entities providing services under arrangement.
(iii) Next of kin, guardian, or custodian.
(iv) Other RNHCIs.
(v) Volunteers.

*[For ASCs at §416.45(c):] The communication plan must include all of the following:
(1) Names and contact information for the following:
(i) Staff.
(ii) Entities providing services under arrangement.
(iii) Patients' physicians.
(iv) Volunteers.

*[For Hospices at §418.113(c):] The communication plan must include all of the following:
(1) Names and contact information for the following:
(i) Hospice employees.
(ii) Entities providing services under arrangement.
(iii) Patients' physicians.
(iv) Other hospices.

*[For HHAs at §484.102(c):] The communication plan must include all of the following:
(1) Names and contact information for the following:
(i) Staff.
(ii) Entities providing services under arrangement.
(iii) Patients' physicians.
(iv) Volunteers.

*[For OPOs at §486.360(c):] The communication plan must include all of the following:
(2) Names and contact information for the following:
(i) Staff.
(ii) Entities providing services under arrangement.
(iii) Volunteers.
(iv) Other OPOs.
(v) Transplant and donor hospitals in the OPO's Donation Service Area (DSA).
Observations:
Name: - Component: -- - Tag: 0030


Based on document review, it was determined the facility failed to include names and contact information in its emergency preparedness plan.

Findings include:

1. Documentation reviewed on January 22, 2024, at 8:45 a.m., revealed the emergency preparedness plan did not include updated/accurate names and contact information for resident physicians.

Interview with the Facility Administrator on January 22, 2024, at 12:30 p.m., confirmed the facility failed to provide documention of the above deficiency at the time of inspection.





 Plan of Correction - To be completed: 02/20/2024

The Emergency Preparedness was reviewed and approved on August 18,2023. The facility updated all sections of the Emergency Preparedness Plan that included changes to the contact information for the Maintenance Director position on January 29,2024 and the supporting physician that provides resident care in addition to the Medical Director. The NHA will be educated by the RDO/Designee on the Emergency Preparedness Plan contact information requirements by February 20, 2024. The Emergency Prepared Plan will be updated with all changes at the time of occurrence. The Emergency Plan will be audited by the NHA weekly x4 weeks, followed by monthly x2 for accuracy. Results will be monitored in QA/QI x3 months.
403.748(d), 416.54(d), 418.113(d), 441.184(d), 482.15(d), 483.475(d), 483.73(d), 484.102(d), 485.542(d), 485.625(d), 485.68(d), 485.727(d), 485.920(d), 486.360(d), 491.12(d), 494.62(d) STANDARD EP Training and Testing:This is a less serious (but not lowest level) deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents.  This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status.
§403.748(d), §416.54(d), §418.113(d), §441.184(d), §460.84(d), §482.15(d), §483.73(d), §483.475(d), §484.102(d), §485.68(d), §485.542(d), §485.625(d), §485.727(d), §485.920(d), §486.360(d), §491.12(d), §494.62(d).

*[For RNCHIs at §403.748, ASCs at §416.54, Hospice at §418.113, PRTFs at §441.184, PACE at §460.84, Hospitals at §482.15, HHAs at §484.102, CORFs at §485.68, REHs at §485.542, CAHs at §486.625, "Organizations" under 485.727, CMHCs at §485.920, OPOs at §486.360, and RHC/FHQs at §491.12:] (d) Training and testing. The [facility] must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least every 2 years.

*[For LTC facilities at §483.73(d):] (d) Training and testing. The LTC facility must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least annually.

*[For ICF/IIDs at §483.475(d):] Training and testing. The ICF/IID must develop and maintain an emergency preparedness training and testing program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training and testing program must be reviewed and updated at least every 2 years. The ICF/IID must meet the requirements for evacuation drills and training at §483.470(i).

*[For ESRD Facilities at §494.62(d):] Training, testing, and orientation. The dialysis facility must develop and maintain an emergency preparedness training, testing and patient orientation program that is based on the emergency plan set forth in paragraph (a) of this section, risk assessment at paragraph (a)(1) of this section, policies and procedures at paragraph (b) of this section, and the communication plan at paragraph (c) of this section. The training, testing and orientation program must be evaluated and updated at every 2 years.
Observations:
Name: - Component: -- - Tag: 0036

Based on document review and interview, it was determined the facility failed to include a staff training and testing program in the emergency preparedness plan.

Findings include:

1. Documentation review on January 22, 2024, at 8:30 a.m., revealed a written training and testing program was not included in the emergency preparedness plan and inspector could not verify on site.

Interview with the Facility Administrator on January 22, 2024, at 12:30 p.m., confirmed the above deficiency.






 Plan of Correction - To be completed: 02/20/2024

The facility had an Emergency Preparedness Plan that included a written training and testing program that was reviewed and updated on August 18, 2023. The Maintenance Director and NHA will be educated on 483.73(d):] (d) by the RDO/Designee by February 20,2024. The facility will review and update the Emergency Preparedness manual annually before April 18, 2024 and as needed to capture changes. Results will be monitored in QA/QI monthly to maintain compliance.
403.748(d)(2), 416.54(d)(2), 418.113(d)(2), 441.184(d)(2), 482.15(d)(2), 483.475(d)(2), 483.73(d)(2), 484.102(d)(2), 485.542(d)(2), 485.625(d)(2), 485.68(d)(2), 485.727(d)(2), 485.920(d)(2), 486.360(d)(2), 491.12(d)(2), 494.62(d)(2) STANDARD EP Testing Requirements:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
§416.54(d)(2), §418.113(d)(2), §441.184(d)(2), §460.84(d)(2), §482.15(d)(2), §483.73(d)(2), §483.475(d)(2), §484.102(d)(2), §485.68(d)(2), §485.542(d)(2), §485.625(d)(2), §485.727(d)(2), §485.920(d)(2), §491.12(d)(2), §494.62(d)(2).

*[For ASCs at §416.54, CORFs at §485.68, REHs at §485.542, OPO, "Organizations" under §485.727, CMHCs at §485.920, RHCs/FQHCs at §491.12, and ESRD Facilities at §494.62]:

(2) Testing. The [facility] must conduct exercises to test the emergency plan annually. The [facility] must do all of the following:

(i) Participate in a full-scale exercise that is community-based every 2 years; or
(A) When a community-based exercise is not accessible, conduct a facility-based functional exercise every 2 years; or
(B) If the [facility] experiences an actual natural or man-made emergency that requires activation of the emergency plan, the [facility] is exempt from engaging in its next required community-based or individual, facility-based functional exercise following the onset of the actual event.
(ii) Conduct an additional exercise at least every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [facility's] response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the [facility's] emergency plan, as needed.

*[For Hospices at 418.113(d):]
(2) Testing for hospices that provide care in the patient's home. The hospice must conduct exercises to test the emergency plan at least annually. The hospice must do the following:
(i) Participate in a full-scale exercise that is community based every 2 years; or
(A) When a community based exercise is not accessible, conduct an individual facility based functional exercise every 2 years; or
(B) If the hospice experiences a natural or man-made emergency that requires activation of the emergency plan, the hospital is exempt from engaging in its next required full scale community-based exercise or individual facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.

(3) Testing for hospices that provide inpatient care directly. The hospice must conduct exercises to test the emergency plan twice per year. The hospice must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual facility-based functional exercise; or
(B) If the hospice experiences a natural or man-made emergency that requires activation of the emergency plan, the hospice is exempt from engaging in its next required full-scale community based or facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop led by a facilitator that includes a group discussion using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the hospice's response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the hospice's emergency plan, as needed.


*[For PRFTs at §441.184(d), Hospitals at §482.15(d), CAHs at §485.625(d):]
(2) Testing. The [PRTF, Hospital, CAH] must conduct exercises to test the emergency plan twice per year. The [PRTF, Hospital, CAH] must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or
(B) If the [PRTF, Hospital, CAH] experiences an actual natural or man-made emergency that requires activation of the emergency plan, the [facility] is exempt from engaging in its next required full-scale community based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an [additional] annual exercise or and that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, a facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [facility's] response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the [facility's] emergency plan, as needed.

*[For PACE at §460.84(d):]
(2) Testing. The PACE organization must conduct exercises to test the emergency plan at least annually. The PACE organization must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or
(B) If the PACE experiences an actual natural or man-made emergency that requires activation of the emergency plan, the PACE is exempt from engaging in its next required full-scale community based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or individual, a facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the PACE's response to and maintain documentation of all drills, tabletop exercises, and emergency events and revise the PACE's emergency plan, as needed.

*[For LTC Facilities at §483.73(d):]
(2) The [LTC facility] must conduct exercises to test the emergency plan at least twice per year, including unannounced staff drills using the emergency procedures. The [LTC facility, ICF/IID] must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise.
(B) If the [LTC facility] facility experiences an actual natural or man-made emergency that requires activation of the emergency plan, the LTC facility is exempt from engaging its next required a full-scale community-based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the [LTC facility] facility's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the [LTC facility] facility's emergency plan, as needed.

*[For ICF/IIDs at §483.475(d)]:
(2) Testing. The ICF/IID must conduct exercises to test the emergency plan at least twice per year. The ICF/IID must do the following:
(i) Participate in an annual full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise; or.
(B) If the ICF/IID experiences an actual natural or man-made emergency that requires activation of the emergency plan, the ICF/IID is exempt from engaging in its next required full-scale community-based or individual, facility-based functional exercise following the onset of the emergency event.
(ii) Conduct an additional annual exercise that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the ICF/IID's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the ICF/IID's emergency plan, as needed.

*[For HHAs at §484.102]
(d)(2) Testing. The HHA must conduct exercises to test the emergency plan at
least annually. The HHA must do the following:
(i) Participate in a full-scale exercise that is community-based; or
(A) When a community-based exercise is not accessible, conduct an annual individual, facility-based functional exercise every 2 years; or.
(B) If the HHA experiences an actual natural or man-made emergency that requires activation of the emergency plan, the HHA is exempt from engaging in its next required full-scale community-based or individual, facility based functional exercise following the onset of the emergency event.
(ii) Conduct an additional exercise every 2 years, opposite the year the full-scale or functional exercise under paragraph (d)(2)(i) of this section is conducted, that may include, but is not limited to the following:
(A) A second full-scale exercise that is community-based or an individual, facility-based functional exercise; or
(B) A mock disaster drill; or
(C) A tabletop exercise or workshop that is led by a facilitator and includes a group discussion, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(iii) Analyze the HHA's response to and maintain documentation of all drills, tabletop exercises, and emergency events, and revise the HHA's emergency plan, as needed.

*[For OPOs at §486.360]
(d)(2) Testing. The OPO must conduct exercises to test the emergency plan. The OPO must do the following:
(i) Conduct a paper-based, tabletop exercise or workshop at least annually. A tabletop exercise is led by a facilitator and includes a group discussion, using a narrated, clinically relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan. If the OPO experiences an actual natural or man-made emergency that requires activation of the emergency plan, the OPO is exempt from engaging in its next required testing exercise following the onset of the emergency event.
(ii) Analyze the OPO's response to and maintain documentation of all tabletop exercises, and emergency events, and revise the [RNHCI's and OPO's] emergency plan, as needed.

*[ RNCHIs at §403.748]:
(d)(2) Testing. The RNHCI must conduct exercises to test the emergency plan. The RNHCI must do the following:
(i) Conduct a paper-based, tabletop exercise at least annually. A tabletop exercise is a group discussion led by a facilitator, using a narrated, clinically-relevant emergency scenario, and a set of problem statements, directed messages, or prepared questions designed to challenge an emergency plan.
(ii) Analyze the RNHCI's response to and maintain documentation of all tabletop exercises, and emergency events, and revise the RNHCI's emergency plan, as needed.
Observations:
Name: - Component: -- - Tag: 0039

Based on document review and interview, it was determined the facility failed to meet emergency preparation testing requirements in the emergency preparedness plan.

Findings include:

1. Documentation review on January 22, 2024, at 8:40 a.m., reveled the facility failed to meet the annual requirements for a community-based, full-scale exercise.

Interview with the Facility Administrator on January 22, 2024, at 12:30 p.m., confirmed the above deficiency.





 Plan of Correction - To be completed: 02/20/2024

The facility conducted a community based, full scale exercise on April 14, 2023. The documentation was located after the survey ended. The Maintenance Director and NHA will be educated on 483.73(d):] by the RDO/Designee by February 20, 2024. The facility will participate in annual full scale exercise that is community based or annual individual, facility based functional exercise for 2024. Results will be monitored in QA/QI monthly to maintain compliance.
Initial comments:Name: MAIN BUILDING 01 - Component: 01 - Tag: 0000


Facility ID# 341202
Component 01
Main Building

Based on a Medicare/Medicaid Recertification Survey completed on January 22, 2024, it was determined that Havencrest Nursing Center was not in compliance with the following requirements of the Life Safety Code for an existing health care occupancy. Compliance with the National Fire Protection Association's Life Safety Code is required by 42 CFR 483.90(a).

This is a one-story, Type II (000), unprotected noncombustible building, with a basement, that is fully sprinklered.


 Plan of Correction:


NFPA 101 STANDARD Doors with Self-Closing Devices:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Doors with Self-Closing Devices
Doors in an exit passageway, stairway enclosure, or horizontal exit, smoke barrier, or hazardous area enclosure are self-closing and kept in the closed position, unless held open by a release device complying with 7.2.1.8.2 that automatically closes all such doors throughout the smoke compartment or entire facility upon activation of:
* Required manual fire alarm system; and
* Local smoke detectors designed to detect smoke passing through the opening or a required smoke detection system; and
* Automatic sprinkler system, if installed; and
* Loss of power.
18.2.2.2.7, 18.2.2.2.8, 19.2.2.2.7, 19.2.2.2.8
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0223


Based on observation and interview, it was determined the facility failed to maintain the self-closing doors in one instance, affecting one of four smoke compartments.

Findings include:

1. Observation on January 22, 2024, at 10:18 a.m., revealed the door to the housekeeping closet by the restroom failed to latch when tested.

Interview with the Facility Administrator on January 22, 2024, at 12:30 p.m., confirmed the above listed self-closing door deficiency.





 Plan of Correction - To be completed: 02/20/2024

The self closing door to the housekeeping closet by the restroom was adjusted so that the door would close to the latched position. During that assessment and adjustment the door was noted to be defective and prevents the door from closing to the latched position without pulling it closed completely. The facility will contact an individual to provide the purchase and installation of the existing door. All other self closing doors will be checked and adjusted to ensure the device closes the door in the latched position. The Maintenace Director will be educated on NFPA 7.2.1.8.2 by the NHA/Designee by February 20, 2024. An audit of all doors with self closing devices will be completed weekly x4 by the Maintenance Director/Designee, followed by monthly x2. Results will be monitored in QA/QI meetings x3 months.
NFPA 101 STANDARD Emergency Lighting:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Emergency Lighting
Emergency lighting of at least 1-1/2-hour duration is provided automatically in accordance with 7.9.
18.2.9.1, 19.2.9.1
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0291


Based on observation and interview, it was determined the facility failed to maintain emergency lighting in one instance, affecting one of four smoke compartments.

Findings include:

1, Observation on January 22, 2024, at 10:45 a.m., revealed the emergency battery lighting, in the kitchen, failed to illuminate when the test button was depressed.

Interview with the Facility Administrator on January 22, 2024, at 12:30 p.m., confirmed the emergency battery lighting in the kitchen failed to illuminate when tested.



 Plan of Correction - To be completed: 02/20/2024

The facility replaced the battery to the Emergency lighting in the kitchen so that it illuminated when the test button was depressed. The facility will check all Emergency lighting to ensure they illuminate when the test button is depressed. The Maintenance Director will be educated on NFPA 101 Emergency Lighting by the NHA/Designee by February 20, 2024. Weekly audits x4 weeks of all Emergency lighting will be completed by the Maintenance Director/Designee, followed by monthly x2. Results will be monitored in QA/QI x 3months
NFPA 101 STANDARD Exit Signage:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Exit Signage
2012 EXISTING
Exit and directional signs are displayed in accordance with 7.10 with continuous illumination also served by the emergency lighting system.
19.2.10.1
(Indicate N/A in one-story existing occupancies with less than 30 occupants where the line of exit travel is obvious.)
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0293


Based on document review and interview, it was determined the facility failed to perform the monthly exit sign inspection for one of twelve months, affecting the entire facility.

Findings Include:

1. Document review on January 22, 2024, at 8:53 a.m., revealed the facility lacked documentation for the monthly exit sign inspections for the month of December 2023.

Interview with the Facility Administrator on January 22, 2024, at 12:30 p.m., confirmed the facility lacked documentation for exit sign inspection at the time of the survey.





 Plan of Correction - To be completed: 02/20/2024

All exit signs will be inspected and documented in accordance with 7.9.18.2.9.1, 19.2.9.1. The Maintenance Director will be educated on NFPA 7.9.18.2.9.1, 19.2.9.1 by the NHA/Designee by February 20, 2024. An audit of all exit signs will be completed and documented by the Maintenance Director weekly x4 weeks, followed by monthly exit sign inspections x2 months. Results will be monitored in QA/QI meetings x3 months.
NFPA 101 STANDARD Cooking Facilities:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Cooking Facilities
Cooking equipment is protected in accordance with NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, unless:
* residential cooking equipment (i.e., small appliances such as microwaves, hot plates, toasters) are used for food warming or limited cooking in accordance with 18.3.2.5.2, 19.3.2.5.2
* cooking facilities open to the corridor in smoke compartments with 30 or fewer patients comply with the conditions under 18.3.2.5.3, 19.3.2.5.3, or
* cooking facilities in smoke compartments with 30 or fewer patients comply with conditions under 18.3.2.5.4, 19.3.2.5.4.
Cooking facilities protected according to NFPA 96 per 9.2.3 are not required to be enclosed as hazardous areas, but shall not be open to the corridor.
18.3.2.5.1 through 18.3.2.5.4, 19.3.2.5.1 through 19.3.2.5.5, 9.2.3, TIA 12-2




Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0324


Based on observation and interview, it was determined the facility failed to properly install and maintain equipment protected by the kitchen hood extinguishing system in one instance, affecting one of four smoke compartments.

Findings Include:

1. Observation on January 22, 2024, at 11:40 a.m., revealed a gas-fired oven on wheels, in the main kitchen, was not provided with an approved method that would ensure the appliance was returned to an approved design location after it had been moved for maintenance and cleaning, as required by section 12.1.2.3 and 12.1.2.3.1 of NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations.

Interview with the Facility Administrator on January 22, 2024, at 12:30 p.m., confirmed the gas-fired cooking appliance was not tethered in a way so it could not be moved from the ventilation hood and gas connection.




 Plan of Correction - To be completed: 02/20/2024

The facility will install an approved method to ensure the gas fired cooking appliance is tethered in a way so that it does not move from the ventilation hood and gas connection. The NHA will educate the Maintenance Director on NFPA 12.1.2.3, 12.1.2.3.1 by February 20, 2024. An audit of the gas fired appliance tethering will be completed by the Maintenance Director daily x 2 weeks, followed by weekly x4 and then monthly x2 months. Results will be monitored in QA/QI meetings x3 months.
NFPA 101 STANDARD Corridor - Doors:This is a less serious (but not lowest level) deficiency and affects more than a limited number of residents, staff, or occurrences. This deficiency is one that results in minimal discomfort to the resident or has the potential (not yet realized) to negatively affect the resident's ability to achieve his/her highest functional status. This deficiency was not found to be throughout this facility.
Corridor - Doors
Doors protecting corridor openings in other than required enclosures of vertical openings, exits, or hazardous areas resist the passage of smoke and are made of 1 3/4 inch solid-bonded core wood or other material capable of resisting fire for at least 20 minutes. Doors in fully sprinklered smoke compartments are only required to resist the passage of smoke. Corridor doors and doors to rooms containing flammable or combustible materials have positive latching hardware. Roller latches are prohibited by CMS regulation. These requirements do not apply to auxiliary spaces that do not contain flammable or combustible material.
Clearance between bottom of door and floor covering is not exceeding 1 inch. Powered doors complying with 7.2.1.9 are permissible if provided with a device capable of keeping the door closed when a force of 5 lbf is applied. There is no impediment to the closing of the doors. Hold open devices that release when the door is pushed or pulled are permitted. Nonrated protective plates of unlimited height are permitted. Dutch doors meeting 19.3.6.3.6 are permitted. Door frames shall be labeled and made of steel or other materials in compliance with 8.3, unless the smoke compartment is sprinklered. Fixed fire window assemblies are allowed per 8.3. In sprinklered compartments there are no restrictions in area or fire resistance of glass or frames in window assemblies.

19.3.6.3, 42 CFR Parts 403, 418, 460, 482, 483, and 485
Show in REMARKS details of doors such as fire protection ratings, automatics closing devices, etc.
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0363


Based on observation and interview, it was determined that the facility failed to maintain corridor doors in one instance, affecting one of four smoke compartments.

Findings include:

1. Observation on January 22, 2024, at 10:05 a.m., revealed the door to resident room #14 failed to latch when tested.

Interview with the Facility Administrator on January 22, 2024, at 12:30 p.m., confirmed the door to the resident room failed to latch.




 Plan of Correction - To be completed: 02/20/2024

The door to resident room #14 will be adjusted so that the door latches. All other resident room doors will be checked and adjusted to ensure doors latch. The NHA will educate the Maintenance Director on NFPA 101 Corridor—Doors by February 20, 2024. An audit of 50% of resident room doors to ensure latching will be completed by the Maintenance Director weekly x4 weeks, followed by monthly x2 months. Results will be monitored in QA/QI x3 months.
NFPA 101 STANDARD Fire Drills:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Fire Drills
Fire drills include the transmission of a fire alarm signal and simulation of emergency fire conditions. Fire drills are held at expected and unexpected times under varying conditions, at least quarterly on each shift. The staff is familiar with procedures and is aware that drills are part of established routine. Where drills are conducted between 9:00 PM and 6:00 AM, a coded announcement may be used instead of audible alarms.
19.7.1.4 through 19.7.1.7
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0712

Based on documentation review and interview, it was determined the facility failed to perform one of twelve required fire drills, affecting the entire facility.

Findings include:

1. Review of documentation on January 22, 2024, at 9:12 a.m., revealed the facility lacked documentation for a fire drill performed in November of 2023.

Interview with the Facility Administrator on January 22, 2024, at 12:30 p.m., confirmed the facility lacked documentation for the above listed fire drill.






 Plan of Correction - To be completed: 02/20/2024

The facility found missing documentation to support a fire drill was conducted for the month of November 2023 and was placed in the Life Safety manual on January 27, 2024. A fire drill was completed for December 2023 and January 2024 with supporting documentation placed in the Life Safety manual. The Maintenance Director will be educated on NFPA 101 Fire Drills by the NHA by February 20, 2024. The NHA will audit fire drills monthly for completion to maintain compliance. Results will be monitored in QA/QI x3 months.
NFPA 101 STANDARD Electrical Systems - Essential Electric Syste:Least serious deficiency but was found to be widespread throughout the facility and/or has the potential to affect a large portion or all the residents. This deficiency has the potential for causing no more than a minor negative impact on the resident.
Electrical Systems - Essential Electric System Maintenance and Testing
The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110.
Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for 4 continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked, readily identifiable, and separate from normal power circuits. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations.
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70)
Observations:
Name: MAIN BUILDING 01 - Component: 01 - Tag: 0918


Based on documentation review and interview, it was determined the facility failed to perform emergency generator maintenance testing for 2 of the last 12 months, effecting the entire facility.

Findings include:

1. Review of documentation on January 22, 2024, at 9:05 a.m., revealed the facility lacked documentation verifying that the following items were performed in the last two months:

a) 9:05 a.m., the required monthly testing of battery electrolyte specific gravity or conductance testing in the month of November;
b) 9:08 a.m., the required weekly visual inspection and battery electrolyte levels or battery voltage.

Interview with the Facility Administrator on January 22, 2024, at 12:30 p.m., confirmed the above listed generator deficiencies.


 Plan of Correction - To be completed: 02/20/2024

The facility will complete a test of battery electrolyte specific gravity/conductance testing and a visual inspection of battery electrolyte levels or battery voltage. The NHA will educate the Maintenance Director on NFPA 110, 111 by February 20, 2024. The weekly and monthly testing will be completed by the Maintenance Director. The NHA will audit weekly and monthly testing for completion. The results will be monitored in QA/QI x3 months.